SPLIT SYSTEM / HEAT PUMP UNIT SCHEDULE <br />PLAN MARK <br />AHU-I <br />AHU-2 t 3 <br />AHU-4 <br />SYSTEM TYPE <br />SPLIT HP <br />SPLIT HP <br />SPLIT AC <br />NOMINAL TONS <br />1.5 <br />1.5 <br />4,0 <br />SUPPLY AIR FLOW (CFM) <br />2400 - FAN SET - LOU) <br />2400 - FAN SET - LOW <br />1531 FAN SET TAP3 <br />OUTSIDE AIR FLOW (CFM) <br />385 <br />669 / 686 <br />210 <br />COIL: - <br />TOTAL CAPACITY (MBH) <br />88,800 <br />88000 <br />43,500 <br />SENSIBLE CAPACITY (MBH) <br />62,160 <br />62,160 <br />30,450 <br />LATENT CAPACITY (MBH) <br />26,640 <br />26,640 <br />13,050 <br />AIR HANDLER <br />MODEL <br />40RUQAOST•A(3/5) <br />40RUQA08T•A(3/5) <br />F154CNP048L <br />STATIC PRESS. (EXT./TOTAL) <br />-6 <br />,6 <br />.5 <br />MOTOR SPEED <br />— <br />— <br />— <br />HEATER: <br />STAGES <br />I <br />I <br />1 <br />KW <br />10 <br />10 <br />10 <br />COMPRESSORS <br />STAGES <br />2 <br />2 <br />1 <br />PH/RLA/LRA <br />3/25,2/164 <br />3/25.2/164 <br />1/21,8/111 <br />UNIT POWER REQUIREMENTS: <br />VOLTS/o <br />208/230-3 <br />208/230-3 <br />208/230-1 <br />MCA <br />35 <br />35 <br />52,8 <br />MFS <br />50 <br />50 <br />60 <br />SEER/EER <br />12.1 <br />12.1 <br />14.0 <br />MANUFACTURER <br />CARRIER <br />CARRIER <br />CARRIER <br />MODEL NUMBER - CONDENSING UNIT <br />38AUQ090D <br />38AUQ090D <br />24ACC448A <br />AIR BALANCE SCHEDULE <br />AHU 1 <br />OUTSIDE AIR INTAKE CFM <br />+385 <br />SUPPLY AIR CFM <br />+2400 <br />RETURN AIR CFM <br />-915 <br />EXHAUST FAN CFM <br />-100 <br />TOTAL BUILDING PRESSURE <br />"O" CFM <br />AHU 2 <br />OUTSIDE AIR INTAKE CFM <br />+669 <br />SUPPLY AIR CFM <br />+2400 <br />RETURN AIR CFM <br />-1511 <br />EXHAUST FAN CFM <br />-160 <br />TOTAL BUILDING PRESSURE <br />"O" CFM <br />AHU 3 <br />OUTSIDE AIR INTAKE CFM <br />+686 <br />SUPPLY AIR CFM <br />+2400 <br />RETURN AIR CFM <br />-1114 <br />TOTAL BUILDING PRESSURE <br />"O" CFM <br />AHU 4 <br />1 OUTSIDE AIR INTAKE CFM <br />+210 <br />SUPPLY AIR CFM <br />+1531 <br />RETURN AIR CFM <br />-1321 <br />TOTAL BUILDING PRESSURE <br />"O" GFM <br />OUTSIDE AIR CALCULATION <br />2 <br />MIN. <br />AHU <br />SQ, FT. AREA <br />CFM/PRSN + CFM/FT <br />O.A. CFM <br />CATEGORY: OFFICE BUILDING / OFFICE SPPCE <br />1 <br />3500 5 X 35 + .O6 X 3500 385 <br />AHU <br />SQ. FT, AREA <br />CFM/PRSN + CFM/FT 2 <br />MIN, <br />O.A, CFM <br />CATEGORY: MISC./GENERAL MANUFACTURING <br />2 <br />3361 10 X 5 + .11 X 3361 669 <br />2 <br />MIN. <br />AHU <br />SQ. FT, AREA <br />CFM/PRSN + CFM/FT <br />O.A. CFM <br />CATEGORY: MISC./GENERAL MANUFACTURING <br />3 <br />62fo1 10 X 5 + .11 X 6261 686 <br />2 <br />MIN, <br />AHU <br />SQ, FT. AREA <br />GFM[/PRSN + CFM/FT <br />O.A. CFM <br />CATEGORY: MISC./STORAGE <br />4 <br />3500 O X 0+ ,06 X 3500 210 <br />FAN SCHEDULE <br />FAN# <br />MFG. / MODEL <br />TYPE <br />CFM <br />S.P.MG. <br />VOLTS <br />AMPS <br />EF-1 <br />BROAN / QT110LE <br />CEILING EXH. <br />110 <br />0.1" <br />120V <br />.7 <br />EF-2 <br />BROAN / QT50LE <br />CEILING EXH. <br />50 <br />0.1" <br />120V <br />7 <br />MECHANICAL. GENERAL NOTES <br />I, DUCT SHALL BE SECURELY SUPPORTED, HUNG OR SUSPENDED IN ACCORDANCE WITH THE LATEST SMACNA EDITION AND <br />FLORIDA BUILDING CODE MECHANICAL CODE 2011. <br />2, PROVIDE ALL MECHANICAL EQUIPMENT WITH MANUFACTURER'S RECOMMENDED SERVICE AREA CLEARANCES. <br />3, IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED. <br />4, AIR DEVICE LOCATIONS MAY BE ADJUSTED IN COORDINATION WITH LIGHT FIXTURES. <br />5, DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS, DUCTWORK DIFFUSERS REGISTERS, GRILLES AND <br />OTHER ITEMS OF THE AIR HANDLING SYSTEM SHALL NOT BE SUPPORTED BY THE CEILING OR CEIILING SUSPENSION SYSTEM. <br />6, PROVIDE A TRAP IN ALL CONDENSATE PIPING LOCATED AT AIR HANDLING UNITS. SLOPE CONDENSATE LINES 1/8" PER FOOT, <br />CONDENSATE LINES SHALL BE PVC SCH 40. ALL CONDENSATE DRAIN TRAP DETAIL. <br />1. ALL MECHANICAL WORK SHALL MEET ALL THE REQUIREMENTS OF THE 2011" FLORIDA BUILDING CODE MECHANICAL . <br />MECHANICAL NOTES: <br />1. PROVIDE MANUAL DAMPER AT ALL BRANCH CONNECTIONS, SEE DETAIL. <br />2. ALL MECHANICAL WORKS AND INSTALLATIONS SHALL COMPLY WITH FLORIDA MECHANICAL CODE, ASHRAE AND SMACNA STANDARDS <br />3. COORDINATE DIFFUSERS AND GRILLE LOCATIONS WITH OTHER TRADES. <br />4. ALL FLEX FIBERGLASS INSULATION R-6, INSTALL PER LATEST SMACNA STANDARDS. <br />5. OUTSIDE AIR INTAKES EXISTING/ CONFIRM ARE MIN. 10 FEET FROM ANY EXHAUST OR PLUMBING VENTS. <br />6, COORDINATE ALL MECHANICAL WORK INCLUDING EQUIPMENT DUCT WORK OR PIPING WITH ARCHITECT AND OTHER TRADES PRIOR TO WORK, <br />1. ALL INSULATION, MATERIAL, COVERINGS, ADHESIVES, VAPOR BARRIERS NOT TO EXCEED 25 AND SMOKE DEVELOPMENT NOT TO EXCEED 50 <br />8, DUCT TAPES SHALL