<br />ELECTRICAL SYMBOL LEGEND
<br />BASIC MATERIALS BASIC MATERIALS CONT.
<br />SYMBOL DESCRIPTION SYMBOL DESCRIPTION
<br />S a SINGLE POLE SWITCH OUP CONDUIT TURNING UP
<br />(SUBSCRIPT INDICATES ITEM CONTROLLED)
<br />-♦DN CONDUIT TURNING DOWN
<br />S3 THREE-WAY SWITCH
<br />] CONDUIT STUB
<br />S4 FOUR-WAY SWITCH
<br />-� CONDUIT CONTINUED
<br />S
<br />P SINGLE POLE SWITCH
<br />WITH PILOT LIGHT FLEXIBLE CONDUIT
<br />DUPLEX RECEPTACLE - - - - - EXISTING TO BE REMOVED
<br />TWIST LOCK RECEPTACLE EXISTING TO REMAIN
<br />T
<br />SURGE PROTECTION TYPE (TVSS) EXISTING AFFECTED BY THIS PROJECT
<br />DUPLEX RECEPTACLE WITH - - - - FUTURE
<br />EACH HALF ON SEPARATE CIRCUIT
<br />(BREAKER SHALL BE TWO POLE WITH COMMON TRIP) NEW
<br />DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
<br />DUPLEX SAFETY RECEPTACLE MOUNT LIGHTING
<br />COVERPLATES WITH SPANNER HEAD SCREWS
<br />A FIXTURE DESIGNATION
<br />DUPLEX RECEPTACLE WITH TOP HALF SWITCHED [:�d LED FIXTURE
<br />SIMPLEX RECEPTACLE (EWC DENOTES 2 a �►�
<br />ELECTRIC WATER COOLER. COORDINATE WITH EWC LOWER CASE LETTER INDICATES
<br />EWC INSTALLER FOR MOUNTING HEIGHT) CONTROL CIRCUIT SWITCH LEG
<br />GFI RECEPTACLE MOUNTED ABOVE COUNTER CIRCUIT NUMBER
<br />LED FIXTURE DIAGONAL SHADING DENOTES
<br />0 TWO DUPLEX RECEPTACLES WITH COMMON COVER Ea TO LIGHT FIXTURE CONNECTED TO CRITICAL
<br />TWO DUPLEX RECEPTACLES WITH COMMON COVER 0 LED FIXTURE
<br />MOUNTED ABOVE COUNTER
<br />EXIT LIGHT FIXTURE
<br />ISOLATED GROUND DUPLEX RECEPTACLE, ® DIRECTION ARROWS AS SHOWN
<br />IG (ORANGE DEVICE) (SHADED QUADRANT INDICATES FACE(S) OF
<br />DUPLEX RECEPTACLE FIRE ALARM/DETECTION SYS
<br />NOTE:
<br />TICK MARKS SHOWN ON ANY DEVICE REPRESENTS
<br />RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT FD MANUAL PULL STATION
<br />(RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND
<br />® CEILING SMOKE DETECTOR, PHOTO-ELECTRI
<br />® SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED TYPE UNLESS OTHERWISE NOTED
<br />GN GROUND BAR DUCT SMOKE DETECTOR
<br />® CABLE TRAY ® SUPERVISED CONTROL RELAY
<br />Q JUNCTION BOX COMBINATION AUDIBLENISUAL NOTIFICATION
<br />CHIME/FLASHING "FIRE" LIGHT
<br />O CONDUIT SEAL -OFF FITTINGS XXCD CD = CANDELA RATING
<br />SS C3 SURGE SUPRESSOR VISUAL SIGNALING UNIT, WALL MOUNTED
<br />C3 = SERVICE ENTRANCE DEVICE F (NO AUDIO DEVICE)
<br />B3 = DISTRIBUTION BOARD DEVICE FACP
<br />A3 = PANELBOARD DEVICE 1�1 FIRE ALARM CONTROL PANEL
<br />MSTSHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS
<br />OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS GENERAL DEMOLITION NOT
<br />© POWER CONNECTION TO EQUIPMENT
<br />® MAGNETIC MOTOR STARTER OR CONTACTOR
<br />SIZE AS NOTED 1. ALL DEVICES SHOWN ON DEMOLITION PLANS ARE EXISTING.
<br />EDH-X REFER TO SYMBOL LEGEND FOR DEVICE DESCRIPTION.
