XHEZ.W-L-1017 - Through -penetration Firestop Systems Page 1 of 3
<br />System No. W-L-1017
<br />XHEZ.W-L-1017
<br />Through -penetration Firestop Systems
<br />Pace Bottom
<br />........ ..
<br />Design/System/Construction/Assembly Usage Disclaimer
<br />• Authorities Having Jurtst!"on should be consulted In all cases as to the particular requirements covering the Installation and use of UL
<br />Listed or Classified products, equipment, system, devices, and materials.
<br />• Authorities Having Jurisdiction should be consulted before construction,
<br />• Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with
<br />applicable requirements. The published Information cannot always address every construction nuance encountered In the field.
<br />• When field Issues arise, it Is recommended the first contact for assistance be the technical service staff provided by the product
<br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each
<br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate
<br />methods of construction.
<br />• Only Prodactswhoch bear ULsMark arc considered as Classified, Listed, or Reco gnid.
<br />_...... ......... ... .. ........ .... ........ ...... _..... .._.....
<br />Through -penetration Firestop Systems
<br />•F=i (g(grmatdon gLThrouph-penetration Flrritop Systems
<br />System No. W-L-1017
<br />April 30, 1998
<br />Ratings — It and 2 Hr. (See Item a)
<br />T Rating — 0 Hr
<br />L Rating At Ambient -- two than I CFM/sq ft
<br />L Rating At 400 F — less than 1 CFM/s4 ft
<br />htt://database.ul.com/c i-bin/XYV/tom late/LISEXT/1FRAME/sho a e.html?name=X... 11/2/2011
<br />XHEZ.W-L-1017 -
<br />Firestop Systems
<br />Page 2
<br />09 ■
<br />SEOT I ON
<br />1. Wag Assembly — The 1 or 2 hr fire rated gypsum wallboard/stud wall assembly side be constructed of the materials
<br />and In the manner described in the Individual U300 or U400 Series Wad or Partition Designs In the UL Fire Resistance
<br />Directory and shad Include the following construction features:
<br />A. Studs — Wait framing may consist or either wood studs or steel channel studs. Wood studs to
<br />consist of nom 2 by 4 in. cumber spaced 16 in. OC with nom 2 by 4 In, lumber arid plates and crass
<br />braces. Steel studs to be min 3.5/8 in. wide by 1-3/8 In. deep channels spaced max 24 in. OC.
<br />B. Gypsum Board* — Nom 5/8 in, thick, 4 ft. wide with square or tapered edges. The gypsum
<br />wallboard type, number of layers and sleet orientation shall be as specified in the individual Wall
<br />and Partition Design. Diem of circular through opening cut through gypsum wallboard on each site
<br />of well assembly to be mkt 0 In. (point contact) to max 1 in. larger than outside dam of flexible
<br />metal conduit (Item 2) installed in through opening. Side edge of circular opening to be mkt 3 In.
<br />from nearest stud In wail cavity.
<br />C. Fastens — When wood stud framing If employed, gypsum wallboard attached to studs with
<br />cement coated nails as specified In the individual Wall or Partition Design. When steel channel stud
<br />training Is employed, gypsum wallboard attached to studs with Type S sell-driOWg, self -tapping
<br />bugle -head steel screws as specified In the individual Wall or Partition Design.
<br />2. Through Penetrating Product* — Flexible Metal Conduit — Nom 4 in. diem (or smaller) aluminum or steel Flexible
<br />Metal Conduit+. Max one flexible metal conduit to be installed near center of circular opening in gypsum wallboard.
<br />Flexible metal conduit to be rigidly supported on both skies of wall assembly.
<br />AFC CABLE SYM04S INC
<br />3. Fill, Vold or Cavity Materials — Caulk — Caulk fill material forced Into annular space around entire circumference of
<br />through penetrating product to completely fill opening In gypsum wallboard layers on each side of the wall assembly. A min
<br />5/8 in. thickness of caulk is required for the i hr F Rating. A min 1-1/4 in. thickness of caulk Is required for the 2 hr F
<br />Rating.
