ELECTRICAL SPECIFICATIONS <br />1.1 .SCOPE <br />A. WORK INCLUDED: Include the following Work in addition to items normally part of this Section: <br />01 Wiring for lighting and power. <br />02 Installation of lighting fixtures with lamps. <br />03 Lighting panelboards and distribution panelboards. <br />04 Connection of equipment shown. <br />05 Control wiring. <br />06 Disconnection and removal of existing fixtures and wiring not to be reused. <br />1.2 MINIMUM COMPLIANCE STANDARDS <br />A. All work shall be done in accordance with the requirements of the following: <br />01 Florida Building Code Sixth Edition (2017). <br />02 Florida Building Code - Electrical Conservation Sixth Edition (2017), Section C405. <br />03 2014 issue of the National Electrical Code (NFPA 70). <br />04 All Receptacle Control to conform to ASHRAE Standard 90.1, 8.4.2, 2010. <br />05 Wiring in Patient Care Areas shall comply with NEC 517. <br />06 Other applicable NFPA Codes. <br />07 Regulation of local authorities having jurisdiction. <br />B. Furnish and install all labor, material and equipment and services necessary for complete and <br />safe installation of the electrical system indicated on the drawings and noted in the <br />specifications hereinafter. Electrical systems and equipment shall in general include the following: <br />01 General provisions for electrical work. <br />02 Wiring, distribution equipment and devices. <br />03 Lighting fixtures and lamps. <br />04 Grounding system. <br />1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK <br />A. DRAWINGS: Electrical drawings considered diagrammatic and indicate general arrangement of work <br />and systems. Refer to other drawings to verify location of equipment, etc. Check drawings of <br />other trades to verify exact space condition or underground lines. Drawing Scales prohibit the <br />indication of all offsets, fittings and accessories required, however these items will be <br />provided by this subcontractor at no extra cost to the owner. <br />B. QUALITY OF MATERIALS: New, best of their respective kind, free from defects, and listed by <br />Underwriter's Laboratories, Inc. or bearing their label. <br />C. SHOP DRAWINGS: Submit four (4) copies of shop drawings for lighting fixtures and panelboards. <br />Obtain approval before equipment is ordered, built or installed. <br />D. EXCAVATION AND BACKFILLING: Excavate, backfill and restore surfaces for all electrical work. <br />E. Visit site and inspect existing facilities before bid in order to ensure proper evaluation of <br />working conditions and location of existing equipment. <br />1.4 WIRING, DISTRIBUTION EQUIPMENT AND DEVICES <br />A. CONDUCTORS: Copper, in accordance with ASTM Standards, size references AWG. Conductors No. 10 and <br />smaller size solid, No. 8 and larger stranded. Insulation of conductor thermoplastic, type THHN <br />(min. size: No. 12) any wire installed outside, underground, in slabs, or exposed to moisture <br />shall have THWN insulation. <br />B. RACEWAYS: RIGID STEEL CONDUIT, full weight pipe