<br />ELECTRIC DUCT HEATER
<br />2. EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE
<br />MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER TAKEN FROM ORIGINAL DRAWINGS AND FIELD
<br />INVESTIGATION, ALL EXISTING CONDITIONS MUST BE
<br />VF VARIABLE FREQUENCY DRIVE VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVEN,
<br />DD DIRECT DIGITAL CONTROL PANEL 3. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL
<br />ELECTRICAL DEVICES WITHIN THE PROJECT AREA. IT IS
<br />INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL
<br />TRANSFORMER KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE
<br />PROJECT AREA, ANY DISCREPANCIES OR CONDITIONS NOT
<br />SHOWN ON THIS PLAN SHALL BE BROUGHT TO THE
<br />® AUTOMATIC TRANSFER SWITCH ATTENTION OF THE ENGINEER. THE CONTRACTOR IS
<br />RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER
<br />LEI30AR NON -FUSED DISCONNECT SWITCH, SIZE AS NOTED SHOWN ON THE PLANS OR NOT,
<br />NF NF DENOTES NON -FUSED 4. ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT
<br />"AR FUSED DISCONNECT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE
<br />20AF DURING CONSTRUCTION, SO AS NOT TO CAUSE ANY
<br />AR DENOTES AMP RATING OF SWITCH DISRUPTION TO THESE OTHER SPACES. IT IS THE
<br />MCP AF DENOTES AMP FUSE SIZE CONTRACTOR'S RESPONSIBILITY TO INSURE THAT ALL
<br />CONDUITS, NEW OR EXISTING, WITHIN THE PROJECT AREA
<br />SIZE �# OF POLES ARE PROPERLY SUPPORTED AND PROVIDED WITH BONDING
<br />L® 30/3 COMBINATION MAGNETIC MOTOR STARTER, BUSHING IN ACCORDANCE WITH THE NATIONAL ELECTRIC
<br />0 3R SIZE AS NOTED, 3 POLE UNLESS OTHERWISE NOTED CODE.
<br />5. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE
<br />ENCLOSURE NEMA 1 UNLESS NOTED DISPOSED OR TURNED OVER TO THE OWNER AT THE
<br />NEMA STARTER SIZE OWNER'S DISCRETION.
<br />^ BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, 6. THIS CONTRACTOR SHALL PROVIDE ELECTRICAL FOR
<br />SURFACE MOUNTED PHASING WORK AS REQUIRED OR DIRECTED BY THE
<br />ARCHITECT, REFER TO ARCHITECURAL PHASING PLAN.
<br />BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, TEMPORARY ELECTRICAL SERVICES (POWER, LIGHTING,
<br />FLUSH MOUNTED NURSE CALL, FIRE ALARM, ETC) SHALL BE PROVIDED WHEN
<br />NEW WORK AFFECTS SERVICES NEEDING TO REMAIN
<br />® BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, ACTIVE. IF FIRE ALARM SYSTEM CANNOT BE MAINTAINED IN
<br />SURFACE MOUNTED THE CONSTRUCITON AREA, A FIRE WATCH SHALL BE
<br />PROVIDED.
<br />T BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, 7, UNLESS OTHERWISE NOTED, ALL EQUIPMENT, WIRING
<br />FLUSH MOUNTED DEVICES, LIGHT FIXTURES, CONDUIT AND WIRE IN THE
<br />BRANCH CIRCUIT CONDUIT CONCEALED ABOVE PROJECT AREA SHALL BE REMOVED. THE CONTRACTOR
<br />CEILING OR IN WALL. CONDUIT SHALL INCLUDE SHALL INVESTIGATE THE PROJECT AREA PRIOR TO BID TO
<br />PHASE, NEUTRAL AND GROUND CONDUCTORS DETERMINE ALL REQUIRED DEMOLITION.
<br />AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED). 8, CONTRACTOR SHALL PROVIDE MEANS OF AUTOMATIC
<br />BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB, SMOKE DETECTION VIA INSTALLED SMOKE DETECTORS
<br />--\ CONNECTED TO THE FACITLITY FIRE ALARMS SYSTEM FOR
<br />UNDERGROUND OR UNDER FLOOR. COVERAGE DURING NON -OCCUPIED PERIODS WITHIN THE
<br />CONSTRUCTION AREA, IF DESIRED, A DOCUMENTED FIRE
<br />BRANCH CIRCUIT CONDUIT EXPOSED WATCH OF THE ENTIRE AREA PERFORMED IN INCREMENTS
<br />NO GREATER THAN ONE HOUR MAY BE PERFORED
<br />GROUND OR GROUND ROD AS NOTED PROVIDED THAT IT IS DOCUMENTED IN FULL ACCORDANCE
<br />WITH NPFA 72. COORDINATE ACTIVITY IN FIELD WITH
<br />C CRITICAL BRANCH CONDUIT GENERAL CONTRACTOR.
<br />�- L LIFE SAFETY BRANCH CONDUIT 9. 'ETR" DENOTES EXISTING ELECTRICAL DEVICE TO REMAIN.
<br />�EQ� EQUIPMENT BRANCH CONDUIT
<br />NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
<br />GENERAL NOTES
<br />FIXTURE)
<br />TEM
<br />C
<br />1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE
<br />FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS
<br />OTHERWISE NOTED.
<br />2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE
<br />FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS
<br />OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL
<br />BE MOUNTED T ABOVE BACK SPLASH TO CENTERLINE OF
<br />DEVICE.
<br />3. THE EQUIPMENT GROUNDING TERMINAL BARS OF THE
<br />NORMAL AND ESSENTIAL ELECTRICAL SYSTEM
<br />PANELBOARDS SERVING THE SAME PATIENT VICINITY SHALL
<br />BE BONDED TOGETHER WITH AN INSULATED, CONTINUOUS,
<br />COPPER CONDUCTOR NOT SMALLER THAN NUMBER 10.
<br />4. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND
<br />RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE
<br />INSTALLED.
<br />A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT
<br />SHALL BE IN COMPLIANCE WITH NEC 110.
<br />B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM
<br />FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH
<br />OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF
<br />ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE
<br />ELECTRICAL EQUIPMENT OR ARCHITECTURAL
<br />APPURTENANCES IN ACCORDANCE WITH NEC 408.
