, I 1 11 1 1 13 s R"I i I 1. 19 11..1 -WIN..,1w Mug _1,1 1 11! 1 ' !.1 'I' I 1 111TIVIRI, I i
<br />1 I 2 I 3 I 4
<br />a
<br />rn
<br />N
<br />tf
<br />CM
<br />to
<br />O
<br />N
<br />0
<br />Q
<br />LO
<br />N
<br />co
<br />PLUMBING SPECIFICATIONS`
<br />1.00 - GENERAL PROVISIONS
<br />1.01 PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY OPERATING
<br />PLUMBING SYSTEM.
<br />1.02 CODES AND STANDARDS: ALL PLUMBING WORK SHALL BE IN STRICT COMPLIANCE WITH THE 2017
<br />FLORIDA PLUMBING CODE AND ALL LOCAL CODES HAVING JURISDICTION.
<br />1.03 ALL PLUMBING WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. CONTRACTOR
<br />SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED FOR THE EXECUTION OF
<br />THIS WORK.
<br />1.04 CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES BEFORE FABRICATION OR
<br />INSTALLATION. OFFSETS AND/OR TRANSITIONS REQUIRED SHALL BE PROVIDED WITHOUT
<br />ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL HIS WORK IN A TIMELY
<br />MANNER TO PREVENT DELAYS IN THE CONSTRUCTION.
<br />1.05 CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT AND/OR
<br />MATERIAL.
<br />1.06 PROVIDE ALL MATERIALS REQUIRED TO PROPERLY SUPPORT ALL PIPING ANDEQUIPMENT. PIPE
<br />HANGERS SHALL BE ADJUSTABLE TYPE AND BE SPACED IN ACCORDANCE WITH THE FLORIDA
<br />PLUMBING CODE. PROVIDED PLASTIC COATED RING ON HANGERS FOR COPPER PIPING TO
<br />PROVIDE DIELECTRIC ISOLATION.
<br />1.07 PROVIDE DIELECTRIC UNIONS OR FLANGES BETWEEN COPPER AND STEEL PIPING AND BETWEEN
<br />BRASSWARE AND STEEL. DO NOT USE STEEL AND COPPER PIPING IN THE SAME SYSTEM
<br />WITHOUT SUCH ISOLATION.
<br />1.08 PROVIDE REDUCING FITTINGS (REDUCING BUSHINGS SHALL NOT BE USED) WHERE CHANGES IN
<br />PIPE SIZES OCCUR.
<br />1.09 THIS CONTRACTOR SHALL SUPPLY AND INSTALL ALL SERVICES THROUGHOUT THE BUILDING AND
<br />MAKE CONNECTION TO SITE UTILITIES APPROXIMATELY 6-0" OUTSIDE THE BUILDING.
<br />CONTRACTOR SHALL SUPPLY AND INSTALL FIXTURES, FITTINGS, VALVING AND TRIM AND MAKE
<br />READY FOR USE ALL FIXTURES, EQUIPMENT, ETC.
<br />1.10 SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
<br />2.00 - BASIC MATERIALS AND METHODS
<br />2.01 DOMESTIC WATER - ABOVEGROUND WATER PIPE AND FITTINGS - TYPE "L" COPPER.
<br />2.02 PROVIDE UNIONS OR FLANGES IN ALL DOMESTIC WATER SERVICE LINES AT EACH PIECE OF
<br />EQUIPMENT, SPECIALTY VALVES OR AT OTHER LOCATIONS REQUIRED FOR READY DISCONNECT.
<br />2.03 WATER HAMMER ARRESTORS SHALL BE INSTALLED AT THE LOCATIONS ON THE PLANS AND IN
<br />ACCORDANCE WITH PDI STANDARD WH-201. PRODUCTS SHALL BE EQUAL TO THOSE
<br />MANUFACTURED BY PRECISION PLUMBING PRODUCTS OR SIOUX CHIEF.
<br />2.04 VALVES: PROVIDE VALVES TO ISOLATE EACH RISER, BRANCH LINE AND PIECE OF EQUIPMENT.
<br />2.05 PROVIDE PRESSURE REDUCING VALVE AND AIR GAP CONNECTION AT DISHWASHER AS REQUIRED
<br />BY CODE AND ACCORDING TO MANUFACTURER.
