I.
<br />ROOF WIND DESIGN
<br />PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 •52.70 PSF (62.70)
<br />ZONE 3 = 60M PSF (70,50)
<br />ZONE 2e • 60.50 PSF (70.50)
<br />ZONE 3e = 69.80 PSF (79,80)
<br />ZONE 2n • 69.80 PSF (79.80)
<br />ZONE 3r = 83.80 PSF (93.80)
<br />ZONE 2r • 69.80 PSF (79.80)
<br />"A"• 4'-O" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT: +/- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING
<br />EXP 1140/20), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32" STRUCTURAL SHEATHING EXP 1 (40/20).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 1 Od RING SHANK GUN
<br />NAILS @ 4" O.C. EDGEWISE ZA BLOCKING ALL PANEL JOINTS W/ IN 4' OF
<br />GABLE END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA.
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />10d
<br />RINGSHANK,
<br />212"
<br />0131
<br />F1667
<br />S REW S ANK
<br />70 000
<br />RING
<br />((16-20 RINGS
<br />RSRS-03
<br />8tl
<br />RING SHANK,
<br />2 3/8'
<br />0.113
<br />SCREW SHANK
<br />pER INCH)
<br />RSRS
<br />RSRS-01
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />23/8"
<br />0,113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />KAF ItHUK IKUSb
<br />ROOF SHEATHING
<br />EXTERIOR SHEATHING
<br />0 =
<br />r
<br />USE 1/7' CDX OR 7/16' O.S.B. PLY WITH Bid RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />O
<br />j 3
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT
<br />In
<br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL,
<br />BUILDING LENGTH
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />ROOF SHEATHING ATTACHEMENT SPACING
<br />ZONE 1: tOd NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />NOTE; GABLES -DROP GABLE END & (1) ADD'L DROPPED
<br />ZONE 2e, 2n, 2r: 10d NAILS @," O.C. ON EDGE AND 4" O.C. IN FIELD
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @
<br />ZONE 3,3e, 3r: 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />16'0C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED
<br />BLOCKING PER NAILING SCHEDULE
<br />AND ADHERES TO ASCE 7-16
<br />fid RING BHANK GUN NAILS @ 0" O C.
<br />,. TOPS BOTTOM EDGES ..
<br />49
<br />V '
<br />VP FXT gHPATHING ATTAr:41MFNT
<br />o
<br />8
<br />- 10d RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING
<br />#8 7' DECK SCREWS @ 6"-8' O.C. MAX @
<br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING /
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33/C33M. MAXIMUM AGGREGATE SIZE SHALL BE 31C.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD.
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH ORWEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/4'.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO, 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 5-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-0NGROUND WHERE INDICATED ON
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />.
<br />DRAWINGSSEAMS ZAPPED BINCHES AND SEALED NTH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORMWORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FSCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS,
<br />SYP 02.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION, THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />BE SUPPORTED WITH 2'CHAIRS SPACED T-W OC, EACH WAY,
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THENFPA. TRUSS DESIGNS SHALL BE
<br />L SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />O
<br />RE AR SHALL B ASTM A615AO1 M GRADE 40 IN CONCRETE DEFORMED BAR R ASTM
<br />SHALL A S M A615
<br />B E 5N OE E S, D PLACED
<br />GRADE 80 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE
<br />MEETING THE REQUIREMENTS OF ASTM A446/A448M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN LOADS:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />D
<br />DESIGN, SE, AND ERECT WOOD TRUSSES ACCORDANCE WITH TP "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDDFOR S FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:,A AND "SCSI LATEST EDITION"
<br />ROOF: UVELOAD FLOOR: LIVE LOAD 40 psf
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO, UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARYAND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 psf TOP CHORD -np-cunent
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" NB BAR - 36'
<br />WOOD TRUSSES.
<br />10 psf BTM CHORD -nonconcurrent
<br />#5 BAR - SO' #7 BAR - 47'
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 38" x SET CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990.