<br />5. CRITICAL AND LIFE SAFETY LIGHT SWITCHES SHALL BE
<br />ROUTED IN CONDUIT AND BOXES OTHER THAN THAT FOR
<br />THE NORMAL BRANCH. ESSENTIAL SYSTEM SWITCHES
<br />SHALL BE RED IN COLOR.
<br />BRANCH.
<br />6. PATIENT CARE AREAS SHALL BE PROVIDED WITH
<br />GROUNDING IN ACCORDANCE WITH NEC 517.
<br />7. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE -
<br />RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND
<br />SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT
<br />AFFECTING THE FIRE CLASSIFICATION, ALL OF THE
<br />FOLLOWING CONDITIONS SHALL BE MET:
<br />A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
<br />B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF
<br />FRAMING SPACE.
<br />C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
<br />D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM
<br />BOARD SHALL BE COMPLETELY FILLED WITH JOINT
<br />COMPOUND (OR OTHER APPROVED MATERIAL).
<br />DEVICE
<br />E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16
<br />SQUARE INCHES. THE INTEGRITY OF THE WALL RATING
<br />SHALL BE MAINTAINED.
<br />F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES
<br />SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE
<br />FEET.
<br />G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE
<br />RESISTIVE ASSEMBLIES SHALL BE SEPARATED BY A MINIMUM
<br />HORIZONTAL DISTANCE OF 24 INCHES.
<br />ES
<br />H. OUTLET BOXES SHALL BE SECURELY FASTENED TO
<br />WALL FRAMING MEMBERS.
<br />I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE
<br />CUT NOT TO EXCEED 1/8 INCH BETWEEN THE EDGES OF THE
<br />OUTLET BOX AND THE EDGES OF THE OPENING.
<br />8. NON-METALLIC RACEWAYS SHALL NOT BE USED TO SERVE
<br />ANY PATIENT CARE SPACE. ALL WIRING SHALL BE
<br />MECHANICALLY PROTECTED BY INSTALLATION IN METALLIC
<br />RACEWAYS,
<br />9. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS
<br />OTHERWISE NOTED.
<br />10. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE
<br />GROUND PIN IS MOUNTED UP,
<br />11. THE NUMBER OF ARROWHEADS ON THE HOMERUNS
<br />DENOTES THE NUMBER OF CIRCUITS.
<br />12. ALL NEW AND EXISTING PANELS AFFECTED BY THIS PROJECT
<br />SHALL BE PROVIDED WITH A NEW TYPE WRITTEN
<br />DIRECTORY.
<br />CODES
<br />1. LIFE SAFETY CODE - NFPA 101(2015).
<br />2. NATIONAL ELECTRICAL CODE - NFPA 70 (2014).
<br />3. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2013); NATIONAL FIRE ALARM & SIGNALING CODE.
<br />4. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2015). HEALTH CARE FACILITIES
<br />5. BUILDING CODE: FLORIDA BUILDING CODE (2017 6TH EDITION).
<br />6. FGI - GUIDELINES FOR DESIGN & CONSTRUCTION OF THE HEALTH CARE FACILITIES. (2014)
<br />ELECTRICAL DRAWING INDEX
<br />SHEET
<br />DESCRIPTION
<br />ISSUED
<br />E001
<br />GENERAL INFORMATION - ELECTRICAL
<br />Yes
<br />E002
<br />ELECTRICAL ONE -LINE DIAGRAM
<br />Yes
<br />ED101
<br />LEVEL 1 DEMOLITION PLAN - PHASE 1 - POWER
<br />Yes
<br />ED102
<br />LEVEL 1 DEMOLITION PLAN - PHASE 2 - POWER
<br />Yes
<br />E101
<br />LEVEL 1 RENOVATION PLAN - PHASE 1 - POWER
<br />Yes
<br />E102
<br />LEVEL 1 RENOVATION PLAN - PHASE 2 - POWER
<br />Yes
<br />E201
<br />LEVEL 1 RENOVATION PLAN - PHASE 1 - LIGHTING
<br />Yes
<br />E202
<br />LEVEL 1 RENOVATION PLAN - PHASE 2 - LIGHTING
<br />Yes
<br />E301
<br />ELECTRICAL DETAILS
<br />Yes
<br />E401
<br />PANEL SCHEDULES
<br />Yes
<br />DIVISION 26 SPECIFICATIONS
<br />1. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, TRANSPORTATION, INSURANCE,
<br />TEMPORARY PROTECTION, TEMPORARY LIGHTING, SUPERVISION AND INCIDENTAL ITEMS ESSENTIAL FOR PROPER INSTALLATION AND OPERATION,
<br />EVEN THOUGH NOT SPECIFICALLY MENTIONED OR INDICATED BUT WHICH ARE USUALLY PROVIDED OR ARE ESSENTIAL FOR PROPER
<br />INSTALLATION AND OPERATION OF ALL ELECTRICAL SYSTEMS THE ELECTRICAL SYSTEM REQUIRED UNDER THIS DIVISION CONSISTS BASICALLY
<br />OF, BUT IS NOT LIMITED TO THE FOLLOWING: LIGHTING SYSTEM, POWER SYSTEM, ALARM SYSTEM, POWER DISTRIBUTION, EQUIPMENT
<br />CONNECTIONS, ACCESS PANELS, EMPTY CONDUIT SYSTEMS AND ALL REQUIRED WIRING.
