<br />TECHNOLOGY SYSTEMS SYMBOL LEGEND
<br />RS&H
<br />M
<br />A
<br />a
<br />CM
<br />1P
<br />Cl)
<br />0
<br />0
<br />N
<br />N
<br />co
<br />BASIC MATERIALS
<br />SYMBOL DESCRIPTION
<br />OJ JUNCTION BOX
<br />�J FLOOR MOUNTED JUNCTION BOX
<br />PEDESTAL MOUNTED JUNCTION BOX
<br />EXISTING CONDUIT ABOVE HARD CEILING
<br />_
<br />BETWEEN CEILING BOXES
<br />CONDUIT CONCEALED ABOVE CEILING OR IN WALL
<br />CONDUIT CONCEALED IN SLAB, UNDERGROUND OR
<br />_
<br />UNDER
<br />FLOOR
<br />- - - - - -
<br />CONDUIT EXPOSED
<br />-Q
<br />CONDUIT TURNING UP
<br />-�
<br />CONDUIT TURNING DOWN
<br />CONDUIT STUB
<br />CONDUIT CONTINUED
<br />FLEXIBLE CONDUIT
<br />I
<br />GROUND OR GROUND ROD AS NOTED
<br />O
<br />SLEEVE TURNING UP
<br />SLEEVE TURNING DOWN
<br />_ _ _ _ _
<br />EXISTING TO BE REMOVED
<br />EXISTING TO REMAIN
<br />EXISTING AFFECTED BY THIS PROJECT
<br />__________
<br />FUTURE
<br />NEW
<br />COMMUNICATIONS CABLE TRAY FOR HORIZONTAL
<br />CABLING. DIMENSIONS SHOWN ON DRAWINGS.
<br />E 3
<br />RATED WALL PENETRATION SEE FLOOR PLAN AND
<br />DETAILS FOR QUANTITY AND TYPE.
<br />SECURITY SYSTEM
<br />SYMBOL DESCRIPTION
<br />FIX
<br />FIXED CCTV CAMERA
<br />DPS
<br />DOOR POSITION SWITCH
<br />CR
<br />CARD READER
<br />CK
<br />COMBINED CARD READER/KEYPAD
<br />KP
<br />KEYPAD
<br />EL
<br />ELECTRIC LATCH.
<br />EM
<br />ELECTRIC MORTISE LOCK
<br />ES
<br />ELECTRIC STRIKE.
<br />ML
<br />MAGNETIC LOCK
<br />DE
<br />DELAYED EGRESS
<br />DM
<br />DELAYED EGRESS MAGNETIC LOCK
<br />DOOR RELEASE BUTTON
<br />a
<br />REX OR ADA DOOR OPEN BUTTON
<br />I�
<br />DURESS BUTTON
<br />IS
<br />INTERCOM SUBSTATION WITH CAMERA
<br />MASTER INTERCOM STATION W/ LCD MONITOR &
<br />MI
<br />REMOTE DOOR RELEASE BUTTONS
<br />0
<br />REQUEST TO EXIT MOTION SENSOR
<br />OASSOCIATED
<br />DOOR DETAIL REFERENCE
<br />MON
<br />CCTV MONITOR
<br />VOICE & DATA SYSTEM
<br />SYMBOL DESCRIPTION
<br />1 � ,
<br />C X N
<br />44 W
<br />F1
<br />S1
<br />ELV
<br />S1
<br />WAP
<br />MOUNTING 2" ABOVE COUNTER OR BACK SPLASH
<br />X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE ADAPTER
<br />(P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH, (PD) PEDESTAL, (H)EADWALL
<br />N=#OF CAT6 JACKS
<br />COMMUNICATIONS "INFORMATION OUTLET" MOUNTED AT
<br />RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED, MODULE
<br />AND FACEPLATE DESCRIPTIONS, SEE DETAIL SHEETS.
<br />WALL TELEPHONE OUTLET. MOUNTED AT 52" ABOVE FINISHED
<br />FLOOR TO THE BOTTOM OF THE BOX. SEE DETAIL SHEETS.
<br />WALL TELEPHONE OUTLET FOR TELEPHONE ELEVATOR MACHINE
<br />ROOM. (S)URFACE MOUNTED AT 52" ABOVE FINISHED FLOOR.