<br />2.06 PROVIDE INLINE WATER FILTER AT WATER DISPENSERS, COFFEE MAKER AND ICE MAKER TO
<br />REMOVE MATERIALS, TASTE AND ODOR - "EVERPURE OR "SYSTEMS W.
<br />2.07 SANITARY WASTE (NON -PRESSURE), SANITARY VENT AND STORM PIPING - ABOVE GROUND - PVC
<br />SCH40 DWV PIPE AND FITTINGS.
<br />2.08 CONDENSATE PIPING - PVC SCH-40 DWV PIPE AND FITTINGS.
<br />2.09 INSTALL GRAVITY LINES SLOPED AT 1/8" PER FOOT FOR PIPE 3" AND LARGER AND 1/4+' PER FOOT
<br />FOR PIPE SMALLER THAN 3". VERIFY INVERT ELEVATION WITH EXISTING PIPING PRIOR TO ANY
<br />PIPE BEING INSTALLED.
<br />2.10 PROVIDE AND PROPERLY LOCATE HANGERS TO ADEQUATELY SUPPORT PIPING. ARRANGE
<br />HANGERS TO PERMIT EXPANSION AND CONTRACTION. DO NOT HANG PIPING FROM FIRE OR
<br />SMOKE WALLS. PROVIDE PIPE HANGERS AT EACH VALVE, STRAINER, AND OTHER PIPING
<br />ACCESSORY, AND AT EACH CHANGE OR DIRECTION.
<br />2.11 THE SIZE OF HANGERS FOR NON -INSULATED PIPES SHALL BE SUITABLE FOR THE PIPE SIZE TO BE
<br />SUPPORTED. FOR INSULATED PIPING, THE SIZE OF THE HANGER SHALL BE SUITABLE FOR THE
<br />PIPE SIZE, PLUS THE INSULATION AND INSULATION SHIELD.
<br />EXISTING WALL HUNG SINK
<br />2.12 SPACING: LOCATE PIPE SUPPORTS AS INDICATED IN THE FOLLOWING TABLE:
<br />HORIZONTAL PIPE HANGER SCHEDULE
<br />MATERIAL
<br />PIPE SIZE
<br />HANGER SPACING
<br />COPPER TUBING
<br />UP T01 114 INCH
<br />1 1/2 INCH AND ABOVE
<br />6 FOOT CENTERS
<br />10 FOOT CENTERS
<br />CAST IRON PIPE
<br />ALL
<br />5 FOOT CENTERS
<br />3.00 - PLUMBING FIXTURES AND TRIM
<br />3.01 ALL PLUMBING FIXTURES SHALL BE "FIRST QUALITY" AS DEFINED AND SET FORTH IN COMMERCIAL
<br />STANDARD CS77-28 AS PROMULGATED BY THE U.S. DEPARTMENT OF COMMERCE.
<br />3.02 ALL FIXTURES ARE TO BE WHITE VITREOUS CHINA UNLESS OTHERWISE SPECIFICALLY NOTED.
<br />FIXTURES AND FITTINGS PROPOSED SHALL BE FROM ONE MANUFACTURER AND OF SIMILAR
<br />CHARACTER IN ANY ROOM OR LOCATION. ESCUTCHEONS, HANDLES, ETC., ON THE DIFFERENT
<br />FIXTURES SHALL BE OF THE SAME DESIGN.
<br />3.03 PROVIDE FIXTURE CARRIERS AS RECOMMENDED BY FIXTURE MANUFACTURER AND/OR
<br />CONSTRUCTION METHOD.
<br />3.04 PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE NON -ACCESSIBLE CEILINGS.
<br />REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
<br />3.05 FLOOR DRAIN TRAP SEALS SHALL HAVE AN APPROVED PRIMING DEVICE DESIGNED FOR THAT
<br />PURPOSE.
<br />3.06 ALL CONCEALED TRAPS, PRIMERS, VALVES, CLEANOUTS, ETC. LOCATED IN TILED AREAS SHALL BE
<br />PROVIDED WITH AN ACCESS PANEL.
<br />4.00 - INSULATION
<br />4.01 ABOVE GROUND COLD AND HOT WATER PIPING - FIBERGLASS, 1" THICKNESS, ASJ JACKET,
<br />DOUBLE SEALING LAP JOINT, 0.24 K AT 75°F. INSULATION AND ADHESIVES INSTALLED IN RETURN
<br />AIR PLENUMS SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE
<br />DEVELOPED RATING OF 50.
