THIS DETAIL ONLY REFERS TO THE DIAMOND -MESH <br />EXPANDED METAL LATH ATTACHMENT. <br />METAL LATH <br />16GAx1-1\2" LONG (3/4%1" CROWN) <br />STAPLES @ 6" O.C. VERT BETWEEN <br />STUDS (NOTED THUS:—) - OFFSET <br />STAPLES BETWEEN STUDS AS SHOWN <br />WALL SHEATHING <br />Backer and Filler Block Dimensions <br />BCI Joist <br />Backer Block <br />Thickness <br />Filler Block Thickness <br />Series <br />3/4" or 7/8" <br />5000s 1.8/1.7 <br />wood panels <br />Two 3/4" wood panels or 2 x <br />1-1/8" or two 1/2" <br />6000s 1.8/1.7 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 1/2" <br />6500s 1.8/1.7 <br />wpanels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 1 /2" <br />602.0 <br />wood panels <br />2 x — + 5/8" or 3/4" wood panel <br />902.0 <br />2x _ lumber <br />Double 2 x — lumber <br />DOUBLE JOIST CONSTRUCTION <br />(Not required if both loaded equally from above) <br />Filler blocking <br />1/8" gap <br />r <br />r <br />1) Support back of web during nailing to prevent damage to <br />web -flange connection. <br />2) Block solid between joists for full length of span. <br />3) Leave 1/8" gap between top of filler blocking and bottom of top flange. <br />4) Place joists together and nail from each side with 2 rows of 10d nails <br />16GAx1-1/2" LONG (3/4"-1" 2x_: CONTRACTOR TO PROVIDE 2x TO FILL THE HEIGHT at 12" o.c., clinched when possible. Stagger rows from opposite <br />CROWN) STAPLES @ 6" OF THE JOIST ASA REQUIRED LEAVING Y" GAP @ TOP sides by 6". <br />O.C. VERT INTO STUDS <br />(NOTED THUS:—) DOUBLE JOIST CONNECTION <br />METAL LATH ATTACHMENT DETAIL <br />REV. 09.24.21 SCALE: 3/4" = V-0" <br />*DETAIL EXCEEDS THE REQUIREMENTS FOR FBCR 703.7.1 LATH* <br />**ONLY APPLIES TO LENNAR TPA/JAX** <br />10'-0" <br />TANK -LESS W/H <br />CORNER OF I I I <br />HOME H C G <br />GARAGE SIDE O O O <br />5'-0" o <br />STUB -OUT FOR 0 1' -0" 0 9 <br />to <br />GAS METER a Q, <br />N <br />• MEASUREMENTS ARE FROM FINISHED FLOOR <br />• ROUGH -IN GAS TO RIGHT (ALWAYS) - 12" OFF -CENTER <br />• ROUGH -IN ELECTRIC TO LEFT (ALWAYS) - 12" OFF -CENTER <br />GAS CONNECTION DETAIL <br />"ONLY APPLIES TO HILLSBOROUGH AND PASCO COUNTY** <br />RAFTER SPAN TABLE <br />MEMBER SIZE AND SPACING <br />MAXIMUM LENGTH <br />MEMBER CONNECTIONS* <br />2" X 4" @ 16" O.C. <br />7'-5" <br />(2)16d TOENAILS <br />2" X 6" @ 16" O.C. <br />10'-8" <br />(2)16d TOENAILS <br />2" X 8" @ 16" O.C. <br />13'-9" <br />(3)16d TOENAILS <br />2" X 10" @ 16" O.C. <br />16'-5" <br />1 SIMPSON HTS20 OR 3 16d TOENAILS <br />2" X 12" 16" O.C. <br />19'-3" <br />1 SIMPSON HTS20 OR (4)16d TOENAILS <br />2" X 4" @ 24" O.C. <br />6'-1" <br />(2)16d TOENAILS <br />2" X 6" @ 24" O.C. <br />8'-6" <br />(2)16d TOENAILS <br />2" X 8" @ 24" O.C. <br />11'-0" <br />(2)16d TOENAILS <br />2" X 10" @ 24" O.C. <br />13'-0" <br />(3)16d TOENAILS <br />2" X 12" @ 24" O.C. <br />164" <br />(1) SIMPSON HTS20 OR (3)16d TOENAILS <br />* TOENAIL CONNECTIONS DESIGNED FOR SHEAR ONLY (i.e. RAFTER TO RIDGEBEAM). <br />** SOUTHERN YELLOW PINE, 55 PSF LOADING <br />N.T.S. <br />SQUASH BLOCKS AT INTERIOR <br />BEARING <br />Vertical load transfer =1900 plf max along load bearing wall. <br />Load bearing wall must stack <br />'Non -stacking walls <br />over squash=20 blocks and <br />require additional <br />wall or beam below.