XHEZ.W-L-1017 - Through -penetration Firestop Systems Page 1 of 3 <br />System No. W-L-1017 <br />XHEZ.W-L-1017 <br />Through -penetration Firestop Systems <br />Pace Bottom <br />........ .. <br />Design/System/Construction/Assembly Usage Disclaimer <br />• Authorities Having Jurtst!"on should be consulted In all cases as to the particular requirements covering the Installation and use of UL <br />Listed or Classified products, equipment, system, devices, and materials. <br />• Authorities Having Jurisdiction should be consulted before construction, <br />• Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with <br />applicable requirements. The published Information cannot always address every construction nuance encountered In the field. <br />• When field Issues arise, it Is recommended the first contact for assistance be the technical service staff provided by the product <br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each <br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate <br />methods of construction. <br />• Only Prodactswhoch bear ULsMark arc considered as Classified, Listed, or Reco gnid. <br />_...... ......... ... .. ........ .... ........ ...... _..... .._..... <br />Through -penetration Firestop Systems <br />•F=i (g(grmatdon gLThrouph-penetration Flrritop Systems <br />System No. W-L-1017 <br />April 30, 1998 <br />Ratings — It and 2 Hr. (See Item a) <br />T Rating — 0 Hr <br />L Rating At Ambient -- two than I CFM/sq ft <br />L Rating At 400 F — less than 1 CFM/s4 ft <br />htt://database.ul.com/c i-bin/XYV/tom late/LISEXT/1FRAME/sho a e.html?name=X... 11/2/2011 <br />XHEZ.W-L-1017 - <br />Firestop Systems <br />Page 2 <br />09 ■ <br />SEOT I ON <br />1. Wag Assembly — The 1 or 2 hr fire rated gypsum wallboard/stud wall assembly side be constructed of the materials <br />and In the manner described in the Individual U300 or U400 Series Wad or Partition Designs In the UL Fire Resistance <br />Directory and shad Include the following construction features: <br />A. Studs — Wait framing may consist or either wood studs or steel channel studs. Wood studs to <br />consist of nom 2 by 4 in. cumber spaced 16 in. OC with nom 2 by 4 In, lumber arid plates and crass <br />braces. Steel studs to be min 3.5/8 in. wide by 1-3/8 In. deep channels spaced max 24 in. OC. <br />B. Gypsum Board* — Nom 5/8 in, thick, 4 ft. wide with square or tapered edges. The gypsum <br />wallboard type, number of layers and sleet orientation shall be as specified in the individual Wall <br />and Partition Design. Diem of circular through opening cut through gypsum wallboard on each site <br />of well assembly to be mkt 0 In. (point contact) to max 1 in. larger than outside dam of flexible <br />metal conduit (Item 2) installed in through opening. Side edge of circular opening to be mkt 3 In. <br />from nearest stud In wail cavity. <br />C. Fastens — When wood stud framing If employed, gypsum wallboard attached to studs with <br />cement coated nails as specified In the individual Wall or Partition Design. When steel channel stud <br />training Is employed, gypsum wallboard attached to studs with Type S sell-driOWg, self -tapping <br />bugle -head steel screws as specified In the individual Wall or Partition Design. <br />2. Through Penetrating Product* — Flexible Metal Conduit — Nom 4 in. diem (or smaller) aluminum or steel Flexible <br />Metal Conduit+. Max one flexible metal conduit to be installed near center of circular opening in gypsum wallboard. <br />Flexible metal conduit to be rigidly supported on both skies of wall assembly. <br />AFC CABLE SYM04S INC <br />3. Fill, Vold or Cavity Materials — Caulk — Caulk fill material forced Into annular space around entire circumference of <br />through penetrating product to completely fill opening In gypsum wallboard layers on each side of the wall assembly. A min <br />5/8 in. thickness of caulk is required for the i hr F Rating. A min 1-1/4 in. thickness of caulk Is required for the 2 hr F <br />Rating. <br />3M COMPANY — CP 2$WB+ <br />*(searing the UL Classfcation Matt <br />1,13SL Ujig 11 on 1998-04-30 <br />......... _.