<br />WIRELESS ACCESS POINT OUTLET. SEE DETAIL SHEETS FOR
<br />MOUNTING DETAILS. QUANTITY AND LOCATIONS ARE APPROXIMATE,
<br />CONTRACTOR TO COORDINATE WITH WLAN VENDOR ACTUAL
<br />QUANTITY AND LOCATIONS BASED ON SIGNAL SURVEY. SIGNAL
<br />SURVEY BY WLAN VENDOR.
<br />BISCUIT JACK OUTLET MOUNTED ABOVE CEILING.
<br />APPROXIMATE LOCATION OF CORNING ONE DAS ANTENNA, + 2 FEET
<br />ANTENNA IS OWNER PROVIDED, STRUCTURED CABLING
<br />CONTRACTOR INSTALLED.
<br />APPROXIMATE LOCATION OF PUBLIC SAFETY LEGACY DAS ANTENNA,
<br />+ 2 FEET, ANTENNA IS OWNER PROVIDED, STRUCTURED CABLING
<br />CONTRACTOR INSTALLED.
<br />COMBINED VOICE/DATA/POWER OUTLET IN POKE-THRU.
<br />CONDUIT, POKE-THRU AND POWER RECEPTACLE PROVIDED BY
<br />DIV. 16. "N" IS THE NUMBER OF CAT 6 JACKS.
<br />COMBINED VOICE/DATA/AUDIONISUAL/POWER OUTLET IN POKE-
<br />THRU. CONDUIT, POKE-THRU AND POWER
<br />RECEPTACLE PROVIDED BY DIV. 16. N IS THE NUMBER
<br />OF CAT 6 JACKS, SEE AV DETAILS FOR AV CONNECTION
<br />REQUIREMENTS.
<br />TELEVISION OUTLET - FLUSH MOUNTED. (1) COAX RG-6 AND (1)
<br />CAT6 UTP CABLE TO TELECOMM ROOM. ADJACENT DUPLEX
<br />RECEPTACLE BY ELECTRICAL CONTRACTOR. COORDINATE
<br />MOUNTING LOCATION WITH ARCHITECTURAL.
<br />TELEVISION OUTLET - CEILING MOUNTED. (1) COAX RG-6 AND (1)
<br />CAT6 UTP CABLE TO TELECOMM ROOM. ADJACENT DUPLEX
<br />RECEPTACLE BY ELECTRICAL CONTRACTOR. COORDINATE
<br />MOUNTING LOCATION WITH ARCHITECTURAL.
<br />3/4" PLYWOOD BACKBOARD. BY DIVISION 16
<br />F -1 T -19" EQUIPMENT RACK
<br />L_ T
<br />TELECOMM PANEL
<br />NOTES:
<br />1. CONTRACTOR TO REMOVE ALL EXISTING LOW VOLTAGE CABLES NOT TO BE REUSED. E.G. ALL
<br />EXISTING UTP 4 PAIR CABLES. NO ABANDONED CABLES SHALL BE LEFT IN THE PROJECT AREA
<br />2. OUTLET QUANTITY AND CONFIGURATION SHALL BE PER THESE DRAWINGS. FOR LOCATION
<br />RELATIVE TO CASE WORK AND EQUIPMENT REFER TO ARCHITECTURAL ELEVATIONS.
<br />3. WIRE ACCESS POINTS (WAP) SHALL BE PROVIDED BY THE OWNER AND INSTALLED BY THE
<br />STRUCTURED CABLING CONTRACTOR.
<br />PAGING AND BACKGROUND MUSIC SYSTEM
<br />OCEILING MOUNTED SPEAKER -
<br />X-Y X-Y: X DENOTES FLOOR
<br />Y DENOTES SUBZONE
<br />WALL MOUNTED SPEAKER -
<br />X-Y X-Y: X DENOTES FLOOR
<br />Y DENOTES SUBZONE
<br />VC CEILING SPEAKER VOLUME CONTROL
<br />NOTES:
<br />1. AUDIO/VISUAL DEVICES AND EQUIPMENT ARE SHOWN FOR
<br />REFERENCE ONLY AND WILL BE PROVIDED BY THE OWNER.