galvanized, threaded, and minimum 1/2 inch except <br />as noted or required for wiring. ELECTRICAL METALLIC TUBING (EMT), thin wall pipe, galvanized, threadless, <br />comression fittings, and minimum 1 /2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT, <br />continuous singlestrip, galvanized, and minimum 1 /2" size except as noted or required for wiring. PVC <br />CONDUIT, heavy duty type, size as indicated. Separate raceways shall be used for each voltage system. <br />Type AC or MC Cable where permitted. <br />C. DISCONNECT SWITCHES: General Duty, horsepower rated for motor loads 600 or 250 volt rating, fused <br />or non -fused as noted; number of poles as indicated, cover interlocked with switch. Enclosure <br />NEMA 1 for indoor use and NEMA 3R for weatherproof applications. Switch to be Square "D" or equal. <br />D. CIRCUIT BREAKERS: Molded case, thermal -magnetic quick -make, quick -break, bolt -on type with <br />manually operated insulated trip -free handle. Multi -pole types with internal common trip bar. <br />Terminals suitable for copper or aluminum conductors. Interrupting capacity minimum 10,000 RMS <br />symmetrical amperes circuit breakers to be Square "D" or equal, type as required. <br />E. PANELBOARDS: Voltage, phasing and ampere ratings as indicated, circuit breaker type as indicated, <br />busbars of hard drawn copper, minimum 98% conductivity, galvanized steel back box, door and trim. <br />All corners lapped and welded, hardware chrome plated with flush lock and catch. Hinges semi - <br />concealed, 5 knuckle steel with nonferrous pins, 180 degree openings. Minimum gutter space 5- <br />3/4" sides, top and bottom. Increase size where required by code. Directory holder complete <br />with clear plastic transparent cover indicating typewritten list of feeder cables, conduit sizes, <br />circuit numbers, outlets of equipment supplied, and their location. Circuit breaker type <br />panelboards to be Square "D" type NQOD or I -Line, or equal. A plastic label shall be located on exterior of <br />panelboard identifying the system voltage, phase, and current rating. <br />F. WIRING DEVICES: All devices the product of the same manufacturer. Wall switches single pole, 20 <br />ampere, 120 volt. Wall switches three-way, 20ampere, 120 volt. Receptacles duplex, 2 wire; 3 <br />pole grounded, 20 ampere, 120 volt. <br />G. DEVICE PLATES: Provide for all outlets where devices are installed. Provide engraved marking for <br />special outlets. Provide blank plates for empty or future outlet boxes. DEVICE AND DEVICE PLATES <br />COLORS TO BE VERIFIED WITH INTERIOR DESIGNER AND OWNER. <br />1.5 LIGHTING FIXTURES AND LAMPS <br />A. Furnish and install complete system of lighting fixtures, lamps, accessories and supports as <br />specified and indicated. Submittals of equal quality are allowed. <br />1.6 GROUNDING SYSTEM <br />A. EQUIPMENT: Ground non -current carrying metal parts of panelboard, raceways and all lighting <br />fixtures. All conduits shall have equipment grounding conductors. <br />1.7 INSTALLATION <br />A. Secure all supports to building structure. Support horizontal runs <br />of metallic conduit not more than 10 feet apart. Run exposed raceways parallel with or at right <br />angles to walls. <br />B. Pass raceways over water, steam or other piping when pull boxes are not required. No raceway <br />within 3 inches of steam or hot water pipes, or appliances, except crossings where raceway shall <br />be at least 2 inches from pipe cover. <br />C. Cut conduit ends square, ream smooth. Paint male threads of field threaded conduit with graphite <br />base pipe compound. Draw up tight with conduit couplings. <br />D. Leave wire sufficiently long to permit making final connections. In raceways over 50 feet in <br />which wiring is not installed, furnish pull wire. <br />E. Verify locations of outlets and switches. <br />F. Support panel, junction and pull boxes independently to building structure with no weight bearing <br />on conduits. <br />G. Connect conduit to motor conduit terminal boxes with flexible conduit; minimum 18 inches in <br />length and 50% slack. Do not terminate in or fasten raceways to motor foundation. <br />H. Contractor to remove and salvage all abandoned electrical equiment. <br />1. This contractor shall warrant all labor and materials for one year from date of final written <br />acceptance. <br />J. Owner assumes responsibility to do periodic maintenance on all Aluminum Wire Connections and will <br />provide a signed letter to attest to this agreement. <br />1.8 LOW VOLTAGE <br />A. Low Voltage wiring drawings to be provided by others. <br />r <br />4'-0" <br />Bollards to be placed <br />minimum 3' from face <br />of furthest extended <br />piece of electrical <br />equipment to face of <br />bollard. Bollards to <br />be spaced 40" center <br />to center. <br />Finished Floor <br />6"0 Black Iron Pipe <br />filled w/3000 PSI Concrete <br />2'-0" <br />TYPICAL BOLLARD INSTALLATION DETAIL <br />NTS <br />ELECTRICAL SYMBOLS <br />SFD - CEILING FAN SPEED CONTROL RATED FOR THE LOAD <br />S3D - 3-WAY SINGLE POLE DIMMER SWITCH <br />SD - SINGLE POLE DIMMER SWITCH (0-10V OR LINE VOLTAGE AS REQUIRED) <br />Sap - 3-WAY SINGLE POLE TOGGLE SWITCH W/PILOT LIGHT <br />S - SINGLE POLE TOGGLE SWITCH <br />S3 - 3-WAY SINGLE POLE TOGGLE SWITCH <br />Sa - "a/b" INDICATES LIGHTS TO BE SWITCHED <br />(5)a,b - OCCUPANCY SENSOR W/TWO LEVELS OF LIGHTING LINE VOLTAGE <br />*& - TIME CLOCK OVERIDE SWITCH (MAX. 2 HR) <br />10 - LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR <br />- LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR <br />OO - LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR (LARGE RESTROOMS) <br />® - LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR (SMALL RESTROOMS) <br />- LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR W/2 LIGHT CONTROL <br />(SEE SWITCH DETAIL) <br />© - WALL MOUNTED OCCUPANCY SENSOR (CLOSETS) <br />- WALL MOUNTED DIMMABLE OCCUPANCY SENSOR <br />VERIFY LINE VOLTAGE OR 0-10V <br />® - MANUAL "ON" OCCUPANCY SENSOR <br />0 - MANUAL "ON" DIMMABLE OCCUPANCY SENSOR <br />VERIFY LINE VOLTAGE OR 0-10V <br />® - LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR FOR RECEPTACLES <br />DS - DAYLIGHT SENSOR <br />77 - SPLIT DUPLEX RECEPTACLE HALF ON TIME CLOCK OR OCCUPANCY SENSOR. <br />RECEPTACLES MUST BE MARKED TO INDICATE THAT THEY ARE CONTROLLED. <br />4 - QUADRAPLEX RECEPTACLE HALF ON TIME CLOCK OR OCCUPANCY SENSOR. <br />RECEPTACLES MUST BE MARKED TO INDICATE THAT THEY ARE CONTROLLED. 