<br />4.02 ABOVE GROUND STORM PIPING - FIBERGLASS, 1/2" THICKNESS, ASJ JACKET, DOUBLE SEALING LAP
<br />JOINT, 0.24 K AT 757. INSULATION AND ADHESIVES INSTALLED IN RETURN AIR PLENUMS SHALL
<br />HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE DEVELOPED RATING OF
<br />50.
<br />4.03 ABOVEGROUND CONDENSATE PIPING SHALL BE 1/2" FLEXIBLE UNICELLULAR POLYOLEFIN FOAM
<br />AND SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE DEVELOPED
<br />RATING OF 50-IMCOA "IMCOLOCK".
<br />5.00 - VALVES AND COCKS
<br />5.01 VALVES 2" AND SMALLER SHALL BE BALL VALVES, 150 PSI SWP, 400 PSI WOG. STANDARD PORT
<br />BALL, BRONZE TRIM, CAST BRONZE BODY, CHROMIUM -PLATED BRASS BALL, BRONZE NON -
<br />BLOWOUT STEM, TEFLON SEAT, DOUBLE 0-RING STEM SEALS, ZINC -COATED STEEL HANDLE WITH
<br />PLASTIC COATED HAND GRIP, 90 DEGREE OPERATION FROM FULL OPEN TO TIGHT SHUT-OFF -
<br />STOCKHAM S214-BR-T-T, STOCKHAM S216-BR-T-S OR EQUAL.
<br />5.02 CHECK VALVES, ROUGH BRASS, REGRINDING BRONZE DISC - STOCKHAM B-345; B-309 OR EQUAL.
<br />6.00 - STERILIZATION
<br />6.01 DOMESTIC WATER PIPING SHALL BE THOROUGHLY FLUSHED OUT AND STERILIZED IN
<br />ACCORDANCE WITH THE FLORIDA PLUMBING CODE.
<br />PLUMBING FIXTURE SCHEDULE
<br />CHROME PLATED CAST BRASS GRID STAINER WITH 1-1/4" O.D. OFFSET TAILPIECE, CHROME PLATED
<br />17 GAUGE 1-1/4"X1-1/2" BRASS P-TRAP W/ CLEANOUT PLUG AND SLIP NUTS. PROVIDE P-TRAP AND
<br />TAILPIECE WITH PREWRAPPED SEAMLESS MOLDED CLOSED CELL VINYL INSULATION WITH FLEXIBLE
<br />COLLARS TO ALLOW PIPE CONNECTION. PRE -WRAPPED DRAIN INSULATION KIT SHALL INCLUDE HOT
<br />AND COLD ANGLE STOPS AND WATER SUPPLY COVERS OF SAME MATERIAL.
<br />3/8" I.P.S. CHROME PLATED ANGLE SUPPLY, LOOSE KEY STOP, REDUCER, WROUGHT BRASS DEEP
<br />BELL FLANGE ESCUTCHEON AND 1/2" CHROME PLATED COPPER EXTENSION TUBE.
<br />CONCEALED ARMS FLOOR MOUNTED CARRIER: COATED STEEL UPRIGHTS WITH WELDED FEET, CAST
<br />IRON ADJUSTABLE HEADERS, STEEL SLEEVES, ALIGNMENT TRUSS AND FASTENERS.
<br />BASIS OF DESIGN
<br />SINK - EXISTING FOR REUSE
<br />FAUCET - EXISTING FOR REUSE
<br />STRAINERITRAP - MCGUIRE 155WC/PW 2150 WC (PROVIDE NEW)
<br />SUPPLIES - MCGUIRE H170LK (PROVIDE NEW)
<br />CARRIER - ZURN ZR-1231 (PROVIDE NEW)
<br />EXISTING TRIPLE COMPARTMENT SINK
<br />CHROME PLATED CAST BRASS GRID STAINER WITH 1-1/4" O.D. OFFSET TAILPIECE, CHROME PLATED
<br />17 GAUGE 1-1/4"X1-1/2" BRASS P-TRAP W/ CLEANOUT PLUG AND SLIP NUTS. PROVIDE P-TRAP AND
<br />TAILPIECE WITH PREWRAPPED SEAMLESS MOLDED CLOSED CELL VINYL INSULATION WITH FLEXIBLE
<br />COLLARS TO ALLOW PIPE CONNECTION. PRE -WRAPPED DRAIN INSULATION KIT SHALL INCLUDE HOT
<br />AND COLD ANGLE STOPS AND WATER SUPPLY COVERS OF SAME MATERIAL.