<br />2. THE RACEWAY SYSTEMS NOTED FOR THE AV EQUIPMENT
<br />INSTALLATION SHALL BE PROVIDED BY THE ELECTRICAL
<br />CONTRACTOR AND INSTALLED PER DIVISION 27 SPECIFICATIONS.
<br />3. SPEAKERS AND CABLING SHALL BE PROVIDED BY THE
<br />STRUCTURED CABLING CONTRACTOR.
<br />NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
<br />TECHNOLOGY NOTES
<br />1. PRODUCTS SHALL BE OF MATERIALS THAT ARE SUITABLE FOR THE ENVIRONMENT IN WHICH THEY
<br />ARE TO BE INSTALLED.
<br />2. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE MAINTAINED IN COMPLIANCE
<br />WITH THE NATIONAL ELECTRICAL CODE ARTICLE 110, COORDINATE EQUIPMENT INSTALLATION TO
<br />MAINTAIN REQUIRED CLEARANCES.
<br />3. IF AN OUTLET BOX IS REQUIRED TO BE LOCATED IN AN ASSEMBLY OR PARTITION RATED AS
<br />"FIRE/SMOKE" OR "SMOKE" OR IDENTIFIED AS EITHER "FIRE/SMOKE" OR "SMOKE", THEN ALL OF THE
<br />FOLLOWING CONDITIONS SHALL BE MET:
<br />A. THE OUTLET BOX SHALL BE METALLIC.
<br />B. THE OUTLET BOX OPENINGS SHALL OCCUR ONLY ON ONE SIDE OF THE FRAMING SPACE.
<br />C. THE OUTLET BOX OPENINGS SHALL NOT EXCEED 16 SQUARE INCHES.
<br />D. ALL CLEARANCES BETWEEN THE OUTLET BOX AND THE WALL BOARD
<br />MATERIAL SHALL BE COMPLETELY SEALED WITH APPROVED MATERIALS IN
<br />ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS FOR THE
<br />PROJECT.
<br />E. PROVIDE A SUPPLEMENTAL BARRIER AROUND OUTLETS LARGER THAN 16
<br />INCHES SO THAT THE ORIGINAL RATING OF THE PENETRATION IS MAINTAINED.
<br />F. THE TOTAL AGGREGATE SURFACE AREA OF THE OUTLET BOX SHALL NOT
<br />EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.
<br />G. THE OUTLET BOX SHALL BE SEPARATED FROM OPENINGS ON THE OPPOSITE SIDE
<br />OF THE RATED PARTITION BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
<br />H. THE OUTLET BOX SHALL BE SECURELY FASTENED TO A PARTITION FRAMING
<br />MEMBER BY MEANS OF AN APPROVED ATTACHMENT METHOD.
<br />I. OPENINGS CUT INTO THE WALL BOARD MATERIAL SHALL NOT EXCEED 1/8 INCH
<br />BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
<br />4. LOCATION OF EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE, COORDINATE EXACT
<br />EQUIPMENT LOCATION AND CONNECTION REQUIREMENTS WITH THE APPROPRIATE TRADE PRIOR TO
<br />INSTALLATION.
<br />5. FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE ARCHITECTURAL
<br />REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT NOT INCLUDED ON THE REFLECTED CEILING
<br />PLAN SHALL BE COORDINATED WITH THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED
<br />EQUIPMENT SHALL BE PRIOR TO ANY ROUGH -IN. NOTIFY ENGINEER OF ANY DISCREPANCY.
<br />6. PROVIDE FINAL CONNECTIONS TO OWNER -PROVIDED EQUIPMENT WHERE INDICATED ON THE PLAN
<br />DRAWINGS
<br />7. PRIOR TO ROUGH -IN AND INSTALLATION OF ANY FLOOR -MOUNTED DEVICE, VERIFY LOCATION WITH
<br />THE OWNER AND ARCHITECT.
<br />8. VERIFY AND COORDINATE THE LOCATION OF REQUIRED DIVISION 27 OUTLETS WITH OTHER TRADE
<br />DRAWINGS AND OWNER PROVIDED EQUIPMENT. VOICE/DATA OUTLETS SHALL BE ADJACENT TO AN
<br />ELECTRICAL OUTLET.
