-1 1 — — -- <br />ELECTRICAL SPECIFICATION 15oaz00AINDOOR <br />PANEL CENTER <br />NOTES: 0 #14 to lights & outlets <br />NEMA t 10 #12 to appliances and GFI <br />ELECTRICAL CONTRACTOR 200 AMP/ it #10 to WH <br />MUST VERIFY WITH THE 0 #8 to Range <br />SPECIFICATIONS FOR THE TYPE 10 #6 to HVAC <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR METER <br />LOCATION PURPOSES. <br />15o=vo <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp if <br />UNDERGROUND Disconne <br />SERVICE BY POWER CO. <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING o #4 GROUNDING WIRE <br />TERMINATION PER 7I WITH CODE APPROVED <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />GENERAL ELECTRICAL NOTES . Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />PEPP <br />WEATHERPROOF DUPLEX OUTLET <br />W.P. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />FEFG F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />-?4 FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />1-0 WALL MOUNTED LIGHT FIXTURE <br />ORECESSED LIGHT FIXTURE <br />P.C. LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />� f6 PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />© 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />D]M ELECTRIC METER <br />owl ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />G J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />J OPT. CEILING FAN <br />AB (1) PHONE LINE, (1) DATA PORT <br />SMOKE DETECTORS <br />SMOKE DETECTORS SHALL BE IN ALL SLEEPING <br />AREAS, SHALL BE INTERCONNECTED, SHALL BE WITHIN <br />1' TO 3' OF PEAK, AND SHALL BE 3' FROM THE <br />SUPPLY OR AIR STREAM, AND EQUIPPED WITH <br />BATTERY BACK—UP. ALL SMOKE DETECTORS TO BE <br />ARC —FAULT PROTECTED. <br />FAIR HOUSING ACT REQUIREMENTS: <br />OPERABLE PARTS OF THE CONTROLS FOR LIGHT SWITCHES, ELECTRICAL <br />OUTLETS, THERMOSTATS AND OTHER ENVIROMENTAL CONTROLS MUST BE <br />LOCATED NO HIGHER THAN 48", AND NO LOWER THAN 15", ABOVE THE FLOOR. <br />IF THE REACH IS OVER AN OBSTRUCTION (FOR EXAMPLE, AN OVERHANGING <br />SHELF) BETWEEN 20 AND 25 INCHES IN DEPTH, THE MAXIMUM HEIGHT IS <br />REDUCED TO 44" FOR FORWARD APPROACH; OR 46" FOR SIDE APPROACH <br />PROVIDED THE OBSTRUCTION (FOR EAXMPLE, A KITCHEN BASE CABINET) IS <br />NOT MORE THAN 24 " IN DEPTH. OBSTRUCTIONS SHOULD NOT EXTEND MORE <br />THAN 25" FROM THE WALL BENEATH A CONTROL. <br />COMP. <br />DISC. <br />WP <br />GFI <br />VERIFY METER <br />LOCATION WITH <br />BUILDER <br />2 <br />II,VTR <br />vl` <br />I <br />`21j VT @p SIN <br />3° R <br />r 3" <br />TUB I\\�'� 3^ 3 <br />I I G ll, <br />VillP 4h <br />2^ 3° <br />41, <br />3^ TO <br />MAIN <br />PLUMBING RISER_ <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />UNIT 1397 — ELECTRICAL PLAN <br />SCALE: 1/4"=V-0" <br />N <br />y W <br />cic— o <br />M U N <br />m X <br />cu.. o.. <br />0 <br />N D N <br />w w <br />a <br />C� <br />cc d w <br />uLn <br />�o <br />6�- U <br />0 <br />N <br />CV <br />O <br />N <br />N <br />0 <br />cfl <br />O <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />N <br />� <br />Q co 8 <br />N 0)o <br />v coo <br />- — ono <br />N <br />Q C J U-W <br />M w LL Il <br />w <br />a <br />Z tmIm <br />_o <br />7 .N $ W <br />U) IT m w <br />N N Z Q J <br />LL Z co <br />OU <br />= <br />W ❑ ❑ <br />z N M <br />z � <br />z <br />Q <br />J <br />d � <br />W N z <br />CD o <br />Q) <br />a-1 N <br />l0 w <br />� a <br />V � <br />0,^ LL' 8 <br />vI ^! C N <br />v <br />— E <br />I <br />Q Y <br />o <br />w <br />M <br />a <br />o <br />z <br />z <br />� <br />oLL <br />a R <br />Q <br />E <br />w ? <br />z <br />O a <br />0o <br />�r <br />O <br />Z <br />O C <br />to <br />dz <br />° z <br />CV <br />L <br />w o <br />4) <br />m <br />¢ o <br />Z <br />- F <br />o <br />C <br />�� <br />>z <br />ZU)cazZ <br />in <br />F� <br /><Z <br />N <br />,z <br />oa <br />Z <br />30 <br />a <br />W <br />w <br />CO <br />r <br />J� <br /><a <br />;o <br />o <br />c0 <br />V, <br />zla <br />a <br />0 3 <br />C <br />`-N <br />> L <br />CU <br />ai <br />rn <br />O <br />O <br />\ <br />0 <br />T <br />VV`v!! <br />� <br />M <br />AA1 <br />T <br />:3 C) <br />Q <br />r <br />co <br />Cn in <br />Q <br />T <br />}# <br />�--' <br />O N <br />Ln <br />a=-• <br />CV <br />C:) <br />N <br />N <br />CD <br />CT <br />CIO <br />In <br />Cib <br />a; <br />E <br />c <br />z <br />mv; <br />00 <br />Z <br />E y <br />E v «? <br />cc <br />C <br />c <br />a <br />U Q 0 <br />JOB <br />NO: 22-06575-06570 <br />SCALE : AS NOTED <br />SHEET NO. <br />7 <br />