<br />3/8" I.P.S. CHROME PLATED ANGLE SUPPLY, LOOSE KEY STOP, REDUCER, WROUGHT BRASS DEEP
<br />BELL FLANGE ESCUTCHEON AND 1/2" CHROME PLATED COPPER EXTENSION TUBE.
<br />CONCEALED ARMS FLOOR MOUNTED CARRIER: COATED STEEL UPRIGHTS WITH WELDED FEET, CAST
<br />IRON ADJUSTABLE HEADERS, STEEL SLEEVES, ALIGNMENT TRUSS AND FASTENERS.
<br />BASIS OF DESIGN
<br />SINK - EXISTING FOR REUSE
<br />FAUCET - EXISTING FOR REUSE
<br />STRAINER/TRAP - MCGUIRE 155WC/PW 2150 WC (PROVIDE NEW)
<br />SUPPLIES - MCGUIRE H170LK (PROVIDE NEW)
<br />MOP SINK
<br />FLOOR SINK
<br />PRECAST TERRAllO WITH STAINLESS STEEL CAP, 24"x24N12" TERRAllO SHALL BE MADE OF GREY
<br />12"X12"X10" DEEP CAST IRON BODY WITH WHITE ACID RESISTING PORCELAIN ENAMEL INTERIOR, ALUMINUM
<br />MARBLE CHIPS CAST IN WHITE PORTLAND CEMENT TO PRODUCE A COMPRESSIVE STRENGTH OF NOT
<br />ANTI -SPLASH INTERIOR BOTTOM DOME STRAINER AND NICKEL BRONZE TOP.
<br />LESS THAN 3,000 PSI. TERRAllO SURFACE SHALL BE GROUND AND POLISHED WITH ALL AIR HOLES
<br />AND/OR PITS TO BE GROUTED AND EXCESS REMOVED. DRAIN BODY SHALL BE STAINLESS STEEL CAST
<br />BASIS OF DESIGN
<br />INTEGRAL, AND SHALL PROVIDE FOR A CAULKED LEAD CONNECTION AND NOT LESS THAN 1" DEEP TO
<br />A 3" PIPE.
<br />ZURN - Z1902T
<br />TYPE 304, 20-GAUGE STAINLESS STEEL SPLASH PANELS, 12" HEIGHT SECURED TO WALL ON 2 SIDES,
<br />TRENCH DRAIN
<br />SERVICE FAUCET SHALL BE CHROME PLATED WITH REVNEWABLE SEATS IN MONEL, VACUUM BREAKER,
<br />INTEGRAL STOPS AND SPRING CHECK VALVES, ADJUSTABLE WALL BRACE, PAIL HOOK, AND 3/4" HOSE
<br />A
<br />12" WIDE TOP MODULAR, HEAVY DUTY TRENCH DRAIN
<br />THREAD ON SPOUT.
<br />BASIS OF DESIGN
<br />BASIS OF DESIGN
<br />ZURN - Z665
<br />SINK - WILLIAMS SBC-1700-2-BP
<br />FAUCET - T&S BRASS-B-0665-BST'P
<br />CART WASH
<br />8" WALL MOUNT MIXING FAUCET WITH POLISHED CHROME PLATED BRASS BODY, 90 DEGREE SWIVEL WITH
<br />WATER SOFTENER
<br />VACUUM BREAKER, 44" FLEXIBLE STAINLESS STEEL HOSE WITH HEAT RESISTANT HANDLE,1.15 GPM ANGLED
<br />SPRAY VALVE, COMPRESSION CARTRIDGES WITH SPRING CHECKS, LEVEL HANDLES, 1/2" NPT FEMALE INLETS
<br />MIN FLOW (GPM) - 2.79
<br />AND SPRAY VALVE HOLDER. CERTIFIED TO ASME Al 12.18.1/CSA B125.1, NSF 61 SECTION 9 AND NSF372.2019
<br />SERVICE FLOW (GPM, 15 PSI) - 56
<br />DOE PRSV - CLASS II COMPLIANT.