CONFORM TO NFPA 90A, FLAMESPREAD CLASSIFICATION. <br />S. EXHAUST DUCTS MUST TERMINATE 10' HORIZONTALLY FROM OR 3' ABOVE ALL AIR INTAKES. <br />10. T-STAT LOCATIONS) TO BE DETERMINED BY INSTALLING HVAC CONTRACTOR. <br />II. CONTRACTOR TEST AND BALANCE AIR DISTRIBUTION CFM AS LISTED, <br />HVAC <br />SPECIFICATIONS: <br />EXHAUST FANS: <br />FURNISH EXHAUST FAN WITH PERFORMANCE AND CAPACITIES AS LISTED ON THE DESIGN DRAWINGS. <br />AIR DISTRIBUTION EQUIPMENT: FURNISH SUPPLY AIR DIFFUSERS AND RETURN AIR REGISTER WITH MANUAL BALANCING DAMPERS <br />DUCTWORK: PROVIDE AND INSTALL AIR DISTRIBUTION SYSTEM AS INDICATED IN DESIGN DRAWINGS, <br />ALL PLENUM RIGID SUPPLY AIR AND RETURN AIR DUCTWORK <br />WRAPPED WITH 2" THCK R-6 FIBROUS GLASS DUCT WRAP WITH AND FSX VAPOR BARRIER. ALL FLEXIBLE SUPPLY <br />AIR AND RETURN AIR DUCTWORK SHALL BE CONSTRUCTED TO R-6 REQUIREMENTS. ALL EXHAUST AIR DUCTWORK SHALL BE FLEXIBLE <br />ALUMNIZED DUCT. ALL OUTDOOR AIR DUCTWORK SHALL BE GALV STEEL SNAPLOCK. ALL DUCT AND INSULATION JOINTS SHALL BE WITH <br />GLASS FAB AND APPROVED MASTIC FABRICATED AND SUPPORT ALL DUCTWORK IN ACCORDANCE WITH SMACNA. DUCT DIMENSIONS <br />REFERENCED ARE CLEAR INSIDE DIMENSIONS. FLEXIBLE DUCT IS THE SAME AS THE NECK SIZE. <br />APPLY 2" THICK 0.15 POUND DENSITY FIBERGLASS INSULATION WITH AN FSX VAPOR BARRIER AND GLASS FAB AND MASTIC TO THE <br />TOPS OF ALL SUPPLY AIR DIFFUSER AND REGISTERS. <br />ALL DUCT BRACES SHALL BE EQUIPPED WITH MANUAL VOLUME DAMPERS WITH THE REGULATORS ACCESSIBLE. <br />CONDENSATE PIPING - ALL CONDENSATE PIPING SHALL BE WHITE SCHEDULE 40 PVC ALL HORIZONTAL PIPE SHALL <br />BE INSULATED WITH SOLVENT WELDED OR THREADED FITTINGS. <br />TO AIR WANDLER— <br />THRU FIRST FLOOR <br />CEILING SPACE <br />'e tl <br />INSULATED SUCTION <br />LINE (NO JOINTS ALLOWED) <br />SEE FLOOR PLAN <br />FOR PIPE SIZES <br />LIQUID LINE —� <br />(NO JOINTS ALLOWED) <br />DRILL TO FIT OUTSIDE <br />OF REFRIG. LINES <br />CAULK WATER TIGHT <br />METAL BOOT PAINTED TO <br />MATCH EXTERIOR FACADE <br />IF REFRIG, LINES RUN <br />IN CEILING SPACE <br />FASTENED TO WALL BOTH <br />SIDES W/ 111XI/8" <br />SCREWS 18" APART <br />SUCTION CONNECTION <br />LIQUID CONNECTION <br />COND. UNIT TO BE SECURED <br />WITH (4) KWIK BOLT 3" WITH 2 <br />1/2" MIN EMBED <br />4" CONCRETE SLAB <br />— CAULK W/3M <br />CP-25 OR EQUAL <br />PROVIDE 4" PVC SCW-40 <br />SLEEVE IF