<br />2. GIVE ALL NOTICES, FILE ALL PLANS, PAY ALL FEES, OBTAIN ALL PERMITS, ALL LICENSES, INSPECTIONS, RE -INSPECTIONS AND APPROVALS
<br />FROM AUTHORITIES HAVING JURISDICTION. INCLUDE ALL FEES IN THE BID
<br />3. A. SPECIAL ATTENTION IS CALLED TO THE FACT THAT WORK INVOLVED IS IN CONNECTION WITH EXISTING BUILDINGS WHICH REMAIN IN
<br />OPERATION WHILE WORK IS BEING PERFORMED. WORK MUST BE DONE IN ACCORDANCE WITH THE PRIORITY SCHEDULE. SCHEDULE
<br />WORK FOR A MINIMUM OUTAGE TO OWNER. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING
<br />WORK AND DURING CONSTRUCTION FOR POWER AND/OR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. RECEIVE WRITTEN
<br />ACCEPTANCE FROM THE OWNER NO LATER THAN 7 DAYS IN ADVANCE OF ALL POWER OUTAGES. CONTRACTOR SHALL WORK DURING
<br />OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL. PROTECT EXISTING BUILDINGS AND EQUIPMENT
<br />DURING CONSTRUCTION.
<br />B. CONTRACTOR SHALL VERIFY IF THERE IS ANY PIPING, FIXTURES OR OTHER ITEMS IN THE EXISTING BUILDING WHICH MUST BE REMOVED
<br />OR RELOCATED IN ORDER TO PERFORM THE ALTERATION WORK. BID SHALL INCLUDE ALL REMOVAL AND RELOCATION REQUIRED FOR
<br />COMPLETION OF THE ALTERATIONS AND THE NEW CONSTRUCTION.
<br />C. ALL EXISTING/NEW CONDUIT AND CABLES WITHIN THE AREA OF RENOVATION SHALL BE PROVIDED WITH PROPER SUPPORTS.
<br />D. ALL EXISTING ELECTRICAL WHICH IS DESIGNATED FOR REWORKING OR REQUIRES RELOCATION, REPAIR OR ADJUSTMENT SHALL CONFORM
<br />TO ALL APPLICABLE CODES AND SHALL BE TREATED AS NEW WORK COMPLYING TO ALL PARTS OF THIS SPECIFICATION.
<br />E. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED PROGRAMMING FOR CONNECTION TO EXISTING SYSTEMS INCLUDING BUT NOT
<br />LIMITED TO FIRE ALARM AND NURSE CALL.
<br />4. ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE U.L. LISTED, BEAR THE U.L. LABEL OR BE LABELED OR LISTED WITH
<br />AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY. WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR
<br />CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE SUBMITTED TO PROVE TO THE ENGINEER THAT EQUIPMENT MEETS OR EXCEEDS
<br />AVAILABLE STANDARDS. AFTER TEST DATA IS SUBMITTED AND TENTATIVELY APPROVED, THE CONTRACTOR SHALL PAY FOR ANY REQUIRED
<br />FIELD LLISTING AND/OR CORRECTIVE WORK REQUIRED BY THE FIELD LISTING INSPECTOR IF ALLOWED BY THE AHJ.
<br />5. PROVIDE SHOP DRAWING SUBMITTALS TO THE ARCHITECT/ENGINEER FOR APPROVAL FOR ALL MATERIAL PROVIDED UNDER THIS DIVISION,
<br />EQUIPMENT SHALL NOT BE ORDERED PRIOR TO APPROVAL FROM THE ARCHITECT/ENGINEER.
<br />6. COORDINATION STUDY: ALL PANELBOARD AND CIRCUIT BREAKERS SHALL MATCH THE EXISTING TYPE, AIC RATING, AND MANUFACTURER. ANY
<br />DISCREPANCIES OR CONFLICTS IN THE SPECIFIED EQUIPMENT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER DURING BID FOR
<br />FORMAL CLARIFICATION.
<br />7. PROVIDE AND INSTALL ALL ELECTRICAL SYSTEMS AND ANY NECESSARY ACCESSORIES AS PER NEC AND LOCAL CODES WHETHER SPECIFIED
<br />HEREIN OR SHOWN ON DRAWINGS OR NOT. THE CONTENT OF THESE SPECIFICATIONS (DIVISION 26) AND CONTRACT DOCUMENTS IN GENERAL
<br />ONLY REFERS TO WORK REQUIRED ABOVE AND BEYOND THE REQUIREMENTS OF THE NEC AND LOCAL CODES.
<br />8. DRAWINGS ARE DIAGRAMMATIC. COORDINATE FINAL EQUIPMENT LOCATIONS WITH GOVERNING ARCHITECTURAL AND STRUCTURAL DRAWINGS.
<br />LAY OUT BEFORE INSTALLATION SO THAT ALL TRADES MAY INSTALL EQUIPMENT IN SPACES AVAILABLE. PROVIDE COORDINATION AS
<br />REQUIRED FOR INSTALLATION IN A NEAT AND WORKMANLIKE MANNER.