<br />CAPACITY (KGRAINS) -120
<br />120 V CONNECTION PER VESSEL
<br />BASIS OF DESIGN
<br />BASIS OF DESIGN
<br />T&S BRASS - B-0167-HH
<br />EVOQUA- PTCSSD07-16x65T B
<br />PLUMBING SYMBOL LEGEND
<br />SYMBOL DESCRIPTION
<br />=====AV====
<br />AW
<br />-----AW====
<br />CO2
<br />CA
<br />CD
<br />=====CD====
<br />DA
<br />DI
<br />DV
<br />FOF
<br />FOG
<br />FOR
<br />FOS
<br />====-FOV===-
<br />Ci K
<br />MA
<br />MV
<br />NI
<br />N20
<br />OX
<br />ST
<br />=====ST=====
<br />STO
<br />=====STO===-
<br />M
<br />11 C -
<br />- -
<br />001
<br />Coll
<br />CO I' 0
<br />CO
<br />FD EC
<br />FD CC -
<br />CO
<br />FS IC
<br />i
<br />G
<br />Y
<br />G
<br />C
<br />_MML AP-XX
<br />_EZ�L MAP-XX
<br />11 MGO-XX
<br />III III MGV-XX
<br />1
<br />P2.01
<br />- ACID VENT
<br />- ACID WASTE
<br />- BELOW GROUND ACID WASTE
<br />- CARBON DIOXIDE
<br />- COMPRESSED AIR
<br />- ABOVE GROUND CONDENSATE DRAIN
<br />- BELOW GROUND CONDENSATE DRAIN
<br />- DENTAL AIR
<br />- DEIONIZED WATER
<br />- DENTAL VACUUM
<br />- DOMESTIC COLD WATER
<br />- DOMESTIC HOT WATER
<br />- DOMESTIC HOT WATER RETURN
<br />- FUEL OIL FILL
<br />- FUEL OIL GAGE
<br />- FUEL OIL RETURN
<br />- FUEL OIL SUPPLY
<br />- FUEL OIL VENT
<br />-GAS
<br />- KITCHEN WASTE (GREASE)
<br />- MEDICAL COMPRESSED AIR
<br />- MEDICAL VACUUM
<br />- NITROGEN
<br />- NITROUS OXIDE
<br />-OXYGEN
<br />- ABOVE GROUND SANITARY
<br />-BELOW GROUND SANITARY
<br />- SANITARY VENT
<br />- ABOVE GROUND STORM
<br />- BELOW GROUND STORM
<br />- OVERFLOW STORM DRAIN
<br />- BELOW GROUND OVERFLOW STORM
<br />- SOFT COLD WATER
<br />- WATER METER
<br />- HOSE BIBB OR WALL HYDRANT
<br />- CLEAN OUT PLUG
<br />- WALL CLEANOUT
<br />- WALL CLEANOUT
<br />- FLOOR CLEAN OUT
<br />- FLOOR DRAIN
<br />- ROOF DRAIN
<br />- FLOOR SINK
<br />- SHUT-OFF VALVE IN VALVE BOX
<br />- SHUTOFF VALVE
<br />- BALL VALVE
<br />- CALIBRATED BALANCING VALVE
<br />- CHECK VALVE (SWING)
<br />- PRESSURE REDUCING VALVE '
<br />- SOLENOID OPERATED VALVE
<br />- REDUCED PRESSURE BACKFLOW PREVENTER
<br />- RELIEF OR SAFETY VALVE
<br />- GAS COCK
<br />- GAS PRESSURE REGULATOR
<br />- SHUTOFF VALVE ON RISER
<br />- GAS COCK ON RISER
<br />- CONNECTION, TOP
<br />- CONNECTION, BOTTOM
<br />- ELBOW, TURNED DOWN
<br />- ELBOW, TURNED UP
<br />- TEE, TURNED UP
<br />- TEE, TURNED DOWN
<br />-CAP
<br />- DIRECTION OF FLOW
<br />-ALARM PANEL
<br />- MASTER ALARM PANEL
<br />- MEDICAL GAS OUTLET
<br />- MEDICAL GAS VALVE BOX
<br />- CONNECT TO EXISTING
<br />- DEMOLISH TO POINT INDICATED
<br />- REVISION REFERENCE
<br />- DETAIL REFERENCE: TOP -DETAIL#,
<br />BOTTOM -DRAWING# SHOWN ON