4 <br />- DUPLEX RECEPTACLE ON TIME CLOCK OR OCCUPANCY SENSOR. CONTROLLED <br />RECEPTACLES MUST BE MARKED TO INDICATE THAT THEY ARE CONTROLLED. <br />-� - SIMPLEX RECEPTACLE <br />- DUPLEX RECEPTACLE <br />- QUADRAPLEX RECEPTACLE <br />- FLOOR BOX W/DUPLEX RECEPTACLE. LOCATIONS TO BE VERIFIED W/OWNERS <br />- FLOOR BOX W/QUADRAPLEX RECEPTACLE. VERIFY LOCATIONS W/OWNERS <br />NO - MONITOR CABLE/VERIFY TERMINATION W/OWNERS <br />GFI - GROUND FAULT INTERRUPTER <br />WP - WATER PROOF 3R - NEMA 3R <br />NF - NON -FUSED NL - NIGHT LIGHT <br />- DISCONNECT SWITCH <br />_ - ELECTRICAL PANELBOARD <br />�- EMERGENCY LIGHTING/EXIT SIGN W/BATTERY BACKUP <br />EMERGENCY LIGHTING-W/BATTERY BACKUP <br />TC - TIME CLOCK <br />® - PHOTO ELECTRIC SENSOR <br />® - 208V RANGE RECEPTACLE <br />`­1J- CONDUIT IN FLOOR <br />RC - RECEPTACLE CONTACTOR <br />® - 208V DRYER RECEPTACLE <br />- 2 VOICE (CAT 5)/2 DATA (CAT 6) OUTLET <br />DATA & COMMUNICATIONS TO BE VERIFIED W/OWNERS <br />- RESTROOM EXHAUST FAN <br />NOTE: <br />Occupancy Sensors are to be "Occupancy/Vacancy Sensors unless indicated <br />otherwise. ie: "Manual On" is a Vacancy sensor w/auto off. <br />FIXTURE SCHEDULE <br />PANEL "L1" SCHEDULE 10,000 AIC <br />SERVES <br />LOAD <br />CB/P <br />CKT <br />B/P <br />LOAD <br />SERVES <br />OA OC <br />OA OC <br />Office Mezzanine Lts. <br />1154 <br />20/1 <br />1 <br />2 <br />20/1 <br />1500 <br />Brkrm Receptacle <br />Lobby/Edu./Off Lts. <br />939 <br />20/1 <br />3 <br />4 <br />20/1 <br />1500 <br />Brkrm Receptacle <br />Corrid./Rstrms Lts. <br />704 <br />20/1 <br />5 <br />6 <br />20/1 <br />1200 <br />Refrigerator <br />Off./Conf. Lts. <br />620 <br />20/1 <br />7 <br />8 <br />20/1 <br />900 <br />Office 2 Recept. <br />Spare <br />20/1 <br />9 <br />10 <br />20/1 <br />900 <br />Office 1 Recept. <br />Spare <br />20/1 <br />11 <br />12 <br />20/1 <br />900 <br />Confer. Rm. Recept. <br />Space <br />20/1 <br />13 <br />14 <br />20/1 <br />900 <br />Office 4 Recept. <br />15 <br />16 <br />20/1 <br />900 <br />Office 3 Recept. <br />17 <br />18 <br />20/1 <br />1200 <br />Corrid./DF Recept. <br />19 <br />20 <br />20/1 <br />900 <br />Lobby Recept. <br />21 <br />22 <br />20/1 <br />1620 <br />Educ. Rm Cont. Recept <br />CU4 <br />2194 <br />40/2 <br />23 <br />24 <br />20/1 <br />1500 <br />Hair Sta. Receptacle <br />1 <br />2194 <br />1 <br />25 <br />26 <br />20/1 <br />1500 <br />Hair Sta. Receptacle <br />AHU4 <br />4389 <br />60/2 <br />27 <br />28 <br />20/1 <br />1500 <br />Hair Sta. Receptacle <br />1 <br />4389 <br />1 <br />29 <br />30 <br />20/1 <br />1500 <br />Hair Sta. Receptacle <br />HP1 <br />3386 <br />50/3 <br />31 <br />32 <br />20/1 <br />1500 <br />Hair Sta. Receptacle <br />3386 <br />33 <br />34 <br />20/1 <br />1500 <br />Hair Sta. Receptacle <br />3386 <br />I <br />35 <br />36 <br />20/1 <br />540 <br />Office Mezzanine Recep <br />AHU1 <br />3362 <br />40n471 <br />38 <br />30/2 <br />2250 <br />Water Heater <br />3362 <br />I40 <br />4/1 <br />2250 <br />336242 <br />864 <br />Circulation Pump <br />Sub -Total 107161207614035 9450 110170177041 <br />Total 20166 22246 21739 64151 = 185 Amps Connected (Highest Phase) <br />54205 = 150 Amps Demand <br />Notes: 200A MLO 120/208V 30 4W SN <br />PANEL "12" SCHEDULE 10,000 AIC <br />SERVES <br />LOABD <br />CB/P <br />CKT <br />B/P <br />LOAD <br />SERVES <br />OA OC <br />OA OC <br />Plant Mezzanine Lts. <br />914 <br />20/1 <br />1 <br />2 <br />20/1 <br />1500 <br />Rstrm./Staff Recept. <br />Bottling Area Lights <br />1058 <br />20/1 <br />3 <br />4 <br />20/1 <br />540 <br />Ship/Rec Recept. <br />Shipping and Rec. Lts. <br />1063 <br />20/1 <br />5 <br />6 <br />20/1 <br />540 <br />Bottling Area Recept. <br />Rstrm/Staff Lts. <br />284 <br />20/1 <br />7 <br />8 <br />20/1 <br />540 <br />Ext. Bldg. Recept. <br />Ext. Bldg. Lts. <br />163 <br />20/1 <br />9 <br />10 <br />20/1 <br />1500 <br />Sign <br />Spare <br />20/1 <br />11 <br />12 <br />50/3 <br />3038 <br />Air Compressor �c <br />Future Equip. <br />13 <br />14 <br />3038 <br />15 <br />16 <br />3038 <br />17 <br />18 <br />30/3 <br />2882 <br />Space <br />19 <br />20 <br />2882 <br />21 <br />22 <br />2882 <br />23 <br />24 <br />2 /1 <br />Spare <br />25 <br />26 <br />Space <br />27 <br />28 <br />29 <br />30 <br />HP3 <br />3386 <br />50/3 <br />31 <br />32 <br />50/3 <br />3386 <br />HP2 <br />3386 <br />33 <br />34 <br />3386 <br />3386 <br />I <br />35 <br />36 <br />3386 <br />AHU3 <br />3362 <br />40/3 <br />37 <br />38 <br />40/3 <br />3362 <br />AHU2 <br />3362 <br />40 <br />I <br />3362 <br />3362 <br />I <br />49 <br />42 <br />3362 <br />Sub -Total 7946 7969 7811 118261182E 032E <br />Total 197721979518137 57704 = 165 Amps Connected (Highest Phase) <br />45996 = 128 Amps Demand <br />Notes: 300A MLO 120/208V 30 4W SN <br />�k Actual loads to be verified, not available at time of drawings. <br />MARK <br />MFG. <br />CATALOG NUMBER <br />LAMPS <br />REMARKS <br />A <br />SAYLITE <br />FPELP 24 LED 50 DMV WH 40 <br />50W/LED <br />Lay <br />In <br />B <br />SAYLITE <br />FPELP 22 LED 40 DMV WH 40 <br />40W/LED <br />Lay <br />In <br />C <br />TEXAS FLUORESCENTS <br />555 MW 48L F57W5400L DMV 35K WH <br />57W/LED <br />Wall <br />D <br />TEXAS FLUORESCENTS <br />OUTMW 1 5W 1 20OLD 1 20WH 40K <br />15W/LED <br />Surface <br />E <br />LUM-TECH <br />LEDH-CFK6 23 9 40 UTD/LEDT-R622 <br />23W/LED <br />Recessed <br />F <br />SAYLITE <br />DC150SR 70W7900L MV 50K <br />70W/LED <br />Wall <br />Pack <br />G <br />TEXAS FLUORESCENTS <br />C 48FRLENS F48W5650L DMV 40K <br />48W/LED <br />Strip <br />H <br />EELP <br />EL1-12L WH 40K BL <br />11 W/LED <br />Wall <br />J <br />SAYLITE <br />HILFR 48L Al49W20000L DMV 40K <br />149W/LED <br />High <br />Bay <br />K <br />TEXAS FLUORESCENTS <br />CITE 48LRFF57W680OLLBDMV40K <br />57W/LED <br />Low <br />Bay <br />L <br />SAYLITE <br />SSSTS MW 48L E58W5000L STMV 40K <br />58W/LED <br />Wall <br />X1 <br />EELP <br />EM3-LED LED <br />EMERGENCY <br />LIGHT <br />X2 <br />EELP <br />EM20-E LED <br />EMERGENCY <br />LIGHT <br />X3 <br />EELP <br />XC-LED 2 R W LED <br />EXIT/EMERG. <br />LIGHT <br />X4 <br />EELP <br />CAC 1 R W W LED <br />EXIT/EMERG. <br />LIGHT <br />X5 <br />EELP <br />XE-S 2 R W EM LED <br />EXIT <br />NOTES: <br />1. All Lighting and Switching <br />to meet Florida Energy Code requirements. <br />2. All Lighting to be verified with Owners <br />3. Lamp color index is to <br />be verified w/Owners before purchase. <br />4. All Emergency Lighting <br />to be wired ahead of any switching or time clock/lighting contactors. <br />5. Other Light Fixtures being equal and approved by Owner are permitted. <br />6. Reuse of existing emergency lights permitted if in good working order. <br />7. Fixture package available <br />thru Illuminating Specialists. Phone 727-378-7541, Jim Olender <br />2% SERVICE/FEEDER VOLTAGE DROP CHART <br />This chart is based on a 448 Amp Demand, 208V 30 Service <br />from Utility Xfmr. to Wireway. Then from Wireway to List Station <br />(Est. 24 Amps, to be verified). <br />WIRE TYPE AND SIZE FEET VD %VD <br />UTILITY XFMR. TO WIREWAY <br />(2) 30OKcmil 75'C THW/THWN Wire = 100 1.67 .80 <br />WIREWAY TO LIFT STATION <br /># 4 75'C THW/THWN Wire = 130 1.67 .80 <br />VD 1.67 = 0.80% ® 208V <br />VD 1.67 = 0.80% ® 208V <br />TOTAL VD 3.34 = 1.60% ® 208V <br />Chart indicates distance with load as shown. Should total distance exceed <br />what is indicated it is to be brought to the attention of this Engineer. <br />NOTE: All wire Copper unless indicated otherwise. <br />2 Sets ea. (4)300kcmil,3"C <br />LOAD CALCULATION <br />SHORT <br />CIRCUIT <br />CALCULATIONS: <br />DESCRIPTION <br />kVA <br />GENERAL LIGHTING <br />43198 <br />(Worst Case) <br />I SC <br />1 1.732(100)(43198) <br />+ <br />3500 Sq. Ft. Office LED Lights <br />2.26 <br />2(13923)(208) <br />6600 Sq. Ft. Mezzanine LED Lights <br />2.09 <br />6500 Sq. Ft. Shipping/Bottling LED Lts. <br />2.41 <br />1 SC <br />= 20781.2 AIC <br />Meter, Wireway <br />Exterior LED Bldg. Lts. <br />0.16 <br />6.92 <br />1 SC <br />= 20019.4 AIC <br />300A Fused Disconnect <br />Continuous Load = 1.25 X 6.92 = <br />8.65 <br />1 SC <br />= 10000.0 AIC <br />Let Thru Current ® 300A Fused Disc. <br />RECEPTACLES <br />w/300A Class RK5 FRN-R Fuses <br />1 st 1 Okw ® 100% <br />10.00 <br />plus remainder .5 X 15080 = <br />7.54 <br />1 SC <br />= 19565.4 AIC <br />200A Fused Disconnect <br />Sub Total <br />26.19 <br />1 SC <br />= 8000.0 AIC <br />Let Thru Current ® 200A Fused Disc. <br />HVAC <br />w/200A Class RK5 FRN-R Fuses <br />(1) AHU w/7.5kw Heat ® 10086 = <br />10.09 <br />(3) HP's @ 10158 ea. = <br />30.47 <br />I SC <br />= 16947.E AIC <br />30A Fused Disconnect <br />(3) AHU's