<br />3M COMPANY — CP 2$WB+
<br />*(searing the UL Classfcation Matt
<br />1,13SL Ujig 11 on 1998-04-30
<br />......... _.__. --_ _ _........_._..
<br />le<rienc7 Print this pane
<br />1
<br />1 & 2 - HR FIRE RATED ELECTRICAL
<br />FLEX CONDUIT @ FRAME WALL
<br />NOT TO SCALE
<br />System No. W-L-1315
<br />XHEZ.W-L-1315
<br />Through -penetration Firestop Systems
<br />Design/System/Construction/Assembly Usage Disclaimer
<br />• Authorities Having Jurisdiction should be consulted In all castes as to the particular requirements covering the installation and use of UL
<br />Listed or Classified products, equipment, system, devices, and materials.
<br />• Authorites Having Jurisdiction should be consulted before construction.
<br />• Fire resistance assemblies and products are developed by the design submitter and have been Investigated by UL for compliance with
<br />applicable requirements. The published information cannot always address every construction nuance encountered in the field.
<br />• When field Issues arise, R Is recommended the first contact for assistance be the technical service staff provided by the product
<br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult &,a general Guide Information for each
<br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate
<br />methods of construction.
<br />• Only products which bear UL's Mark are considered as Ciusifted, Listed, or Recognized.
<br />Through -penetration Firestop Systems
<br />See Gerl•ral Information (er Threuph-pen•tr�tien Fhestgjtyst•mc
<br />System No. W-L-1315
<br />August 04, 2003
<br />FRS-1Hr
<br />T Rating — 1 Hr
<br />L Rating At Ambient -- Loss than i CFM/req ft
<br />L Rating at 400* F — 3 CFM/sq ft
<br />I
<br />X.HEZ.W-L-1084 - Through -penetration Firestop Systems Page I oft
<br />CERTIFICATIONS DIRFETORT
<br />System No. W-L-1084
<br />XHEZ.W-L-1084
<br />Through -penetration Firestop Systems
<br />P
<br />Design/System/Construction/Assembly Usage Disclaimer
<br />• Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the Installation and use of UL
<br />Listed or Classified products, equipment, system, devices, and materials.
<br />• Authorities Having Jurisdiction should be consulted before construction.
<br />• Fire resistance assemblies and products are developed by the design submitter and have been Investigated by UL for compliance with
<br />applicable requirements. The published Information cannot always address wary construction nuance encountered in the field.
<br />• When field Issues arise, it Is recommended the first contact for assistance be the technical service staff provided by the product
<br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide information for each
<br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate
<br />methods of construction.
<br />• only beer Mark considered s Classified, Listed or Recognized. ll
<br />... __ .......... ....... .......... _ .......
<br />Through -penetration Firestop Systems
<br />S•e Garhergj jp��hatian for'mrouah-penetratlorw Fir•Sxeo 5vstems
<br />System No. W-L-1084
<br />July 29, 1995
<br />F Rating — 1 H►
<br />T Rating — 0 Hr
<br />.rl A)
<br />SECTION A -A
<br />1. Wall Assembly — The fine rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the
<br />manner specified In the Individual U300 or U400 Series Wad and Partition Designs in the UL Flee Resistance Directory and
<br />htt ://dattabase.ul.com/c i-bin/XYV/teen late/LISEXT/IFRA.ME/show a e.html?name=X... I112/2011
<br />XHEZ.W-L-1315 - Through -penetration Firestop Systems Page 2 of 3
<br />iI iI I it If 1 �A
<br />tt it ii 11 tl I
<br />Ii If it it
<br />It Ii C I
<br />tl it If If I
<br />itDB
<br />it
<br />A 1 li
<br />t I I
<br />t tI
<br />B t I
<br />1 1
<br />LA
<br />I �A
<br />t I rGJ"'t
<br />t 1
<br />e1
<br />I 1
<br />[ f i
<br />t 1 1
<br />{ i1
<br />t if
<br />IE 1 {{{ 1
<br />fC I1 ft tl { I
<br />tt it Ir tt i
<br />fill I ll t
<br />It it It if 1
<br />It 12 1 It Il l
<br />IC ti if tl 1
<br />-r>tE-&A
<br />1. Wall Assembly — The fire -rated gypsum boartf/stud wall assembly shall be constructed of the materials and In the
<br />manner specified In the Individual U300 or U400 Series Wall and Partltton Designs In the UL Fire Resistance Directory and
<br />shall Include the following construction features:
<br />A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to
<br />consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 In. (406 mm) OC. Steel studs to be
<br />min 3-5/8 In. (92 mm) wide and spaced max 24 In. (610 mm) OC.