<br />PLUMBING ABBREVIATIONS
<br />SYMBOL
<br />DESCRIPTION
<br />CA
<br />- COMPRESSED AIR
<br />AFF
<br />-ABOVE FINISH FLOOR
<br />AW
<br />- ACID WASTE
<br />AV
<br />- ACID VENT
<br />CO2
<br />- CARBON DIOXIDE
<br />CB
<br />- CATCH BASIN
<br />CD
<br />- CONDENSATE DRAIN
<br />CFH
<br />- CUBIC FEET PER HOUR
<br />CO
<br />-CLEANOUT
<br />CONT
<br />- CONTINUATION
<br />CW
<br />- DOMESTIC COLD WATER
<br />DI
<br />- DEIONIZED WATER
<br />DN
<br />- DOWN
<br />DS
<br />- DOWNSPOUT
<br />DWG
<br />- DRAWING
<br />EXIST
<br />- EXISTING
<br />OF
<br />- DEGREE FAHRENHEIT
<br />FCO
<br />- FLOOR CLEANOUT
<br />FD
<br />- FLOOR DRAIN
<br />FOF
<br />- FUEL OIL FILL
<br />FOG
<br />- FUEL OIL GAGE
<br />FOR
<br />- FUEL OIL RETURN
<br />FOS
<br />- FUEL OIL SUPPLY
<br />FOV
<br />- FUEL OIL VENT
<br />FS
<br />- FLOOR SINK
<br />G
<br />-GAS
<br />GPH
<br />- GALLONS PER HOUR
<br />GPM
<br />- GALLONS PER MINUTE
<br />GR
<br />- KITCHEN WASTE (GREASE)
<br />HB
<br />- HOSE BIBB
<br />HD
<br />- HUB DRAIN
<br />HW
<br />- DOMESTIC HOT WATER
<br />HWR
<br />- DOMESTIC HOT WATER RECIRCULATING
<br />IE
<br />- INVERT ELEVATION
<br />IW
<br />- INDIRECT WASTE
<br />KW
<br />- KILOWATT
<br />LBS
<br />-POUNDS
<br />MA
<br />- MEDICAL AIR
<br />MV
<br />- MEDICAL VACUUM
<br />MH
<br />-MANHOLE
<br />NI
<br />- NITROGEN
<br />N20
<br />- NITROUS OXIDE
<br />NC
<br />- NORMALLY CLOSED
<br />NIC
<br />- NOT IN CONTRACT
<br />NO
<br />- NORMALLY OPEN
<br />NP
<br />- NON -POTABLE WATER
<br />NTS
<br />- NOT TO SCALE
<br />OD
<br />- OUTSIDE DIAMETER
<br />OX
<br />-OXYGEN
<br />PRV
<br />- PRESSURE REDUCING VALVE
<br />PSI
<br />- POUNDS PER SQUARE INCH
<br />PVC
<br />- POLYVINYL CHLORIDE PIPE
<br />RD
<br />- ROOF DRAIN
<br />RPBP
<br />- REDUCED PRESSURE BACKFLOW PREVENTO
<br />S
<br />- SANITARY
<br />SF
<br />- SQUARE FEET
<br />SH
<br />-SHEET
<br />ST
<br />-STORM
<br />STO
<br />- OVERFLOW STORM DRAIN
<br />SW
<br />- SOFT COLD WATER
<br />V
<br />-VENT
<br />VC
<br />- VACUUM CLEANING
<br />VTR
<br />- VENT THRU ROOF
<br />WCO
<br />- WALL CLEANOUT
<br />WTR
<br />- WATER
<br />CODES AND STANDARDS
<br />FLORIDA BUILDING CODE 6TH EDITION - 2017 EDITION
<br />NFPA #99, HEALTHCARE FACILITIES CODE - 2015
<br />EDITION.
<br />GUIDELINES FOR DESIGN AND CONSTRUCTION.
<br />FLORIDA HEALTHCARE FACILITIES - 2014 EDITION.
<br />ALL LOCAL CODES - LATEST EDITION.
<br />NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
<br />GENERAL NOTES
<br />1. REFERENCE THE SPECIFICATIONS FOR MATERIAL AND EQUIPMENT INSTALLATION
<br />STANDARDS.
<br />2. THE PLUMBING INSTALLATION SHALL COMPLY WITH ALL STATE AND LOCAL CODES.