w/7.5kw Heat ® 8778 ea. = <br />26.33 <br />I SC <br />= 2500.0 AIC <br />Let Thru Current ® 30A Fused Disc. <br />Sub Total <br />66.89 <br />w/30A Class RK5 FRN-R Fuses <br />EQUIPMENT <br />I SC <br />= <10000 AIC <br />Panels L1, L2, and Lift Station <br />(1) Air compressor ® 9114 = <br />X 1.4 largest Motor = <br />12.76 <br />(1) Water Heater ® 4500 = <br />4.50 <br />(1) Circulation Pump ® 864 = <br />.86 <br />Future Equipment <br />40.00 <br />(1) Lift station ® 8646 = <br />8.65 <br />Sub Total <br />66.77 <br />MISCELLANEOUS <br />(1) Sign ® 1500 = 1.50 <br />TOTAL LOAD 161.35 <br />161.35KW ® 120/208V 30 4 WIRE SN = 448 Amps <br />570A 120/208V 30 4 Wire SN Service <br />(3)350Kcmil,35OKcmilN,4G,3"C <br />(3)3/0,3/ON, 6G,2.5"C <br />OWireway <br />Meter <br />T <br />T <br />I <br />Panel <br />L1 <br />Panel <br />1 2 <br />For exterior <br />200A <br />MLO <br />300A <br />MLO TC <br />lighting <br />120/208V <br />120/208V <br />S <br />30A <br />Main <br />200A <br />Main <br />300A <br />Main <br />30 4 <br />Wire <br />30 4 <br />Wire <br />Verify location <br />Fused <br />Fused <br />Fused <br />SN <br />SN <br />TC <br />w/Owners <br />Disconnecl <br />DisconneclDisconnect <br />208V 30 <br />120/208V <br />120/208V <br />0 4 Wire <br />30 4 Wire <br />Time Clock for interior lights to <br />SN <br />SN <br />comply with FBC ENERGY <br />Li <br />Li <br />CONSERVATION SIXTH EDITION (2017) <br />C405.2.2.1 <br />C.T. <br />Lightning <br />Lightning <br />Arrestor <br />Arrestor <br />(3)4,4G,1.25"C <br />Load for Lift Station <br />(3)3/0,3/ON,6G,2.5"C <br />not available at time of <br />�- <br />this drawing. <br />Proposed <br />(3)35OKcmil,35OKcmiIN,4G,3"C <br />B u i I d i n a <br />Extend to metal water line <br />or building steel in accordance <br />with NEC 250. <br />1/0 CU <br />1.25" Conduit <br />to Lift Sta. <br />Minimum (2)5/8"0 Copper Clad <br />Ground Rods spaced 10' apart. <br />RISER DIAGRAM <br />NTS <br />2% SERVICE/FEEDER <br />VOLTAGE <br />DROP <br />CHART <br />This chart is based on a 448 <br />Amp <br />Demand, <br />208V 30 <br />Service <br />from Utility Xfmr. to Wireway. <br />Then <br />from Wireway to <br />Panel <br />L1(150 Amps). <br />WIRE TYPE AND SIZE <br />FEET <br />VD <br />%VD <br />UTILITY XFMR. TO WIREWAY <br />(2) 300kcmil 75'C THW/THWN Wire = <br />100 <br />1.67 <br />.80 <br />WIREWAY TO PANEL L1 <br />3/0 75-C THW/THWN Wire = <br />60 <br />1.20 <br />.58 <br />VD 1.67 = <br />0.80% <br />® 208V <br />VD 1.20 = <br />0.58% <br />® 208V <br />TOTAL VD 2.87 = 1.38% ® 208V <br />Chart indicates distance with load as shown. Should total distance exceed <br />what is indicated it is to be brought to the attention of this Engineer. <br />NOTE: All wire Copper unless indicated otherwise. <br />2% SERVICE/FEEDER <br />VOLTAGE <br />DROP <br />CHART <br />This chart is based on a 448 <br />Amp <br />Demand, <br />208V 30 <br />Service <br />from Utility Xfmr. to Wireway. <br />Then <br />from Wireway to <br />Panel <br />L2(130 Amps). <br />WIRE TYPE AND SIZE <br />FEET <br />VD <br />%VD <br />UTILITY XFMR. TO WIREWAY <br />(2) 30OKcmil 75'C THW/THWN Wire = <br />100 <br />1.67 <br />.80 <br />WIREWAY TO PANEL L2 <br />3/0 75'C THW/THWN Wire = <br />40 <br />.69 <br />.33 <br />VD 1.67 = <br />0.80% <br />® 208V <br />VD .69 = <br />0.33% <br />® 208V <br />TOTAL VD 2.36 = 1.13% ® 208V <br />Chart indicates distance with load as shown. Should total distance exceed <br />what is indicated it is to be brought to the attention of this Engineer. <br />NOTE: All wire Copper unless indicated otherwise. <br />Bond to Concrete enclosed <br />Steel Rebar (min. #4) in <br />Bldg. Foundation per <br />NEC 250.50 <br />3% EQUIPMENT VOLTAGE <br />DROP <br />CHART <br />This chart is based on a 20 amp single <br />pole <br />breaker load at maximum (16 amps) <br />120/208V 30 Service. <br />WIRE TYPE AND SIZE <br />FEET <br />#12 75-C THW/THWN Wire = <br />71 <br />#10 75-C THW/THWN Wire = <br />112 <br /># 8 75'C THW/THWN Wire = <br />179 <br /># 6 75'C THW/THWN Wire = <br />284 <br />NOTE: <br />This chart is "Worst Case". Actual <br />length of <br />wire <br />when calculated from load to load <br />and how <br />the <br />conduits are run can vary from this chart. <br />%%IIII11lt#0,0 <br />V�iP'I <br />l• • <br />z OF « � <br />r:. <br />r <br />m <br />w <br />Q <br />z <br />0 <br />D <br />zj� o <br />jr z <br />Of <br />O <br />L.L_ <br />~ <br />J <br />w <br />m of <br />Q <br />JOf <br />Q <br />L.L_ <br />of Q <br />fY <br />Z=a0 <br />w� <br />� <br />J <br />i-QJJ <br />U <br />0 a. J <br />a' <br />L.� <br />D <br />(n <br />NILLI 2 <br />CL <br />Q <br />ILL Lj <br />Z �OLN <br />0 <br />O O <br />m <br />F_ <br />W <br />EL <br />w <br />a <br />0 <br />4J <br />0 <br />Z <br />0 <br />o <br />0 <br />F- <br />D <br />CY' <br />O <br />0_ <br />< <br />F- <br />p <br />ILL <br />V <br />w <br />IL <br />U <br />w <br />a <br />0 <br />o_ <br />W w = <br />J (n CL J Z <br />0 U 0 w <br />m J � � m <br />Sao= <br />N C) w U W <br />N Q Q LLJ <br />Z p F- <br />0-iJ Z= <br />J <br />Q N O X ~ <br />LL_ w <br />Li Z \ Z J <br />UOw �'F- <br />W W Q o <br />f1 = W Er 00 <br />z <br />C) < o , r, <br />_ <br />0 z N <br />I J F-- 0 <br />v0i ZE W C:) <br />o Q Q W <br />z a Lam.. iii o <br />J <br />0 w <br />W <br />w <br />m <br />0 <br />:2 <br />z <br />Z <br />00 <br />w <br />Z <br />o <br />of <br />CL <br />w <br />m <br />c� <br />z <br />ir <br />w <br />z <br />0 <br />w <br />z <br />w <br />w <br />< <br />� <br />W <br />N <br />` <br />0 <br />Ld <br />T <br />W <br />� <br />w <br />_J <br />W <br />W <br />�n <br />Q <br />Z <br />aM <br />Z N <br />4 <br />Vm <br />0(0�JM <br />L-Jr <br />Z w <br />M: 0 a v) co <br />W <br />0 <br />WZ <br />JN <br />w <br />Z <br />.JZMw <br />LLJ z <br />oca =wN <br /><_J <br />c�►L�_� <br />Zm <br />Z <br />o9 <br />O <br />V)W <br />Z N <br />0st � <br />////��Z <br />V/U <br />Z <br />Z� M1* <br />< 00 N J 00 <br />z <br />Ww <br />S-- -LL <br />ZXF 04�O/ OV�n <br />< LLJM <br />L L <br />L <br />M [L La N <br />M_JI <br />0 ►- lL 0_ v <br />