<br />9. CHECK SITE AND EXISTING CONDITIONS THOROUGHLY BEFORE BIDDING. ADVISE ENGINEER OF DISCREPANCIES OR QUESTIONS NOTED. WHERE
<br />EXISTING CONDITIONS ARE DISCOVERED WHICH ARE NOT IN COMPLIANCE WITH THE CODES AND STANDARDS, THE CONTRACTOR SHALL
<br />SUBMIT PROPERDOCUMENTATION TO THE ARCHITECT FOR CLARIFICATION AND CORRECTIVE WORK DIRECTION. EXISTING
<br />CONDITIONS SHALL NOT REMAIN WHICH WILL CREATE A DISAPPROVAL OF THE RENOVATED AREA.
<br />10. ALL EXISTING CONDUIT AND CABLE PENETRATIONS SHALL BE PROPERLY FIRE TREATED PER CODE AND SPECIFICATION REQUIREMENTS. THE
<br />CONTRACTOR SHALL THOROUGHLY INSPECT ALL EXISTING LOCATIONS AND INCLUDE THE COST OF PATCHING AND REPAIR IN HIS PROPOSED
<br />CONSTRUCTION COST.
<br />11. PROVIDE FIELD SUPERINTENDENT WHO HAS HAD A MINIMUM OF FOUR (4) YEARS PREVIOUS SUCCESSFUL EXPERIENCE ON PROJECTS OF
<br />COMPARABLE SIZES AND COMPLEXITY. SUPERINTENDENT SHALL BE PRESENT AT ALL TIMES THAT WORK UNDER THIS DIVISION IS BEING
<br />INSTALLED OR AFFECTED. SUPERINTENDENT SHALL HAVE PASSED A PROCTORED H.H. BLOCK JOURNEYMAN EXAM WITH 75% GRADE OR
<br />BETTER AND SHALL BE A LICENSED JOURNEYMAN. A RESUME OF THE SUPERINTENDENT'S EXPERIENCE SHALL BE SUBMITTED TO ENGINEER
<br />BEFORE STARTING WORK. AT LEAST ONE MEMBER OF THE ELECTRICAL CONTRACTING FIRM SHALL HOLD A STATE MASTER CERTIFICATE OF
<br />COMPETENCY.
<br />12. PROVIDE ALL REQUIRED COORDINATION AND SUPERVISION WHERE WORK CONNECTS TO OR IS AFFECTED BY WORK OF OTHERS, AND COMPLY
<br />WITH ALL REQUIREMENTS AFFECTING THIS DIVISION.
<br />13. SUITABLY PROTECT ALL EQUIPMENT FURNISHED UNDER THIS DIVISION DURING CONSTRUCTION. RESTORE ALL DAMAGED SURFACES AND
<br />ITEMS TO "LIKE NEW" CONDITION BEFORE A REQUEST FOR SUBSTANTIAL COMPLETION INSPECTION.
<br />14. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE A ONE-YEAR GUARANTEE. THIS GUARANTEE SHALL BE BY THE CONTRACTOR TO
<br />THE OWNER FOR ANY DEFECTIVE WORKMANSHIP OR MATERIAL WHICH HAS BEEN FURNISHED UNDER THIS CONTRACT AT NO COST TO THE
<br />OWNER FOR A PERIOD OF ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION OF THE SYSTEM. THIS GUARANTEE SHALL NOT
<br />INCLUDE LAMPS IN SERVICE. THE PROVISIONS OF GUARANTEE TO THE OWNER AT THE "DEMONSTRATION OF COMPLETED AFTER ONE MONTH
<br />FROM DATE OF SUBSTANTIAL COMPLETION OF THE SYSTEM."
<br />15. PERFORM VERIFICATION WORK AS REQUIRED TO SHOW THAT THE SYSTEM IS OPERATING CORRECTLY IN ACCORDANCE WITH CONTRACT
<br />DOCUMENTS AND MANUFACTURER'S LITERATURE. ALL VERIFICATION SHALL BE DONE AFTER 3-DAY FULL OPERATIONAL PERIOD. ALL WORK
<br />ON THE SYSTEM SHALL BE COMPLETED, AND ALL FORMS AND OTHER INFORMATION SHALL BE SUBMITTED FOR APPROVAL ONE WEEK
<br />BEFORE THE REQUEST FOR FINAL INSPECTION OF THE BUILDING.
<br />16. WHERE THE REQUIREMENTS OF ANOTHER DIVISION, SECTION, OR PART OF THESE SPECIFICATIONS EXCEED THE REQUIREMENTS OF THIS
<br />DIVISION, THOSE REQUIREMENTS SHALL GOVERN.
<br />17. THE ENTIRE INSTALLATION SHALL BE IN HOT DIPPED RIGID GALVANIZED CONDUIT, OR ELECTRIC METALLIC TUBING, UNLESS SPECIFICALLY
<br />NOTED OTHERWISE. RIGID METAL GALVANIZED CONDUIT SHALL BE USED IN ALL DAMP OR WET LOCATIONS OR WHERE SUBJECT TO
<br />MECHANICAL DAMAGE. ELECTRIC METALLIC TUBING SHALL HAVE STEEL COMPRESSION TYPE COUPLINGS AND BE USED INSIDE OF BUILDINGS
<br />AND ONLY IN DRY AREAS WHERE NOT EXPOSED TO MECHANICAL DAMAGE. MINIMUM CONDUIT SIZE FOR ALL SYSTEMS SHALL BE 3/411
<br />.