__. --_ _ _........_._.. <br />le<rienc7 Print this pane <br />1 <br />1 & 2 - HR FIRE RATED ELECTRICAL <br />FLEX CONDUIT @ FRAME WALL <br />NOT TO SCALE <br />System No. W-L-1315 <br />XHEZ.W-L-1315 <br />Through -penetration Firestop Systems <br />Design/System/Construction/Assembly Usage Disclaimer <br />• Authorities Having Jurisdiction should be consulted In all castes as to the particular requirements covering the installation and use of UL <br />Listed or Classified products, equipment, system, devices, and materials. <br />• Authorites Having Jurisdiction should be consulted before construction. <br />• Fire resistance assemblies and products are developed by the design submitter and have been Investigated by UL for compliance with <br />applicable requirements. The published information cannot always address every construction nuance encountered in the field. <br />• When field Issues arise, R Is recommended the first contact for assistance be the technical service staff provided by the product <br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult &,a general Guide Information for each <br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate <br />methods of construction. <br />• Only products which bear UL's Mark are considered as Ciusifted, Listed, or Recognized. <br />Through -penetration Firestop Systems <br />See Gerl•ral Information (er Threuph-pen•tr�tien Fhestgjtyst•mc <br />System No. W-L-1315 <br />August 04, 2003 <br />FRS-1Hr <br />T Rating — 1 Hr <br />L Rating At Ambient -- Loss than i CFM/req ft <br />L Rating at 400* F — 3 CFM/sq ft <br />I <br />X.HEZ.W-L-1084 - Through -penetration Firestop Systems Page I oft <br />CERTIFICATIONS DIRFETORT <br />System No. W-L-1084 <br />XHEZ.W-L-1084 <br />Through -penetration Firestop Systems <br />P <br />Design/System/Construction/Assembly Usage Disclaimer <br />• Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the Installation and use of UL <br />Listed or Classified products, equipment, system, devices, and materials. <br />• Authorities Having Jurisdiction should be consulted before construction. <br />• Fire resistance assemblies and products are developed by the design submitter and have been Investigated by UL for compliance with <br />applicable requirements. The published Information cannot always address wary construction nuance encountered in the field. <br />• When field Issues arise, it Is recommended the first contact for assistance be the technical service staff provided by the product <br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide information for each <br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate <br />methods of construction. <br />• only beer Mark considered s Classified, Listed or Recognized. ll <br />... __ .......... ....... .......... _ ....... <br />Through -penetration Firestop Systems <br />S•e Garhergj jp��hatian for'mrouah-penetratlorw Fir•Sxeo 5vstems <br />System No. W-L-1084 <br />July 29, 1995 <br />F Rating — 1 H► <br />T Rating — 0 Hr <br />.rl A) <br />SECTION A -A <br />1. Wall Assembly — The fine rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the <br />manner specified In the Individual U300 or U400 Series Wad and Partition Designs in the UL Flee Resistance Directory and <br />htt ://dattabase.ul.com/c i-bin/XYV/teen late/LISEXT/IFRA.ME/show a e.html?name=X... I112/2011 <br />XHEZ.W-L-1315 - Through -penetration Firestop Systems Page 2 of 3 <br />iI iI I it If 1 �A <br />tt it ii 11 tl I <br />Ii If it it <br />It Ii C I <br />tl it If If I <br />itDB <br />it <br />A 1 li <br />t I I <br />t tI <br />B t I <br />1 1 <br />LA <br />I �A <br />t I rGJ"'t <br />t 1 <br />e1 <br />I 1 <br />[ f i <br />t 1 1 <br />{ i1 <br />t if <br />IE 1 {{{ 1 <br />fC I1 ft tl { I <br />tt it Ir tt i <br />fill I ll t <br />It it It if 1 <br />It 12 1 It Il l <br />IC ti if tl 1 <br />-r>tE-&A <br />1. Wall Assembly — The fire -rated gypsum boartf/stud wall assembly shall be constructed of the materials and In the <br />manner specified In the Individual U300 or U400 Series Wall and Partltton Designs In the UL Fire Resistance Directory and <br />shall Include the following construction features: <br />A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to <br />consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 In. (406 mm) OC. Steel studs to be <br />min 3-5/8 In. (92 mm) wide and spaced max 24 In. (610 mm) OC. <br />8. Insulation* — R13 (or higher) glass fiber or mineral fiber batt insulation friction fitted into stud <br />cavity. <br />C. Gypsum Board* — One layer of nom 5/8 In. (18 mm) thick gypsum board, as specified In the <br />Individual Wall and Partition Design. Max diam of opening Is 4.1/2 In. (114 mm).. <br />2. Piping system — The piping system for use in dosed (process or supply) or vented (drain, waste or vent) piping <br />systems shall consist of the following: <br />A. Swell or Iron Pipe — Nom 3 in. (76 mm) diam (or smaller) cast or ductile iron pipe or Schedule <br />40 (or heavier) steel pipe, installed within stud cavity and connected to tee. The tee penetrates wall <br />on one side and is Installed either concentrically or eccentrically within the Rrestop system. The <br />annular space between the toe and the edge of the opening shag be min 3/8 in. (10 mm) to max <br />5/8 in. (16 mm). <br />S. Shielded Slip on Coupling — Nom 3 in. (76 mm) diem (or smaller) 32 gauge (or heavier) <br />corrugated stainless steel shielded rubber coupling. Coupling to be secured to tee with stainless <br />steel hose clamp at any point beyond the surface of wall, or may extend a max of i in. into <br />opening. When coupling extends Into opening, the annular space between the coupling and the <br />edge of the opening shall be min 114 in. (6 mm) to max 112 In. (13 men). <br />C. Drench Piping — Branch pipe is secured to shielded slip on coupling with stainless steel hose <br />damp and may consist of the following: <br />1. Polyvinyl Chloride (PVC) Pipe — Nom 3 in. (76 mm) diem (or smaller) <br />Schedule 40 solid care PVC pipe. <br />2. Steel or Iron Pipe — Nom 3 In. (76 men) diem (or smaller) cost or <br />ductile iron pipe or Schedule 40 (or heavier) steel pipe. <br />ht ://database.ul.com/c i-bin/XYV/teen late/LISEXT/iFRAME/sho a e.html?name=X... 11/2/2011 <br />W-L-1084 - <br />Firestop Systems <br />Page 2 of 2 <br />shall include the following construction features: <br />A. Studs — Wall ftaming may Consist of either wood studs or steel channel studs. Wood studs to <br />consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3-5/8 In. wide and spaced <br />max 24 in. OC. <br />S. G rp•um Board* — Nom 5/e in. thick gypsum wallboard, as specified in the Individual Wall and <br />Partition Design. Diem of opening is 1-1/2 In. larger then the outside diem of pipe. <br />2. Through-Porsetrant — One metallic (ripe, conduit or tubing to be centered within the flrestop system. An annular space <br />of 3/4 in. is required within the ttrestw system. Pipe, conduit or tubing to be rigidly supported on both sides of wall <br />assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe — Nom 12 in, diem (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Conduit — Nom 6 In. diem (or smaller) electrical metallic tube g or steal conduit. <br />C. Copper Tlubbig — Nom 6 In. diem (or smaller) Type L (or heavier) copper tubing. <br />D. Copper Pipe — Nom 6 in. diem (or smaller) Regular (or heavier) copper pipe. <br />* — <br />.