<br />8. Insulation* — R13 (or higher) glass fiber or mineral fiber batt insulation friction fitted into stud
<br />cavity.
<br />C. Gypsum Board* — One layer of nom 5/8 In. (18 mm) thick gypsum board, as specified In the
<br />Individual Wall and Partition Design. Max diam of opening Is 4.1/2 In. (114 mm)..
<br />2. Piping system — The piping system for use in dosed (process or supply) or vented (drain, waste or vent) piping
<br />systems shall consist of the following:
<br />A. Swell or Iron Pipe — Nom 3 in. (76 mm) diam (or smaller) cast or ductile iron pipe or Schedule
<br />40 (or heavier) steel pipe, installed within stud cavity and connected to tee. The tee penetrates wall
<br />on one side and is Installed either concentrically or eccentrically within the Rrestop system. The
<br />annular space between the toe and the edge of the opening shag be min 3/8 in. (10 mm) to max
<br />5/8 in. (16 mm).
<br />S. Shielded Slip on Coupling — Nom 3 in. (76 mm) diem (or smaller) 32 gauge (or heavier)
<br />corrugated stainless steel shielded rubber coupling. Coupling to be secured to tee with stainless
<br />steel hose clamp at any point beyond the surface of wall, or may extend a max of i in. into
<br />opening. When coupling extends Into opening, the annular space between the coupling and the
<br />edge of the opening shall be min 114 in. (6 mm) to max 112 In. (13 men).
<br />C. Drench Piping — Branch pipe is secured to shielded slip on coupling with stainless steel hose
<br />damp and may consist of the following:
<br />1. Polyvinyl Chloride (PVC) Pipe — Nom 3 in. (76 mm) diem (or smaller)
<br />Schedule 40 solid care PVC pipe.
<br />2. Steel or Iron Pipe — Nom 3 In. (76 men) diem (or smaller) cost or
<br />ductile iron pipe or Schedule 40 (or heavier) steel pipe.
<br />ht ://database.ul.com/c i-bin/XYV/teen late/LISEXT/iFRAME/sho a e.html?name=X... 11/2/2011
<br />W-L-1084 -
<br />Firestop Systems
<br />Page 2 of 2
<br />shall include the following construction features:
<br />A. Studs — Wall ftaming may Consist of either wood studs or steel channel studs. Wood studs to
<br />consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3-5/8 In. wide and spaced
<br />max 24 in. OC.
<br />S. G rp•um Board* — Nom 5/e in. thick gypsum wallboard, as specified in the Individual Wall and
<br />Partition Design. Diem of opening is 1-1/2 In. larger then the outside diem of pipe.
<br />2. Through-Porsetrant — One metallic (ripe, conduit or tubing to be centered within the flrestop system. An annular space
<br />of 3/4 in. is required within the ttrestw system. Pipe, conduit or tubing to be rigidly supported on both sides of wall
<br />assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
<br />A. Steel Pipe — Nom 12 in, diem (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Conduit — Nom 6 In. diem (or smaller) electrical metallic tube g or steal conduit.
<br />C. Copper Tlubbig — Nom 6 In. diem (or smaller) Type L (or heavier) copper tubing.
<br />D. Copper Pipe — Nom 6 in. diem (or smaller) Regular (or heavier) copper pipe.