<br />PROVIDE INSULATED BUSHINGS AT ENDS OF ALL CONDUITS. ALL CONDUITS AND BACKBOXES SHALL BE COLOR CODED TO MATCH EXISTING
<br />HOSPITAL STANDARDS. SUPPORT CONDUIT IN ACCORDANCE WITH THE NEC. LISTED WHIPS FOR LIGHTING FIXTURES SHALL BE ALLOWED NO
<br />LONGER THAN 6-0" IN LENGTH,
<br />18. BRANCH CIRCUIT AND FEEDER CONDUCTORS FOR ELECTRIC POWER SHALL BE COPPER TYPE THHN/THWN INSULATION FOR BRANCH
<br />CIRCUITS AND THWN INSULATION FOR FEEDERS, UNLESS SPECIFICALLY NOTED OTHERWISE. SIZES #12 AND SMALLER SHALL BE SOLID, #10
<br />AND LARGER STRANDED. NO ALUMINUM WIRING SHALL BE PERMITTED. ALL WIRE SHALL BE SIZE SHOWN ON THE DRAWINGS. IF NO SIZE IS
<br />SHOWN, WIRE SHALL BE MINIMUM NO. 12, EXCEPT THAT BRANCH "HOMERUNS" OVER 50 FT. IN LENGTH SHALL BE MINIMUM NO. 10. WIRE IN
<br />VICINITY OF HEAT -PRODUCING EQUIPMENT SHALL BE TYPE XHHW INSULATION. ALL WIRING SHALL BE MANUFACTURED IN THE USA. WIRING
<br />SHALL BE COLOR CODED ACCORDING TO EXISTING HOSPITAL STANDARDS. USE OF MULTI -WIRE BRANCH CIRCUIT CONFIGURATIONS ARE NOT
<br />PERMITTED. ALL BRANCH CIRCUITS SPECIFIED SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR EACH SIZED TO MATCH THE
<br />CORRESPONDING PHASE CONDUCTORS FOR THE BRANCH CIRCUIT.
<br />19. EACH THREE-PHASE CIRCUIT SHALL BE RUN IN A SEPARATE CONDUIT UNLESS OTHERWISE SHOWN ON THE DRAWINGS. CONDUIT SHALL
<br />NOT BE INSTALLED EXPOSED UNLESS OTHERWISE NOTED. WHERE CIRCUITS ARE SHOWN AS "HOME -RUNS" ALL NECESSARY FITTINGS AND
<br />BOXES SHALL BE PROVIDED FOR A COMPLETE RACEWAY INSTALLATION. NEUTRAL CONDUCTORS SHALL NOT BE SHARED BETWEEN CIRCTUITS
<br />AND THEREFORE ALL CIRCUITS REQUIRING A NEUTRAL CONDUCTOR SHALL EACH RECIEVE A DEDICATED NEUTRAL SIZED TO MATCH THE
<br />CORRESPONDING PHASE CONDUCTORS.
<br />20. OUTLET BOXES SHALL BE ONE PIECE OR PROJECTION WELDED, GALVANIZED STAMPED STEEL FOR GANG SIZES REQUIRED. SECTIONAL
<br />BOXES ARE NOT ACCEPTABLE. BOXES SHALL BE 4" SQUARE AND 1-1/2" DEEP GENERALLY, LARGER BOXES SHALL BE USED AS
<br />REQUIRED BY CODE.
<br />21. ALL RECEPTACLES SHALL BE 20 AMP HOSPITAL GRADE, STANDARD DUPLEX GROUNDING TYPE. SWITCHES SHALL BE SPECIFICATION GRADE,
<br />20 AMP,120/277 VOLT AND SHALL BE OF THE SILENT OPERATING TYPE. GFCI RECEPTACLES SHALL BE HOSPITAL GRADE, UL RATED CLASS
<br />A, GROUP 1. COVER PLATES SHALL BE STAINLESS STEEL FINISHED. ALL WIRING DEVICE COVER PLATES INCLUDING BUT NOT LIMITED TO
<br />RECEPTACLES AND SWITCHES SHALL BE ENGRAVED WITH THE BRANCH CIRCUIT IDENTIFICATION AS REQUIRED (I.E. "PANELNAME'-"CIRCUIT
<br />NUMBER"). COVERPLATES SHALL BE STAINLESS STEEL WITH BLACK INFILLED LETTERS FOR NORMAL BRANCH AND RED INF►LLED LETTERS
<br />FOR EMERGENCY BRANCHES. RECEPTACLES AND SWITCHES SHALL HAVE IVORY FINISH FOR NORMAL BRANCH DEVICES AND RED FINISH FOR
<br />CRITICAL BRANCH DEVICES. APPROVED MANUFACTURER: PASS & SEYMOUR, LEVITON, HUBBELL
<br />22. ALL EQUIPMENT SHALL BE FIRMLY MOUNTED USING APPROVED HANGERS ATTACHED TO STRUCTURAL PORTIONS OF THE BUILDING.
<br />SUPPORTING WITH TIE WIRE IS PROHIBITED. LIGHT FIXTURES RECESSED IN CEILINGS SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE
<br />INDEPENDENT OF THE CEILING SYSTEM.
<br />23. IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR FRAMES, PANELBOARDS, ETC.) SHALL BE BONDED TOGETHER WITH A
<br />GREEN INSULATED COPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250 OF THE N.E.C.