<br />3. UTILITIES AND SERVICES INDICATED ARE TAKEN FROM VARIOUS OLD AND NEW
<br />SURVEYS, AS -BUILT RECORDS AND FIELD INVESTIGATIONS. UNFORSEEN CONDITIONS
<br />PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON
<br />DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND BURIAL DEPTHS, AS
<br />DETERMINED DURING CONSTRUCTION, WILL BE NECESSARY.
<br />4. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, WHICH
<br />ARE TO REMAIN ACTIVE, TO FACILITATE RECONNECTION AND EXTENSION OF THE NEW
<br />WORK.
<br />5. NOTIFY OWNER AT LEAST 72 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE.
<br />SCHEDULE DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES.
<br />SERVICES ARE NOT TO BE LEFT DISRUPTED DURING NON -NORMAL CONTRACTOR
<br />WORKING HOURS.
<br />6. PLANS ARE NOT COMPLETELY TO SCALE. PIPE ROUTING SHOWN IS SCHEMATIC AND IS
<br />NOT INTENDED TO INDICATE EXACT ROUTING. CONTRACTOR SHALL PROVIDE ANY
<br />ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO
<br />MAINTAIN CLEARANCES. VERIFY STRUCTURAL, MECHANICAL AND ELECTRICAL
<br />INSTALLATIONS AND OTHER POTENTIAL OBSTRUCTIONS AND ROUTE PIPING TO AVOID
<br />INTERFERENCES.
<br />7. PROVIDE ALL OFFSETS AND FITTINGS AND MAKE CONNECTION TO SITE UTILITIES.
<br />8. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL
<br />ROOMS OR AS SPECIFICALLY NOTED.
<br />9. PROVIDE ACCESS PANELS FOR ALL VALVES CONCEALED IN WALLS OR ABOVE NON -
<br />ACCESSIBLE CEILINGS.
<br />10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND
<br />FLOORS WITH U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL TO OR
<br />EXCEED THE RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS
<br />FOR FINAL FINISHES.
<br />11. FLASH AND COUNTER -FLASH ROOF PENETRATIONS. SEE ARCHITECTURAL DRAWINGS
<br />FOR DETAILS.
<br />12. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS
<br />WITH ALL TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER.
<br />13. PROVIDE FOUNDATION PAD PENETRATION SLEEVES. ALLOW 1" MINIMUM CLEARANCE
<br />BETWEEN SLEEVE INSIDE SURFACE AND PIPE EXTERIOR.
<br />14. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
<br />15. PROVIDE AUTOMATIC TRAP PRIMERS FOR FLOOR DRAIN TRAP SEALS.
<br />16. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES,
<br />DEVICES, APPLIANCES AND APPARATUS.
<br />17. ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED.
<br />18. MOUNT HOSE BIBBS 24" ABOVE FINISHED GRADE, UNLESS OTHERWISE NOTED.
<br />19. PROVIDE CLEANOUTS IN ACCORDANCE WITH ALL STATE AND LOCAL CODES. INSTALL
<br />CLEANOUT WITH COVER FLUSH TO FINISH SURFACE.
<br />20. COORDINATE EXACT FLOOR DRAIN LOCATIONS WITH ARCHITECTURAL DRAWINGS. SET
<br />FLOOR DRAINS BELOW FINISHED FLOOR TO ALLOW FOR FLOOR SLOPING TO THE DRAIN.
<br />21. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS,
<br />ETC.) PRIOR TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL
<br />PANELS UNDER ANY CIRCUMSTANCES. ANY PIPING RUN OVER PANELS SHALL BE RE-
<br />ROUTED AT NO ADDITIONAL COST.
<br />22. ALL WALL MOUNTED LAVATORIES SHALL BE ATTACHED TO FLOOR MOUNTED CARRIER
<br />DESIGNED TO WITHSTAND A VERTICAL LOAD OF 250 POUNDS ON THE FRONT OF THE
<br />FIXTURE.
<br />23. PROVIDE SANITARY WASTE, VENT, DOMESTIC WATER, ETC. ROUGH -IN AND MAKE FINAL
<br />CONNECTIONS (TO INCLUDE PROVIDING ALL NECESSARY RELATED STOPS, VALVES,
<br />TRAPS, ETC. AND MAKE READY FOR USE) TO ALL EQUIPMENT, WHETHER FURNISHED BY
<br />THIS CONTRACTOR OR FURNISHED BY OTHERS.
<br />24. PROVIDE CERTIFIED COPY OF MEDICAL GAS TEST REPORT AT FINAL A.H.C.A.