<br />15 W TOP CHORD 20 psf TOP CHORD
<br />(7 psf w/ ASPHALT SHINGLES) (10 psf w/ Np GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CAN CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 psf BTM CHORD 5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 FBI
<br />WIND: DEAD LOAD SPEED MPH 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE (FBC 020) EXPOSURE C, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />BIT ATTIC
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tWT UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />, 40p NTS:
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200ps( GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40psf
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY LENGTH ELEVATIONS DIMENSIONS ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />HE TRUSS TO STRUCTURE CONNECTIONS NECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL P
<br />N D LA A L SU ERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED THE CONTRACTORS PRIOR SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Pm - 2000 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-18 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAW WILL . S
<br />SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS TO YRUSS CONNECTIONS.
<br />RO
<br />OF REPRODUCIBLE SEPIAS Of STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 26 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION'
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 FBI, FOOTING
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />SHALL BE TV* THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />CELLS TO BE FILLED.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO
<br />CONCRETE PLACEMENT, CONCRETE SLUMP SHALL NOT EXCEED 5" 4-PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318AND ASTM CM94M OR MEASURING, MIXING, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED, IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE,
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A. T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />1-1/2" FOR #SAND SMALLER
<br />2" FOR#6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SLABS, WALLS AND JOISTS
<br />1-i/Y FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />FILL CM CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O
<br />STRUCTURALSTEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A3S/A36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A500/A500M, GRADE B, Fy = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy =
<br />35 ki i. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPUCAnON
<br />91iE
<br />B-NO
<br />REMAPo(S
<br />APPLI-ON
<br />sin
<br />TYPE
<br />SPACING
<br />IREMARKS
<br />14 PT FURRING TO
<br />MASONRY/GONG.
<br />CASE MRDENEDCgL
<br />MIL11?'LONG.
<br />0"
<br />GPMGE DOOR SUCH
<br />TO MASCNRY/WNG
<br />/4"qA.
<br />OWASHER
<br />PfgN MASONRY
<br />A FASTENER
<br />0"
<br />11-BED.,<"END GIST.,
<br />11/Y EDGE q6T.
<br />91. AL. E%T.000RS
<br />CANAL110NEO CpL
<br />WINTOW4000Rl FASTENED
<br />1S DIA OR
<br />18"OIC WBCAI
<br />a°EMBED., C"ENDCIST,
<br />1x PT, BEE NOTES
<br />NNLI ZIT LONG.
<br />STAGGERED
<br />0GE
<br />INTO MA60NRYFONC.
<br />TMABC=BLICK
<br />TO MASONRY2ICNC.
<br />WWA6F�R
<br />E%PANSION BOLT
<br />2d"aC(1R'gA)
<br />SEDGE qST.
<br />WINDOVIBUCK
<br />CASE MRDENEDcaL
<br />a°D,c
<br />WINDOWIOOOfU FASTENED
<br />METAL STRAP ro
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1x PT, SEE NOTs
<br />NAIL 11 LONG.
<br />STAGGERED
<br />INTO MASONRYICONC.
<br />M-NIRYI-C,
<br />REQUIREMENTS
<br />EXT. BWNO DOOR
<br />BUCK] PT. SEE NOTE 6
<br />(Z)3'is-
<br />NO WASHER
<br />'TAPCON
<br />FASTNER
<br />10 qC
<br />11n'EMBED. O"END.
<br />DIST., 11 EDGE OST.
<br />NON-BEARINGWOOD
<br />WALL TO CONC. SLAB
<br />E AN310N A"EMBED. x"BNO
<br />WASHER BOLT ]<'O� GIST., 3"EDGEg3T.
<br />.IT WINDOW BUCK 0.138°PAFx31Po' 9'O,C <"END. q3T. 117'
<br />PT TO6NOT COL. SEE STAGGERED EDGE DISi.
<br />NOTES
<br />1. STAPLES SHALL NOT BE USED FOR ANV STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOOR$ TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4 PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6, WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL32750
<br />PH: 407-774.6078
<br />FAX: 407.774.4078
<br />www.abdesigngroup.com
<br />AA #: 0003326 A
<br />V
<br />Y
<br />14
<br />svHDLv a# LOT•
<br />ABBOTT PARK
<br />LOT# 28
<br />BLK. 12
<br />PROJECT#
<br />04181.000-28121
<br />MODELe
<br />3EAB
<br />"1504- ALLEX"
<br />GARAGE sWII40:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />%160-YPH ER. C
<br />m
<br />DATE. 06/14/21
<br />sCAL.E: 1 /4"=1 •-O"
<br />8*1ZET
<br />SN1
<br />
|