<br />9. EACH TELEVISION OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG OUTLET BOX WITH A
<br />SINGLE GANG PLASTER RING AND (1) ONE INCH CONDUIT STUBBED UP TO AN ACCESSIBLE LOCATION
<br />ABOVE THE FINISHED CEILING OR TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED. WORK BY
<br />ELECTRICAL CONTRACTOR (DIV. 26) SHALL BE AS PER SPECIFICATION SECTION 270528.
<br />10. THE DESIGNATION "N.►.C." SHALL DENOTE ITEMS, WHICH ARE "NOT IN CONTRACT".
<br />11. THE DESIGNATION "U.S.C." SHALL DENOTE ITEMS, WHICH ARE "UNDER SEPARATE CONTRACT'.
<br />12. THE DESIGNATION "F.B.O." SHALL DENOTE ITEMS, WHICH ARE "FURNISHED BY OTHERS".
<br />13. THE DESIGNATION "O.F.E." SHALL DENOTE ITEMS, WHICH ARE "OWNER FURNISHED EQUIPMENT'.
<br />14. ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE DIVISION 27 EQUIPMENT
<br />SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. PROVIDE COORDINATION FOR THE
<br />INSTALLATION OF THIS RACEWAY SYSTEM WITH THE ELECTRICAL CONTRACTOR. RACEWAY
<br />INSTALLATION SHALL COMPLY WITH DIVISION 27 SPECIFICATIONS.
<br />15. THE SYMBOL LEGEND SHOWN ON THIS SHEET ARE ALL INCLUSIVE, SYMBOLS INCLUDED IN THE
<br />LEGENDS MAY OR MAY NOT BE USED IN THESE PROJECT DRAWINGS.
<br />16. EACH VOICE/DATA OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG OUTLET BOX WITH A
<br />SINGLE GANG PLASTER RING AND (1)1" CONDUIT STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE
<br />THE FINISHED CEILING. WORK BY ELECTRICAL CONTRACTOR (DIV. 26) SHALL BE PER SPECIFICATIONS
<br />SECTIONS 270528.
<br />17. EACH FLOOR MOUNTED VOICE/DATA OUTLET SHALL HAVE A SINGLE GANG SPACE WITHIN THE FLOOR
<br />BOX AND (NUMBER OF 1" CONDUITS SHOWN ON THE DRAWINGS) V CONDUITS CONCEALED IN SLAB
<br />STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING. WORK BY ELECTRICAL
<br />CONTRACTOR (DIV. 26) SHALL BE PER SPECIFICATIONS SECTIONS 270528.
<br />18. ALL BONDING AND GROUNDING ELEMENTS UTILIZED FOR STRUCTURED CABLING SYSTEM SHALL BE
<br />IN COMPLIANCE WITH SPECIFICATION SECTION 270526.
<br />19. INSTALLATION OF CATEGORY 6 UTP CABLE, COAX CABLE AND FIBER OPTICS CABLE SHALL BE IN
<br />COMPLIANCE WITH SPECIFICATION SECTION 271000. CABLE INSTALLATION AND TERMINATIONS THAT
<br />DO NOT COMPLY SHALL BE REPLACED BY THE CONTRACTOR AT NO ADDITIONAL LOST.
<br />20. FOR SPACES WITH HARD CEILING PROVIDE CONDUIT FROM THE JUNCTION BOX SHALL BE
<br />CONTINUOUS TO THE CORRIDOR CABLE TRAY, OPERATING ROOMS FOR EXAMPLE.
<br />21. STRUCTURED CABLING FOR VOICE/DATA SERVICES WILL BE PROVIDED BY AN OWNER APPROVED
<br />VENDOR, NOT THE ELECTRICAL CONTRACTOR.
<br />22. ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE DIVISION 27 CABLING SHALL
<br />BE PROVIDED BY THE ELECTRICAL CONTRACTOR WITH THE EXCEPTION OF INCIDENTAL SLEEVES AND
<br />THE RACKS AND LADDER RACK WITHIN THE TELECOMMUNICATIONS ROOM. THESE RACEWAY
<br />SYSTEMS SHALL BE INSTALLED PER DIVISION 27 SPECIFICATIONS.
<br />SECURITY NOTES
<br />1. ALL DOUBLE DOORS ARE TO RECEIVE (1) DOOR POSITION SWITCH ON EACH DOOR
<br />LEAF AND SHALL REPORT AS ONE ALARM POINT.