<br />BONDING CONDUCTOR THROUGH THE RACEWAY SYSTEM SHALL BE CONTINUOUS FROM EACH WIRING DEVICE OR EQUIPMENT TO PANEL
<br />GROUND BAR OF EACH PANELBOARD. PROVIDE GROUND BAR BOLTED TO THE CAN OF EXISTING PANELS WITHOUT A GROUND BAR. ALL
<br />RACEWAYS SHALL HAVE AN INSULATED COPPER SYSTEM GROUND CONDUCTOR THROUGHOUT THE ENTIRE LENGTH OF CIRCUIT INSTALLED
<br />WITHIN CONDUIT PER NEC 517.13. GROUNDING CONDUCTOR SHALL BE INCLUDED IN TOTAL FILL IN DETERMINING CONDUIT SIZES, EVEN
<br />THOUGH NOT INCLUDED OR SHOWN ON DRAWINGS.
<br />24. A. MOLDED CASE CIRCUIT BREAKERS: ALL PANELBOARD BRANCH CIRCUIT BREAKERS SHALL BE BOLT -ON THERMAL -MAGNETIC MOLDED
<br />CASE TYPE. BREAKERS SHALL BE 1, 2 OR 3 POLE WITH AN INTEGRAL CROSSBAR TO ASSURE SIMULTANEOUS OPENING OF ALL POLES IN
<br />MULTI -POLE CIRCUIT BREAKERS. BREAKERS SHALL HAVE AN OVERCENTER,TRIP-FREE,TOGGLE-TYPE OPERATING MECHANISM WITH QUICK -
<br />MAKE, QUICK -BREAK ACTION AND ACTIVE HANDLE INDICATION. HANDLES SHALL HAVE "ON", "OFF", AND "TRIPPED" POSITIONS. BOLT -ON
<br />BREAKER SHALL BE ABLE TO BE INSTALLED IN THE PANELBOARD WITHOUT REQUIRING ADDITIONAL MOUNTING HARDWARE.
<br />CIRCUIT S Q
<br />120/208 VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 10,000 RIMS SYMMETRICAL AMPERES AT 240VAC.
<br />277/480 VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 18,000 RMS SYMMETRICAL AMPERES AT 600VAC.
<br />25. RECORD DRAWINGSAT THE COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE TWO SETS OF RECORD "AS -BUILT" DRAWINGS IN
<br />ACCORDANCE WITH DIVISION 1, SHOWING THE ACTUAL LOCATION OF ALL EQUIPMENT INSTALLED INCLUDING UNDERGROUND CONDUITS AND
<br />JUNCTION BOXES.
<br />26. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING WORK AND DURING CONSTRUCTION FOR POWER
<br />AND/OR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. A SEVEN (7) DAY NOTICE SHALL BE GIVEN FOR ALL POWER OUTAGES.
<br />CONTRACTOR SHALL WORK DURING OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL.
<br />27. GROUND TESTINGCONTRACTOR SHALL PERFORM A COMPLETE EQUIPOTENTIAL GROUND TEST IN ACCORDANCE WITH NFPA 99 UPON THE
<br />COMPLETION OF ALL BRANCH CIRCUITS TO THE PANELS SPECIFIED. GROUND TEST SHALL BE IN A TYPED WRITTEN FORMAT FOR ISSUANCE
<br />TO AHCA AT THE 100% INSPECTION. TEST SHALL BE PERFORMED IN ALL AFFECTED PATIENT -CARE AREAS.
<br />28. COLOR CODING COLOR CODE ALL POWER AND LIGHTING CABLE. COLOR CODE THE WIRE BY USING COLORED PLASTIC TAPE, PAINTING THE
<br />ENDS ACCESSIBLE AT JUNCTION OR PULL BOXES, OR OTHER METHOD ACCEPTABLE TO THE ENGINEER. USE THE FOLLOWING CHART AS
<br />APPLICABLE;
<br />120/208 277/480
<br />CONDUCTOR VOLTS CONDUCTOR VOLTS
<br />PHASE A BLACK PHASE A BROWN
<br />PHASE B RED PHASE B ORANGE
<br />PHASE C BLUE PHASE C YELLOW
<br />NEUTRAL WHITE NEUTRAL GRAY
<br />EQUIRGROUND GREEN EQUIRGROUND GREEN
<br />29. COLOR CODING OF RACEWAYS/BOXES: ALL BOXES AND ENCLOSURES SHALL BE MARKED SO AS TO BE READILY IDENTIFIED AS PART OF THE
<br />SYSTEM FOR WITH IT SERVES. CONDUIT AND BOXES, INCLUDING BACK BOXES. PANELS, ETC. SHALL BE SPOT PAINTED. CONDUITS SHALL BE
<br />IDENTIFIED TO WITHIN 6" OF THE BOX OR ENCLOSURE. PROVIDE SPOT PAINTING BANDS AT ALL CONDUIT COUPLING LOCATIONS OR EVERY 1 U-0"
<br />WHICHEVER IS LESS ALONG WITHIN 6" OF EACH SIDE OF WALLS AND FLOOR THAT THE CONDUIT PENETRATES. THE FOLLOWING COLOR CODES
<br />SHALL BE USED UNLESS OTHERWISE REQUIRED TO MATCH EXISTING COLOR CODING;
<br />BLACK: NORMAL BROWN: MISCELLANEOUS COMMUNICATIONS
<br />PURPLE: ESSENTIAL DISTRIBUTION BLUE: TELEPHONEICOMPUTER
<br />YELLOW: LIFE SAFETY BRANCH WHITE: NURSE CALL
<br />ORANGE: CRITICAL BRANCH LIGHT PINK: TV
<br />GREEN: EQUIPMENT BRANCH GREY: PAGING
<br />RED: FIRE ALARM BRANCH BEIGE: PHYSIOLOGICAL MONITORING
<br />30. EQUIPMENT IDENTIFICATION:
<br />LOCATIONS: PROVIDE NAMEPLATES FOR EACH UNIT OF THE FOLLOWING CATEGORIES OF ELECTRICAL WORK:
<br />A. SWITCHBOARD, PANELBOARDS, ELECTRICAL CABINETS AND ENCLOSURES.