* <br />consideration. Check <br />local building <br />1/16 <br />code for appropriate <br />details in <br />One 10d box <br />areas=20 of high <br />1 <br />or-20 sinker <br />lateral load. <br />T <br />nail each side <br />at bearing. <br />Boise Joist Blocking <br />Use 3" (10d) nails at 6" o.c <br />^r �Load bearing walls = � :17 <br />Provide adequate bearing <br />for each lapped joist. <br />Squash block 10d nails (2x4 minimum) SECTION @ INT. BRG. WALL <br />Bearing wall, Versa -Lam LVL or N.T.S. <br />Glulam Beam <br />KNOCKOUTS) <br />tr_) ALL i MINIMUM SPACING = 2x GREATEST <br />KNOCKOUTS) ALLOWED DIMENSION OF LARGEST HOLE <br />IN BEARING ZONES D (KNOCKOUT EXEMPTS) <br />(see table below) D <br />(see table below) <br />DO NOT cut, notch id <br />or drill flanges <br />FILL CELLS ,— STD. 900 HOOK BOND BEAM <br />w <br />cr > STD. 900 CONT. #5 <br />BAR I HOOK BAR <br />#5 CONT. <br />FROM <br />FOUNDATION <br />TO HIGHEST <br />BOND BEAM <br />V BOND BEAM STEP <br />SCALE: N.T.S. <br />2nd FLOOR <br />INTERIOR/EXT WALL SEE <br />PLAN FOR MORE INFO <br />CONT. BASE PLATE <br />BEARING COLUMN <br />SEE PLAN FOR REQ'D'-PLYWOOD FLOOR <br />COLUMN AND :% SHEATHING PER PLAN <br />CONNECTION - 1 TJI TO BE CUT TO ALLOW <br />-J�-" FOR BLOCKING/TJI <br />MASONRY WALL OR <br />1 1 " INTERIOR BRG. WALL <br />TJI PER PLAN <br />OTHERWISE SOLID <br />BLOCKING TO MATCH <br />— Solid block all posts from # OF 2nd FLOOR <br />above to bearing below. STUDS <br />SECTION @ INT. BRG. WALL <br />N.T.S. <br />1/8" min. 2" min. <br />} Small gap „ <br />2" max. 4 max. - <br />Web Stiffener Fastener Schedule <br />Joist BearingLocation <br />- -� Series Depth End Intermediate <br />® 9-1/21,_ _ 2-8d 2— d <br />BCI5000s 11-7/8" 2-8d 3- <br />W 2-8d_ — >8d <br />Clinch nails ` -- 9-1/2" 2-8d 2-8d <br />when \ BCI 6000s® 11-7/8"- 2-8d 3-8d <br />possible BCI6500s® 14" 2-8d 5-88d <br />16" 2-8d 6-8d <br />11-7/8" 2-8d 3-8d <br />BCI 60s 14" 2-8d - 5-8d <br />Tight fit ..----- T 16" 2-8d 6-8d <br />1 11-7/ " 3-16d 3-16d <br />2x4/Plywood/OSB web stiffener 2" min. gCl 90s® 14" 5-16_d 5-16d <br />required when indicated or 4" max. 16" 6-16d 6-16d <br />- Hangers with side nailing. <br />- Hangers with sides not containing WEB STIFFENER <br />top flange of joist. <br />- Birdsmouth cuts. N.T.S. <br />- Under 2nd floor column w/ loads <br />higher than 15001b. <br />BLOCKING PANEL, INTERIOR <br />Vertical load transfer =1900 plf max. along bearing wall <br />Required on interior walls : - for vertical load transfer <br />when load bearing - for lateral support when joists <br />meet over wall, or wall stacks directly over wall or <br />beam below Load bearing wall must stack over <br />blocking and wall or beam below.