<br />2. ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.
<br />3. ALL CONDUIT ABOVE GRADE SHALL BE METALLIC.
<br />4. ALL CONDUIT, WIRING, AND ASSOCIATED BACK BOXES SHALL BE FULLY CONCEALED
<br />WITHIN WALLS, FLOORS, AND CEILINGS.
<br />5. INSTALLATION OF CATEGORY 6 UTP CABLE SHALL BE IN ACCORDANCE WITH EIA/TIA
<br />GUIDELINES. CABLE INSTALLATION AND TERMINATIONS THAT DO NOT COMPLY SHALL BE
<br />REPLACED BY THE CONTRACTOR.
<br />A. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO AVOID
<br />STRETCHING THE CONDUCTORS.
<br />B. THE MINIMUM BENDING RADIUS OF THE CABLE SHALL NOT BE LESS THAN 4X THE
<br />OUTSIDE DIAMETER OF THE CABLE.
<br />C. THE CABLE SHALL BE INSTALLED WITHOUT KINKS OR TWISTS AND THE APPLICATION
<br />OF CABLE TIES SHALL NOT DEFORM THE CABLE BUNDLE.
<br />D. STRIP BACK ONLY AS MUCH CABLE JACKET AS IS REQUIRED TO TERMINATE THE
<br />CABLE AND THE AMOUNT OF UNTWISTING IN A PAIR AS A RESULT OF THE
<br />TERMINATION SHALL NOT EXCEED 0.5 IN.
<br />6. INSTALLATION OF FIBER OPTIC CABLES SHALL BE IN ACCORDANCE WITH EIA/TIA
<br />GUIDELINES. CABLE INSTALLATION AND TERMINATIONS THAT DO NOT COMPLY SHALL
<br />BE REPLACED BY THE CONTRACTOR.
<br />A. THE BEND RADIUS FOR INTRABUILDING 2 AND 4-FIBER HORIZONTAL OPTICAL FIBER
<br />CABLE SHALL NOT BE LESS THAN 1 IN UNDER NO-LOAD CONDITIONS. WHEN UNDER A
<br />MAXIMUM TENSILE LOAD OF 50 LBF, THE BEND RADIUS SHALL NOT BE LESS THAN 2 IN.
<br />B. THE BEND RADIUS FOR INTRABUILDING OPTICAL FIBER BACKBONE SHALL NOT BE
<br />LESS THAN THAT RECOMMENDED BY THE MANUFACTURER IF NO RECOMMENDATION
<br />IS KNOWN, THEN THE APPLIED BEND RADIUS SHALL NOT BE LESS THAN 10 TIMES THE
<br />CABLE OUTSIDE DIAMETER UNDER NO-LOAD CONDITIONS AND NOT LESS THAN 15
<br />TIMES THE CABLE OUTSIDE DIAMETER WHEN THE CABLE IS UNDER TENSILE LOAD.
<br />C. THE BEND RADIUS FOR INTRABUILDING OPTICAL FIBER BACKBONE SHALL NOT BE
<br />LESS THAN THAT RECOMMENDED BY THE MANUFACTURER IF NO
<br />RECOMMENDATION IS KNOWN, THEN THE APPLIED BEND RADIUS SHALL NOT BE
<br />LESS THAN 10 TIMES THE CABLE OUTSIDE DIAMETER NO-LOAD CONDITIONS AND
<br />NOT LESS THAN 20 TIMES THE CABLE OUTSIDE DIAMETER WHEN THE CABLE IS
<br />UNDER A TENSILE LOAD UP TO THE RATING OF THE CABLE, USUALLY 600 LBF.
<br />7. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO PROCEEDING WITH
<br />INSTALLATION. ALL PENETRATIONS THROUGH FIRE RATED BARRIERS SHALL BE
<br />COMPLETELY SEALED WITH APPROPRIATE FIRE STOP MATERIAL IN ACCORDANCE WITH
<br />NFPA AND FIRE AUTHORITY HAVING JURISDICTION.
<br />8. ALL SECURITY PRODUCTS AND SYSTEMS SHALL BE LISTED BY A NATIONALLY RECOGNIZED
<br />TESTING LABORATORY
<br />9. ALL INTERCOM PRODUCTS SHALL BE LISTED BY A NATIONALLY RECOGNIZED LISTING LABORATORY.