<br />INSPECTION.
<br />PLUMBING DRAWING INDEX
<br />P001
<br />GENERAL INFORMATION - PLUMBING
<br />Yes
<br />PD101
<br />LEVEL 1 DEMOLITION PLAN - PHASE 1 - GRAVITY
<br />Yes
<br />PD102
<br />LEVEL 1 DEMOLITION PLAN - PHASE 2 - GRAVITY
<br />Yes
<br />PD201
<br />LEVEL 1 DEMOLITION PLAN - PHASE 1 - PRESSURE
<br />Yes
<br />PD202
<br />LEVEL 1 DEMOLITION PLAN - PHASE 2 - PRESSURE
<br />Yes
<br />P101
<br />LEVEL 1 RENOVATION PLAN - PHASE 1 - GRAVITY
<br />Yes
<br />P102
<br />LEVEL 1 RENOVATION PLAN - PHASE 2 - GRAVITY
<br />Yes
<br />P201
<br />LEVEL 1 RENOVATION PLAN - PHASE 1 - PRESSURE
<br />Yes
<br />P202
<br />LEVEL 1 RENOVATION PLAN - PHASE 2 - PRESSURE
<br />Yes
<br />P301
<br />PLUMBING DETAILS
<br />Yes
<br />P401
<br />PLUMBING RISER DIAGRAM
<br />Yes
<br />P402
<br />PLUMBING RISER DIAGRAM
<br />Yes
<br />1715 N. Westshore Blvd., Suite 600
<br />Tampa„ Florida 33607-3999
<br />904-256-2500 Fax 904-256-2503
<br />www.rsandh.com
<br />FL Cert. Nos. AAC001886 * IB26000956
<br />5620 * LCC000210 * GB238
<br />&:-T LC
<br />ENGINEERING
<br />S0LUT10NSo
<br />255 S. Orange Avenue
<br />Suite 1600
<br />Orlando, FL 32801
<br />P 407, 841.9050
<br />www.tic-engineers.com
<br />COA 15
<br />0 Copyright 2019 TLC Engineering Solutions, Inc.
<br />TLC Project No.: 119333
<br />THINK. LISTEN. CREATE.
<br />PROJECT TITLE:
<br />KITCHEN RENOVATION
<br />ADVENTHEALTH ZEPHYRHILLS
<br />PROJECT ADDRESS:
<br />7050 Gall Blvd. Zephyrhills, FL 33541
<br />Aaron Lee Johnson, P.E.
<br />Florida License #71576
<br />�E E J
<br />♦♦♦,t ,pti
<br />♦
<br />���♦ Q`� •' � G•E N 3 • • S ��i�
<br />• •. 2
<br />No 71576
<br />•.*
<br />*, *
<br />M
<br />.�: y •
<br />Ts d.MeIt has Doen S M"A Hi I 9' d
<br />y
<br />Wned and seated by the ws*Adua, iy `�
<br />named. dated DgWl
<br />���r�p','
<br />O
<br />4=
<br />usrg a ,mil ,�
<br />S+pnature Pooled udDws of Ihes efiTCl� 1`C ♦♦
<br />doc~ are not t�deted steed
<br />40
<br />and sea4d. and the epnature mwt De�}p
<br />verified «, an~ e+ect.a,K copies �- 1 t �� 0.03.25
<br />��1:29' 21-04'00'
<br />M
<br />N
<br />W
<br />0
<br />O
<br />U
<br />I~
<br />Z
<br />w
<br />J
<br />U
<br />Q
<br />U
<br />Q
<br />REVISIONS
<br />NO. DESCRIPTION DATE
<br />DATE ISSUED: 03/20/2020
<br />REVIEWED BY: ALJ
<br />DRAWN BY: BJL
<br />DESIGNED BY: BJL
<br />PROJECT NUMBER:
<br />504- 0226- 000
<br />0 2019 RS&H, INC.
<br />SHEET TITLE:
<br />GENERAL
<br />INFORMATION -
<br />PLUMBING
<br />SHEET ID:
<br />Pool
<br />PROJECT STATUS:
<br />CONSTRUCTION
<br />DOCUMENTS
<br />Copyright C 2018. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the
<br />expressed written consent of this corporation is prohibited. All rights reserved.
<br />2
<br />3
<br />4
<br />:1
<br />
|