REFRIG. LINES <br />RUN UNDER SLAB <br />CONDENSING UNIT MOUNTING DETAIL <br />NITS <br />METAL WALL CAP <br />W/ BACKDRAFT DAMPER <br />AND BIRD SCREEN <br />12 ga, HANGER WIRE <br />AL SUPPORT <br />AP MIN. 1 I WIDE <br />BACK DRAFT <br />DAMPER <br />FAN <br />HOUSING <br />WALL / <br />FLASHING A OPENING L SUSPENDED <br />SEAL WALL CAP O CEILING TILES <br />IV <br />REMOVABLE GRILL <br />w NOTE: <br />EXHAUST AIR DUCTS TO BE GALV. <br />METAL OR THERMARN ALUM. <br />FAN WEIGHT: +/- 5 LBS <br />EXHAUST FAN DETAIL <br />IN SUSPENDED CEILING <br />SCALE: N.T.S. <br />EF OPTION 1 - FIELD DECIDED <br />FLOAT SWITCH IN SECONDARY DRAIN <br />LINE TO DISABLE AHU SHOULD <br />AIR HANDLING UNIT <br />VENT CLEANOUT WITH <br />SLIP -FIT (NOT SCREW) <br />CAP WITH DRILLED HOLE <br />T MIN. <br />4' _ <br />PITCH TO OFFSET LINE <br />FRICTION MINIMUM 1/8' <br />PER FOOT <br />CONDENSATE TRAP DETAIL <br />NOT TO SCALE <br />TYPICAL SPINAN FITTING W/DAMPER <br />DRAW BAND FOR INTERIOR LINER <br />SUPPORTS 5 f DISTANCE <br />Im WIDE MIN. <br />ATYPICAL DIFFUSER <br />EXTERIOR LINER SEAL AND FASTEN TO DUCT TRUNK <br />AS PER 2011 FLORIDA MECHANICAL CODE SECTION 603 <br />DUCT TRUNK <br />TYPICAL FLEX DUCT INSTALLATION <br />NO SCALE <br />12 GA WIRE <br />HANGER (TYP.) <br />I <br />ACOUSTICAL CEILING <br />DIFFUSER DETAIL <br />FLEX DUCT <br />INSULATION <br />ACOUSTICAL CEILING <br />CEILING EXHAUST FAN DETAIL <br />NTS <br />ROOF CURB -FLAT ROOF CAP <br />ROOF - CEILING/ROOF <br />FLASHING MIN. <br />EXH. DUCT <br />z I — FRAMING <br />EXHAUST <br />FAN <br />L <br />EXHAUST DUCT J� CEILING <br />GRILLE <br />CEILING <br />EF OPTION 2 - FIELD DECIDED <br />26 GA. (TYP,) - <br />SUPPORT WIRES <br />TYP. X 2 <br />V-O" O.G. MAX. <br />IS" <br />2" MEIrAL STRAP <br />THERMAL BARRIER AT ROOF DECK <br />MA) <br />AL <br />T SET <br />Wa,w <br />c <br />G) —V,\/{I <br />VERTICAL -UP FLOW A.H.U. UNIT DETAIL <br />AHU-4 DETAIL <br />VIBRATION HANGER W/ NEOPRENE <br />3/8" THREADED R ISOLATOR, TYPE BSRA COMBINATION <br />FASTENED TO STRUCTU SPRING AND RUBBER -IN -SHEAR 3/8" ROD. ATTACH <br />HANGER W/ 30' MISALIGNMENT. TO STRUCTURE WITH <br />REFRIGERANT AMBER/BOOTH OR E 3/8" CONCRETE <br />PIPING, ANCHORS, HILTI OR <br />EQUAL <br />FLEXIBLE <br />CONNECTION <br />FLEXIBall <br />SA DUCT <br />CONNECTION ��ZT S PLAN <br />3/4" AUXILIARY IN= <br />CONDENSATE DRAIN ROUTED <br />TO STORM PIPING <br />RA DUCT <br />REFER TO PLAN <br />FOR SIZES <br />AUXILIARY DRAIN PAN WITH CONDUCTIVI SOR <br />TO DE -ENERGIZE UNIT ON SENSING MOISTURE IN PAN. <br />PAN TO EXTEND UNDER VALUING OF UNIT AND 6" <br />BEYOND UNIT ELSWHERE. <br />HORIZ. FAN COIL UNIT DETAIL <br />NOT TO SCALE AHU-2 4 3 DETAIL <br />METAL 1X2X1 U —� SEAL INNER LINER WITH MASTIC OR <br />CHANNEL. APPROVED TAPE AND PANDUIT STRAP. <br />SEAL COLLAR WITH MASTIC OR GASKET. <br />INSTALL IN ACCORDANCE WITH HVAC GENERAL NOTES 2. <br />FIBERGLASS AND <br />FLEX DUCT SUPPORT DETAIL <br />NOT TO SCALE <br />N <br />W <br />LL <br />Q ;g <br />J <br />w <br />Q LL � <br />w <br />muf2 <br />It W N <br />W <br />rz <br />v <br />to <br />^ <br />LVz <br />co <br />co <br />w <br />�>U) <br />z <br />W <br />T <br />O <br />z <br />i <br />J <br />co <br />Z <br />w <br />z_ <br />0D <br />Zm <br />� <br />D <br />O <br />W <br />z <br />E <br />cn <br />W <br />LL <br />Z <br />-N <br />0 <br />w <br />Z <br />J OD <br />QO LL a <br />T <br />D LU <br />w <br />i <br />m0N <br />0. <br />LLI <br />Q <br />0 <br />z <br />0 <br />> <br />W <br />m <br />ao <br />i- <br />04 <br />PROVIDE <br />m <br />CD <br />UNISTRUT <br />z <br />O <br />SUPPORT <br />LLI <br />H <br />1" THICK RIBBED NEOPRENE <br />ISOLATION PAD LOCATED ON <br />ALL FOUR CORNERS OF <br />FCU. AMBER/BOOTH "NRC" <br />OR EQUAL. <br />PRESSURE GAU E <br />,-OUTSIDE AIR DUCT <br />AIR HANDLI G <br />UNIT FIL <br />SUPPLY AIR FLEXIBLE SECTIO <br />DUCT-7 [CONNECTIO MOTORIZED DAMPER <br />pad <br />jp <br />pm <br />IPA <br />j <br />PA04�p�4 <br />--�__ FLEXIBLE <br />CONNECTION <br />FLOOR 12" BASE RAILS RETURN AIR <br />DRAIN PROVIDED BY AHU DUCT <br />CEILING HOUSEKEEPING PAD <br />CONDENSATE <br />DRAIN <br />HORIZONTAL DRAW-THRU <br />AIR HANDLING UNIT <br />NOT TO SCALE A-IU-I DETAIL <br />1►{E4�0/ <br />i T s <br />I <br />l <br />L. _SO­1 P.E.'L_C{EN$E N0 ,38654 <br />I'l X 172CIJADF CITY, FL 33526 <br />00 <br />r` <br />mr <br />cb <br />O <br />m <br />O <br />0 <br />Q <br />W <br />L.L <br />0 <br />LL <br />Q <br />J <br />0 <br />0 <br />Z <br />Q <br />w <br />0 <br />=W <br />U <br />J <br />� <br />Q <br />� <br />Z <br />J <br />J <br />C� <br />0 <br />Z <br />U) <br />W <br />U- <br />� <br />X:I <br />0- <br />U <br />0 <br />LL <br />N <br />� <br />�0 <br />L.L. <br />w <br />NZN <br />0. <br />0 <br />U <br />M 2 <br />