<br />(1) PROVIDE A NAMEPLATE OUTSIDE ABOVE THE DOOR (IF EQUIPPED WITH ONE) LISTING ITS
<br />DESIGNATION, BRANCH, VOLTAGE AND CIRCUIT NUMBER.
<br />(2) PROVIDE AN ENGRAVED PHENOLIC PLASTIC LAMINATE NAMEPLATE:
<br />(NORMAL BRANCH: BLACK W/WHITE LETTTERS)
<br />(CRITICAL BRANCH: ORANGE W/WHITE LETTTERS)
<br />(EQUIPMENT BRANCH: GREEN W/WHITE LETTTERS)
<br />(LIFE SAFETY BRANCH: YELLOW W/WHITE LETTTERS)
<br />(3) NAMEPLATE SIZE SHALL MATCH EXISTING.
<br />B. ACCESS PANEUDOORS TO ELECTRICAL FACILITIES.
<br />C. MOTOR STARTERS.
<br />D. ALL WIRING DEVICE'S COVERPLATES INCLUDING BUT NOT LIMITED TO RECEPTACLES AND
<br />SWITCHES SHALL BE REPLACED WITH NEW 302 STAINLESS STEEL COVERPLATES, AND ENGRAVED
<br />IN BLACK FOR NORMAL AND RED FOR EMERGENCY BRANCHES WITH THE BRANCH CIRCUIT
<br />IDENTIFICATIONS AS REQUIRED (I.E. "PANELNAME" - CIRCUIT NUMBER").
<br />E. ALL EXIT LIGHTS TO HAVE LABELS MADE (WHITE WIRED LETTERS) AND INSTALLED ON CANOPY
<br />OF FIXTURE WITH PANELNAME - CIRCUIT NUMBER.
<br />F. ALL AUTOMATIC DOOR CONTROLLERS TO HAVE LABELS MADE (WHITE WIRED LETTERS) AND
<br />INSTALLED BY DOOR CONTROL ENCLOSURE (LOCATED BELOW THE CEILING) WITH
<br />PANELNAME - CIRCUIT NUMBER.
<br />1715 N. Westshore Blvd., Suite 600
<br />Tampa„ Florida 33607-3999
<br />904-256-2500 Fax 904-256-2503
<br />www.rsandh.com
<br />FL Cerl. Nos. AAC001886 * IB26000956
<br />5620 * LCC000210 * GB238
<br />,&:-TLC
<br />ENGINEERING
<br />S© L U T I 0 N S®
<br />255 S. Orange Avenue
<br />Suite 1600
<br />Orlando, FL 32801
<br />P 407.841.9050
<br />www.tic-engineers.com
<br />COA 15
<br />C Copyright 2019 TLC Engineering Solutions, Inc.
<br />TLC Project No.: 119333
<br />THINK. LISTEN. CREATE.
<br />PROJECT TITLE:
<br />KITCHEN RENOVATION
<br />ADVENTHEALTH ZEPHYRHILLS
<br />PROJECT ADDRESS:
<br />7050 Gall Blvd. Zephyrhills, FL 33541
<br />Christopher V. O'Hara, P.E.
<br />Florida License #66504
<br />�69H Eq IO,���i
<br />5
<br />i
<br />V' No 66504
<br />C14
<br />.-:13 �' STATE OF U m
<br />DN � 0 'rit CkS//TOPHER V OHAR� • • 441 O
<br />OID.O. 4 OOJp0900 .. =¢Q1 Ip;A110001 `y'y��� f000088F5.
<br />CN=CHiM1�F�„ QV=GE't�iil f®I�R
<br />ARCHITEjG ING I'RC CTURE, C=US
<br />Date: 20- 0 I 0 'N A\_ % M
<br />1�111111111��`, N
<br />w
<br />G
<br />O
<br />c,)
<br />z
<br />LU
<br />J
<br />U
<br />Q
<br />U
<br />x
<br />Q
<br />REVISIONS
<br />NO. DESCRIPTION DATE
<br />DATE ISSUED: 03/20/20
<br />REVIEWED BY: CVO
<br />DRAWN BY: MA
<br />DESIGNED BY: MA
<br />PROJECT NUMBER:
<br />504- 0226- 000
<br />0 2019 RS&H, INC.
<br />SHEET TITLE:
<br />GENERAL
<br />INFORMATION -
<br />ELECTRICAL