<br />* —
<br />.� V N 1 tan •� Min in. 1 f fill m withinannulus,O h rill h 3 old a ct ataNe SN t S 8 th duress o material applied th us t both
<br />/
<br />! �i pp
<br />surfaces of wail assembly.
<br />314 COMPANY — FS-2000+
<br />•bearing the UL Classification Mark
<br />j on 1995-07-29
<br />rill en Notice of Disclaimer Pwa Too
<br />a
<br />The appearance of a company's name or product in this database does not in Itself assure that products so Identified have been manufactured
<br />under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow -Up
<br />Service. Always kook for the Mark on the product.
<br />UL permits the reproduction of the material contained In the Onfine Certification Directory subject to the following conditions: 1. The Guile
<br />Information, Designs and/or Listings (files) must be presented In their entirety and In a non -misleading manner, without any manipulation of the
<br />data (or drawngs). 2. The statement "Reprinted from the Online Certifications Directory with permission from Undervrrlters Laboratories Inc." must
<br />appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice In the following format: -Copyright O
<br />2011 Underwriters Laboratories Inc.49"
<br />A- it C a pe n 0 0 pi as g an i; a l dun *If Kina to, a ha,Bl 0 1 w'tn iniepil: y, piaro-Gibr. and Mn�*'94t (jr.
<br />1 & 2 - HR FIRE RATED CONDUIT
<br />PIPE FRAME WALL
<br />3. Fail, Vold or Cavity Materials* — Seelant — Min 518 In. (16 mm) thickness of fill material applied within the annulus,
<br />flush with surface of wad.
<br />NUCO 1(NC — Self Seat GG-266
<br />*Gearing the UL Classification Mark
<br />t ae��'� on 2003-08-04
<br />n t this gAgg Psae Too
<br />4.
<br />The appearance of a company's name or product In this database does not in Itself assure that products So identified have been manufactured
<br />under UVS Follow -Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow -Up
<br />Service. Always Wok for the Mark on the product.
<br />UL permits the reproduction of the material contained In the Online Certification Directory subject to the following condRloric 1. The Guide
<br />Information, Designs and/or Listings (Iles) must be prevented In their entirety and In a non -misleading manner, without any manipulation of the
<br />data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwr ten Laboratories Inc." must
<br />appear adjscent to tin extracted material. In addition, the reprinted material must include a copyright notice In the following format: "Copyright Cf
<br />2011 Underwriters Laboratories Inc.®'
<br />An in4span4001 A,eaniralluo *oikloq for a ba'e't o.rid w.th n1+/9111r. plorlilan 4n4 nnOn'edor.
<br />/1
<br />1 - HR FIRE RATED PIPE
<br />PENTRATION @ FRAME WALL
<br />SAMUEL OLMEDO
<br />ARCH I T E C T
<br />FL. REG. AR0015027
<br />TEL. 407. 967. 3109
<br />soarcht @ yahoo.com
<br />P.O. BOX 784825
<br />WINTER GARDEN, FL. 34778
<br />PERMIT SET
<br />REVISIONS:
<br />NO DATE DESCRIPTION
<br />3-25-12 JII CORP
<br />INSTRUMENTS OF SERVICE OWNERSHIP
<br />ALL REPORTS, PLANS, SPECIFICATIONS,
<br />COMPUTER FILES, FIELD DATA, NOTES
<br />INSTRUMENTS PREPARED BY THE
<br />AND OTHER DOCUMENTS AND RELATED
<br />INSTRUMENTS PREPARED BY THE
<br />ARCHITECT OR CONSULTANTS AS
<br />INTRUMENTS OF SERVICE SHALL REMAIN
<br />THE PROPERTY OF THE ARCHITECT OR
<br />CONSULTANT. THE ARCHITECT AND OR
<br />THE CONSULTANT SHALL RETAIN ALL
<br />COMMON LAW, STATUTORY AND OTHER
<br />RESERVED RIGHTS, INCLUDING THE
<br />COPYRIGHT THERETO.
<br />RESTAURANT