<br />10. ACCESS CONTROL EQUIPMENT AND WIRING WILL BE PROVIDED BY AN OWNER APPROVED VENDOR,
<br />NOT THE ELECTRICAL CONTRACTOR.
<br />11. CCTV CAMERAS AND WIRING WILL BE PROVIDED BY AN OWNER APPROVED VENDOR, NOT THE
<br />ELECTRICAL CONTRACTOR.
<br />12. ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE DIVISION 27 EQUIPMENT
<br />SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. PROVIDE COORDINATION FOR THE
<br />INSTALLATION OF THIS RACEWAY SYSTEM WITH THE ELECTRICAL CONTRACTOR. RACEWAY
<br />INSTALLATION SHALL COMPLY WITH DIVISION 27 SPECIFICATIONS.
<br />TECHNOLOGY DRAWING INDEX
<br />SHEET
<br />DESCRIPTION
<br />ISSUED
<br />T001
<br />GENERAL INFORMATION - TECHNOLOGY
<br />Yes
<br />TD101
<br />LEVEL 1 DEMOLITION PLAN - PHASE 1 - TECHNOLOGY
<br />Yes
<br />TD102
<br />LEVEL 1 DEMOLITION PLAN - PHASE 2 - TECHNOLOGY
<br />Yes
<br />T101
<br />LEVEL 1 RENOVATION PLAN - PHASE 1 - TECHNOLOGY
<br />Yes
<br />T102
<br />LEVEL 1 RENOVATION PLAN - PHASE 2 - TECHNOLOGY
<br />Yes
<br />T201
<br />TECHNOLOGY - DETAILS
<br />Yes
<br />T202
<br />TECHNOLOGY - DETAILS
<br />Yes
<br />1715 N. Westshore Blvd., Suite 600
<br />Tampa„ Florida 33607-3999
<br />904-256-2500 Fax 904-256-2503
<br />www.rsandh.com
<br />FL Cert. Nos. AAC001886 * IB26000956
<br />5620 * LCC000210 * GB238
<br />'TLC
<br />ENGINEERING
<br />S 0 L U T 10 N So
<br />255 S. Orange Avenue
<br />Suite 1600
<br />Orlando, FL 32801
<br />P 407.841.9050
<br />www.tic-engineers.com
<br />COA 15
<br />© Copyright 2019 TLC Engineering Solutions, Inc.
<br />TLC Project No.: 119333
<br />THINK. LISTEN. CREATE.
<br />PROJECT TITLE:
<br />KITCHEN RENOVATION
<br />ADVENTHEALTH ZEPHYRHILLS
<br />PROJECT ADDRESS:
<br />7050 Gall Blvd. Zephyrhills, FL 33541
<br />Christopher V. O'Hara, P.E.
<br />Florida License #66504
<br />�`% OpHEIR������ii
<br />O
<br />.�
<br />No 66504
<br />O: STATE OF :4
<br />I�v 9234219200�rU1E000088FS.
<br />OPER�p S OR
<br />HRIST
<br />TECTURE. O=TLC EN pa ECTURE, C=US
<br />2020 03.26 1 T51:51-04'00'
<br />REVISIONS
<br />NO. DESCRIPTION DATE
<br />DATE ISSUED: 03/20/20
<br />REVIEWED BY: JTA
<br />DRAWN BY: MBR
<br />DESIGNED BY: JTA
<br />PROJECT NUMBER:
<br />504- 0226- 000
<br />© 2019 RS&H, INC.
<br />SHEET TITLE:
<br />GENERAL
<br />INFORMATION
<br />TECHNOLOGY
<br />SHEET ID:
<br />T001
<br />I PROJECT STATUS: I
<br />CONSTRUCTION DOCUMENTS
<br />A
<br />N
<br />mr
<br />0
<br />0
<br />O
<br />M
<br />N
<br />W
<br />G
<br />0
<br />U
<br />H
<br />Z
<br />uu
<br />J
<br />U
<br />U
<br />a
<br />Copyright © 2018. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the
<br />expressed written consent of this corporation is prohibited. All rights reserved.
<br />I
<br />4
<br />5
<br />
|