* <br />When joists meet over wall, provide <br />ir-1 3/4" minimum bearing for each. <br />Use 10dx3" nails at 6"o.c. for all joist <br />blocking panel *Non -stacking walls <br />require additional consideration.— <br />rj <br />6„ A 1Y" ROUND HOLE MAY <br />BE CUT ANYWHERE IN CANTILEVER <br />THE WEB. PROVIDE AT <br />LEAST 3" OF CLEARANCE <br />FROM OTHER HOLES <br />MINIMUM DISTANCE FROM SUPPORT, LISTED BELOW, IS REQUIRED FOR ALL HOLED GREATER THAN 1y" <br />NOTES: <br />DO NOT CUT HOLES <br />LARGER THAN %" <br />ROUND IN <br />CANTILEVERS. <br />1. JOISTS MUST BE PROPERLY DESIGNED TO MEET BUILDING CODE REQUIREMENTS. <br />2, TABLE IS FOR UNIFORMLY LOADED MAXIMUM LOADS OF 40 PSL(LIVE) AND 15 PSF (DEAD) ON SIMPLE SPAN APPLICATIONS ONLY. <br />3. REFER TO JOIST SPECIFIER GUIDE FOR INSTALLATION AND OTHER INFO. <br />4, SELECT A TABLE ROW BASED ON JOIST DEPTH AND THE ACTUAL JOIST SPAN ROUNDED UP TO THE NEAREST TABLE SPAN. SCAN ACROSS <br />THE ROW TO THE COLUMN HEADED BY THE APPROPRIATE ROUND HOLE DIAMETER OR RECTANGULAR HOLE SIDE. USE THE LONGEST SIDE OF <br />A RECTANGULAR HOLE. THE TABLE VALUES IS THE CLOSEST THAT THE CENTERLINE OF THE NEAREST SUPPORT. <br />5. THE ENTIRE WEB MAY BE CUT OUT. DO NOT CUT THE FLANGES. HOLES APPLY TO EITHER SINGLE OR MULTIPLE JOISTS IN REPETITIVE <br />MEMBER CONDITIONS. <br />6. FOR MULTIPLE HOLES, THE AMOUNT OF UNCUT WEB BETWEEN HOLES MUST EQUAL AT LEAST TWICE THE DIAMETER (OR LONGEST SIDE) OF <br />THE LARGEST HOLE. <br />7. %' ROUND KNOCKOUTS IN THE WEB MAY BE REMOVED BY USING A SHORT PIECE OF METAL PIPE AND HAMMER. <br />8. HOLES MAY BE POSITIONED VERTICALLY ANYWHERE IN THE WEB. THE JOIST MAY BE SET WITH THE 1Y2" KNOCKOUT HOLES TURNED WITHER <br />UP OR DOWN. <br />9. THIS TABLE WAS DESIGNED TO APPLY TO THE DESIGN TO APPLY TO THE DESIGN CONDITIONS COVERED BY TABLES ELSEWHERE IN HIS <br />PUBLICATION. USE THE BC CALC SOFTWARE TO CHECK OTHER HOLE SIZES OR HOLES UNDER OTHER DESIGN CONDITIONS. IT MAY BE <br />POSSIBLE TO EXCEED THE LIMITATIONS OF THIS TABLE BY ANALYZING A SPECIFIC APPLICATION WITH THE BC CALC SOFTWARE. <br />HOLE CUTTING CHART <br />N.T.S. <br />Plumbing <br />Joist <br />I -Joist can be offset <br />up to 3" to avoid <br />vertical plumbing <br />3" max <br />JOISTS OFFSET <br />Backer block (12" wide min.) <br />Nail with 10-10d nails. <br />Install tight to top flange. <br />Joist hanger <br />Filler block. <br />Nail with <br />10-10d nails <br />Backer block required where top <br />mount hanger load exceeds 250 lbs. <br />Install tight to top flange. <br />1/4"-2" gap <br />V,-,- <br />Backer Block <br />"Top Mount" "Face Mount" <br />Backer block shall be tight Backer block shall be tight <br />to bottom of top flange with to top of bottom flange with <br />1/4"-2" gap at top of bottom 1/4"-2" gap at bottom of top <br />flange. flange. <br />Web stiffner as <br />Web stiffeners are not required when top required if hanger <br />flange is laterally supported by joist hanger. doesn't meet <br />height <br />requirements <br />d p hJoist <br />o <br />I -JOISTS BUCKETS <br />N.T.S. <br />SIMPSON MGT <br />w/(22)10d <br />NAILS TYP. <br />GIRDER TRUSS <br />7�. <br />r 2X TOP PLATE <br />5/81 <br />THRU <br />BOLT <br />2 X B.U.0 <br />SIMPSON MGT <br />w/ (22)10d <br />NAILS TYP. <br />TYPICAL SIMPSON MGT TO <br />BUILT-UP COLUMN DETAIL <br />TYPICAL SIMPSON LUS/HUS/HUC <br />INSTALLATION <br />MIN. EMBEDMENT <br />SCHEDULE FOR <br />AND QUANTITY <br />W FASTENERS <br />TYPICAL SIMPSON META12 / <br />META12 TSS INSTALLATION <br />A/C CHASE 4" PVC <br />SLEEVE THRU STEM <br />WALL <br />SLEEVE THRU STEM ­'Li <br />• <br />SEE PLAN FOR •• .. • <br />FOUNDATION INFO ' a • d' <br />STEM FOUNDATION <br />GRADE <br />REINF. SEE PLAN <br />LA/C CHASE 4" PVC (2) #5 REBAR <br />SLEEVE THRU FOOTING <br />MONO FOUNDATION <br />TYP. FND. PENETRATIONS <br />SCALE: N.T.S. <br />SIMPSON META12 / META12 TSS <br />INSTALLATION @ MID SPAN <br />NOTE: <br />UPLIFT VALUE <br />IS BASED ON <br />S.P.F. <br />LOCATION OF <br />SECOND H10A <br />SIMPSON H10A • • •• (WHEN <br />w/ (18)10d x 1 1/2" — REQUIRED) <br />NAILS <br />UPLIFT =1015# <br />TYPICAL SIMPSON H10A <br />INSTALLATION <br />TYPICAL SIMPSON MTS <br />/ HTS INSTALLATION <br />TOP (2) #5's x 4'-0" v <br />CENTERED @ PIPE <br />PENETRATION <br />12" BELOW <br />GRADE <br />r <br />E . I I%aa <br />PLUMBING LINE <br />PVC OR SCH40 SLEEVE <br />A d <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE VERTICAL THRU FND. <br />TOP (2) #5's x 4' 0"—\ <br />CENTERED @ PIPE <br />PENETRATION <br />4 d � <br />PVC OR SCH40 SLEEVE <br />/ r PLUMBING LINE <br />d .q <br />d <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE PERPENDICULAR TO FND. <br />TOP (2) #5's x 4'-0" PVC OR SCH40 SLEEVE <br />CENTERED @ PIPE <br />PENETRATION PLUMBING LINE <br />4 ° d dO' ° dv L <br />°. a <br />MLIE1 <br />SEE FND. PLN. <br />SIZE & REINF. <br />N <br />o_ <br />0 <br />,,�tr,sttaarrrfr� <br />M <br />U �. <br />�` • <br />* No <br />. <br />. O� T.. <br />ID 1" ';y <br />To the best of the Engineers knowledge, Information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />V <br />0) <br />6o <br />0 <br />2 LL <br />in-r-32 LL W Wa <br />la <br />U_ a 5 <br />Z <br />13 <br />�+_i <br />�4 o� <br />i°'° <br />W <br />LNG O <br />�O^jQ' ¢<¢ <br />LL <br />o_ <br />N <br />� to <br />Z <br />W <br />O U <br />OD❑ <br />0 <br />z <br />z <br />J <br />a <br />E3 <br />z <br />C1c� <br />U <br />� <br />G) <br />OLL, <br />g <br />VLn <br />_ d <br />ra <br />U <br />0 <br />C <br />c <br />M <br />O° <br />_ <br />z• <br />Q$ <br />l I <br />S <br />'T <br />o <br />U <br />Z <br />C'4 <br />�L• i <br />Wg <br />m <br />Z <br />� <br />8. - <br />3 <br />8 <br />y <br />W <br />aLL <br />=1 <br />c <br />L.n <br />(1) <br />O <br />O <br />— <br />> <br />� <br />0 <br />T- <br />O <br />LO <br />r <br />� <br />M <br />CoT <br />Q <br />Cr <br />0 <br />00 <br />T <br />(n s <br />m <br />O <br />Q <br />T <br />CN N <br />CEO <br />C <br />CD <br />tV <br />CO <br />Q t <br />CD <br />tT <br />LO <br />iu <br />M <br />z <br />' � <br />C <br />a <br />E <br />8 <br />¢ o <br />JOB NO : 22-01571-01566 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />SN1 <br />11 PASCO <br />COUNTY <br />