� V N 1 tan •� Min in. 1 f fill m withinannulus,O h rill h 3 old a ct ataNe SN t S 8 th duress o material applied th us t both <br />/ <br />! �i pp <br />surfaces of wail assembly. <br />314 COMPANY — FS-2000+ <br />•bearing the UL Classification Mark <br />j on 1995-07-29 <br />rill en Notice of Disclaimer Pwa Too <br />a <br />The appearance of a company's name or product in this database does not in Itself assure that products so Identified have been manufactured <br />under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow -Up <br />Service. Always kook for the Mark on the product. <br />UL permits the reproduction of the material contained In the Onfine Certification Directory subject to the following conditions: 1. The Guile <br />Information, Designs and/or Listings (files) must be presented In their entirety and In a non -misleading manner, without any manipulation of the <br />data (or drawngs). 2. The statement "Reprinted from the Online Certifications Directory with permission from Undervrrlters Laboratories Inc." must <br />appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice In the following format: -Copyright O <br />2011 Underwriters Laboratories Inc.49" <br />A- it C a pe n 0 0 pi as g an i; a l dun *If Kina to, a ha,Bl 0 1 w'tn iniepil: y, piaro-Gibr. and Mn�*'94t (jr. <br />1 & 2 - HR FIRE RATED CONDUIT <br />PIPE FRAME WALL <br />3. Fail, Vold or Cavity Materials* — Seelant — Min 518 In. (16 mm) thickness of fill material applied within the annulus, <br />flush with surface of wad. <br />NUCO 1(NC — Self Seat GG-266 <br />*Gearing the UL Classification Mark <br />t ae��'� on 2003-08-04 <br />n t this gAgg Psae Too <br />4. <br />The appearance of a company's name or product In this database does not in Itself assure that products So identified have been manufactured <br />under UVS Follow -Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow -Up <br />Service. Always Wok for the Mark on the product. <br />UL permits the reproduction of the material contained In the Online Certification Directory subject to the following condRloric 1. The Guide <br />Information, Designs and/or Listings (Iles) must be prevented In their entirety and In a non -misleading manner, without any manipulation of the <br />data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwr ten Laboratories Inc." must <br />appear adjscent to tin extracted material. In addition, the reprinted material must include a copyright notice In the following format: "Copyright Cf <br />2011 Underwriters Laboratories Inc.®' <br />An in4span4001 A,eaniralluo *oikloq for a ba'e't o.rid w.th n1+/9111r. plorlilan 4n4 nnOn'edor. <br />/1 <br />1 - HR FIRE RATED PIPE <br />PENTRATION @ FRAME WALL <br />SAMUEL OLMEDO <br />ARCH I T E C T <br />FL. REG. AR0015027 <br />TEL. 407. 967. 3109 <br />soarcht @ yahoo.com <br />P.O. BOX 784825 <br />WINTER GARDEN, FL. 34778 <br />PERMIT SET <br />REVISIONS: <br />NO DATE DESCRIPTION <br />3-25-12 JII CORP <br />INSTRUMENTS OF SERVICE OWNERSHIP <br />ALL REPORTS, PLANS, SPECIFICATIONS, <br />COMPUTER FILES, FIELD DATA, NOTES <br />INSTRUMENTS PREPARED BY THE <br />AND OTHER DOCUMENTS AND RELATED <br />INSTRUMENTS PREPARED BY THE <br />ARCHITECT OR CONSULTANTS AS <br />INTRUMENTS OF SERVICE SHALL REMAIN <br />THE PROPERTY OF THE ARCHITECT OR <br />CONSULTANT. THE ARCHITECT AND OR <br />THE CONSULTANT SHALL RETAIN ALL <br />COMMON LAW, STATUTORY AND OTHER <br />RESERVED RIGHTS, INCLUDING THE <br />COPYRIGHT THERETO. <br />RESTAURANT <br />INTERIOR BUILD —OUT <br />FOR: <br />JEREMIAH'S <br />TALIAN ICE <br />7936 GALL BLVD <br />ZEPHYRHILLS, FL 33541 <br />SHEET <br />F. R. PENETRATIONS <br />DETAILS <br />FR1 <br />r- <br />N <br />O <br />e-i <br />O <br />U <br />w <br />H <br />NOT TO SCALE <br />