AIR <br />BALANCE <br />+ OUTSIDE <br />AIR <br />CALCULATIONS <br />BASED <br />ON 2007 FLORIDA <br />MECHANICAL CODE, <br />TABLE <br />403.3 <br />VENTILATION <br />SPACE TYPE MEDICAL OFFICE <br />AREA OF USABLE SPACE/PEOPLE 2327 SQFT <br /># OF PEOPLE 7 /1000 SOFT <br />MIN. VENT. MULTIPLIER 20 CFM/PERSON <br />MIN. REQUIRED VENTILATION 325.8 CFM <br />VENTILATION PROVIDED 600 CFM <br />AIR BALANCE <br />EXIST RTU-1 <br />EXIST RTU-2 <br />TOTAL SUPPLY AIR <br />PRESSURIZATION <br />320 CFM <br />280 CFM <br />600 CFM <br />2900 CFM <br />20.00 <br />EXHAUST AIR OUTLETS <br />EF-1 (6) <br />OA- EA <br />480 CFM <br />480 CFM <br />OA x 100% <br />EXHAUST FAN <br />SCHEDULE <br />TAG <br />AREA SERVED <br />FAN <br />TYPE <br />DRIVE <br />TYPE <br />AIRFLOW <br />(CFM) <br />E.S.P. <br />("W.C.) <br />RPM <br />FAN <br />HP <br />VOLTAGE <br />(V/O/Hz) <br />SONES <br />DUCT <br />SIZE <br />MANUFACTURER <br />MODEL <br />ACCESS. <br />EF-1 <br />SINGLE TOILET <br />CENT. <br />DIRECT <br />80 <br />0.10 <br />900 <br />54W <br />120/1 /60 <br />2.5 <br />4" 0 <br />GREENHECK <br />SP-B80 <br />2,3,4,5,E <br />STANDARD ACCESSORIES: <br />NOTES <br />1 <br />ROOF CURB <br />1. <br />2. <br />3. <br />PROVIDE VIBRATION ISOLATORS WITH ALL FANS. <br />CONNECT EF-1 TO OPERATE WITH WALL SWITCH & PROVIDE <br />5 MINUTE TIME DELAY (IF REQUIRED). <br />PROVIDE EXPLOSION PROOF MOTOR FOR FAN IN GAS STORAGE CLOSET. <br />2 <br />BACKDRAFT DAMPER <br />3 <br />BIRDSCREEN <br />4 <br />L6 <br />WALL/ROOF CAP <br />5 <br />DISCONNECT <br />SPEED CONTROLLER <br />AIR DEVICE SCHEDULE <br />TAG <br />FACE SIZE <br />MATERIAL <br />FINISH <br />MANUFACTURER <br />MODEL <br />NOTES <br />SD-1 <br />2424 <br />ALUM. <br />WHITE <br />PRICE <br />ASCD <br />1,2,3 <br />SD-2 <br />12x12 <br />ALUM. <br />WHITE <br />PRICE <br />ASCD <br />1,2,3,4 <br />RG-1 <br />2424 <br />ALUM. <br />WHITE <br />PRICE <br />APFRF <br />1,2 <br />1. <br />REFER TO PLANS FOR ALL NECK SIZES. <br />2. <br />NOISE CRITERIA NOT TO EXCEED 30 NC. <br />3. <br />A DIFFUSERS ARE 4-WAY THROW UNLESS NOTED <br />ALL CEILING <br />N . <br />0 PLAN <br />4. <br />FOR USE IN HARD CEILING OR DUCT, PROVIDE INTEGRAL VOLUME <br />DAMPER. <br />5. <br />SUBMIT TO ARCH. FOR APPROVAL PRIOR TO ORDERING. <br />AIRFLOW <br />0 <br />EXHAUST FAN INSTALLATION <br />SCALE: NONE <br />FLEXIBLE DUCT RUNOUT TO <br />AIR DEVICE. PROVIDE <br />CAN CONNECTION TO TRUNK <br />RGLASS <br />THREADED ROD HANGER TRAPEZE <br />WITH VIBRATION ISOLATORS (TYP.) <br />INTEGRAL BACKDRAFT DAMPER <br />CEILING FAN <br />CEILING GRILLE <br />HANGER STRAP, 1 ", 22 GAUGE <br />SHEET METAL. TYPICAL <br />WRAP INSULATION ABOVE <br />THE CEILING DIFFUSERS <br />RADIUS NOT LESS THAN <br />CONICAL SPIN -IN FITTING,Z THE FLEX DUCT <br />WITH DAMPER DIAMETER <br />(OMIT DAMPER IF PROVIDED IN DIFFUSER) <br />3 SHEET METAL SCREWS THRU HELIX <br />OF FLEXIBLE DUCT, BAND CLAMP, TAPED FLEXIBLE DUCT, "THERMAFLEX MIKE" <br />NOTE: OR "METALFLEX", INSULATED <br />PROVIDE OPPOSED BLADE DAMPER DO NOT SAG OR KINK <br />IN DRYWALL CEILINGS. <br />FLEXIBLE DUCT RUNOUT <br />SCALE: NONE <br />MECHIANCAL SPECIFICATIONS: <br />1. GENERAL <br />A. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM <br />AS OUTLINED IN THE CONTRACT DRAWINGS AND THESE SPECIFICATIONS. <br />B. NOTE THAT DRAWINGS ARE DIAGRAMMATIC ONLY AND INTENDED TO SHOW THE GENERAL <br />ARRANGEMENT OF SYSTEMS, NOT EVERY MINUTE DETAIL. <br />C. DO NOT SCALE PLANS. <br />D. PROVIDE ALL NECESSARY FITTINGS, TRANSITITONS, CONNECTORS, ETC. WHETHER SHOWN <br />OR NOT ON PLANS. <br />E. ALL WORK IS NEW UNLESS OTHERWISE NOTED. <br />F. THESE PLANS REPRESENT THE DESIGN INTENT BASED ON INFORMATION AVAILABLE AT <br />THE TIME OF DESIGN. ANY SUBSTANTIAL MODIFICATIONS OR ALTERATIONS MADE DURING <br />THE CONSTRUCTION PHASE SHALL BE REPORTED TO THE ENGINEER PRIOR TO WORK. <br />MODIFICATIONS MADE WITHOUT THE ENGINEER'S WRITTEN APPROVAL SHALL REMAIN THE <br />RESPONSIBILITY OF THE CONTRACTOR. <br />G. IN CASE OF ANY DISCREPANCIES BETWEEN THE DRAWINGS, SPECIFICATIONS, FIELD <br />CONDITIONS, CODES, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REFER ALL <br />SUCH MATTERS TO THE ENGINEER IN WRITING IMMEDIATELY FOR RESOLUTION PRIOR TO <br />EXECUTING ANY WORK. ANY WORK PERFORMED WITHOUT THE WRITTEN AUTHORIZATION OF <br />THE ENGINEER SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. <br />H. ALL WORK SHALL CONFORM TO THE FOLLOWING CODES (AS APPLICABLE) AS WELL AS <br />ALL LOCAL REGULATIONS, ORDINANCES, AND AMENDMENTS: <br />2007 FLORIDA BUILDING CODE W/ 2009 SUPPLEMENT <br />2. SCOPE OF WORK <br />PROVIDE A COMPLETE NEW MECHANICAL SYSTEM AS DESCRIBED BY THESE DOCUMENTS. <br />3. ITEMS FURNISHED BY CONTRACTOR <br />IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL MATERIALS, <br />EQUIPMENT, AND ACCESSORIES NECESSARY TO MAKE A COMPLETE INSTALLATION, ALL <br />EQUIPMENT SHALL BE STORED IN A SAFE, DRY PLACE IN THE MANUFACTURER'S ORIGINAL <br />PACKAGING UNTIL READY FOR USE. THE OWNER SHALL NOT BE RESPONSIBLE FOR <br />PROVIDING ANY PART OF THE PROJECT, UNLESS SPECIFICALLY NOTED. THE CONTRACTOR <br />SHALL ALSO BE RESPONSIBLE FOR PAYING ALL REQUIRED FEES, OBTAINING ALL PERMITS, <br />AND ARRANGING FOR ALL INSPECTIONS, INCLUDING COORDINATION WITH AND SATISFYING <br />ALL REQUIREMENTS OF ANY APPLICABLE UTILITY COMPANY(IES) AS MAY BE REQUIRED TO <br />EXECUTE THIS SCOPE OF WORK. <br />4. WORK IN EXISTING BUILDINGS <br />A. DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE. <br />B. ALL ITEMS REMOVED AND NOT RE -USED SHALL BE TURNED OVER TO THE OWNER. <br />CONTRACTOR SHALL REMOVE ANY UNSATISFACTORY ITEMS FROM THE PROJECT SITE. <br />C. SOME EXISTING ITEMS TO REMAIN WITHOUT WORK ARE SHOWN FOR CLARITY OR <br />REFERENCE ONLY. NOTE THAT ADDITIONAL ITEMS WITHOUT WORK MAY ALSO BE PRESENT. <br />D. DRAWINGS OF EXISTING SYSTEMS ARE BASED ON EXISTING DOCUMENTS AND FIELD <br />CONDITIONS, SOME OF WHICH MAY BE UNVERIFIED. PRIOR TO SUBMITTING A BID, <br />CONTRACTOR SHALL STUDY THE PLANS AND VISIT THE PROJECT SITE IN ORDER TO <br />BECOME FAMILIAR WITH EXISTING CONDITIONS. ANY DISCREPANCIES IN THE CONTRACT <br />DOCUMENTS WHICH COULD SIGNIFICANTLY IMPACT THE PROJECT BUDGET OR SCHEDULE <br />MUST BE REPORTED TO THE ENGINEER IN WRITING IMMEDIATELY. FAILURE TO DO SO WILL <br />NOT BE SUFFICIENT CAUSE FOR DELAYS OR CHANGES LATER IN THE PROJECT. CHANGE <br />ORDERS RESULTING FROM FAILURE TO PROPERLY INVESTIGATE EXISTING FIELD CONDITIONS <br />WILL NOT BE ACCEPTED. ALL WORK IS NEW UNLESS OTHERWISE NOTED. <br />E. MODIFICATIONS TO EXISTING SYSTEMS NECESSARY TO CONNECT TO NEW WORK SHALL <br />BE CONSIDERED TO BE PART OF THE BASIC WORK OF THIS CONTRACT. <br />F. COORDINATE ALL WORK SCHEDULES WITH THE OWNER TO MINIMIZE DISRUPTIONS TO <br />EXISTING SYSTEMS OUTSIDE THIS SCOPE OF WORK. <br />5. COORDINATION <br />ALL WORK ON THIS PROJECT SHALL BE COORDINATED WITH THE OWNER AND ALL OTHER <br />TRADES PRIOR TO BEGINNING AY WORK OR ORDERING ANY MATERIALS. CONTRACTOR <br />SHALL REVIEW PLANS OF ALL DISCIPLINES INVOLVED AND ADVISE THE ARCHITECT IN <br />X PRIOR TO ANY <br />A S THAT MAY EXIST P I <br />WRITING OF ANY CONFLICTS CODE OR SAFETY ISSUE <br />FABRICATION OR ORDERING OF EQUIPMENT. RESOLUTION OF SUCH CONFLICTS WHICH ARE <br />NOT REPORTED PRIOR TO CONSTRUCTION SHALL REMAIN THE RESPONSIBILITY OF THE <br />CONTRACTOR AND CHANGE ORDER PROPOSALS FOR SUCH WORK WILL NOT BE ACCEPTED <br />PROVIDE ROUTING AND OFFSETS NECESSARY TO AVOID CONFLICTS WITH STRUCTURE, <br />FINISHES, AND WORK OF OTHERS. CONTRACTOR SHALL PROVIDE ALL CORE PENETRATIONS <br />AND PATCHING FOR FLOOR PENETRATIONS. <br />6. BASIS OF DESIGN <br />A. THE MECHANICAL CONTRACT DOCUMENTS HAVE BEEN PREPARED USING THE ASHRAE <br />97.5% DESIGN CRITERIA WITH THE FOLLOWING DESIGN CONDITIONS: <br />INDOOR OUTDOOR <br />SUMMER 75F DB/50% RH 92F DB/79F WB <br />WINTER 72F DB 36F DB <br />B. THE FOLLOWING BUILDING MATERIALS/INSULATION R-VALUES WERE USED IN THE HVAC <br />CALCULATIONS. IF THE ACTUAL MATERIALS TO BE USED IN THE CONSTRUCTION PHASE <br />(VERIFY WITH ARCH.) DIFFER FROM THESE SPECIFICATIONS, PARTICULARLY WITH REGARD <br />TO THE ROOF, CONTACT THE ENGINEER PRIOR TO CONSTRUCTION IN WRITING IMMEDIATELY <br />TO VERIFY THE ABILITY OF THE HVAC SYSTEMS TO EFFECTIVELY CONDITON THE SPACE: <br />WALLS: BRICK & CONCRETE BLOCK WALL WITH R-4 BOARD INSULATION <br />ROOF: FLAT BUILTUP ROOF WITH R-19 BATT INSULATION <br />FLOOR: CONCRETE FLOOR SLAB ON GRADE, NO INSULATION <br />GLASS: DOUBLE PANE TINTED GLASS WITH NO INTERNAL SHADES <br />7. EQUIPMENT GENERAL <br />A. ALL EQUIPMENT OF EACH TYPE SHALL BE BY ONE MANUFACTURER AND SHALL HAVE <br />CAPACITIES AND CHARACTERISTICS AS LISTED IN THE EQUIPMENT SCHEDULES. ALL <br />EQUIPMENT SHALL BE UL LISTED, NO EXCEPTIONS! SUBSTITUTIONS ARE ACCEPTABLE <br />PROVIDED THAT THE SUBSTITUTED EQUIPMENT HAS EQUIVALENT CAPACITY AS THAT <br />SCHEDULED AND IS PROVIDED BY AN ACCEPTABLE MANUFACTURER AS LISTED FOR THAT <br />EQUIPMENT TYPE. CONTRACTOR SHALL SUBMIT PRODUCT DATA FOR ALL EQUIPMENT TO <br />THE ENGINEER FOR APPROVAL PRIOR TO ORDERING. SUBMITTALS SHALL INCLUDE <br />DIMENSIONS, WEIGHT, CLEARANCES, FAN/PUMP CURVES, ELECTRICAL CHARACTERISTICS, <br />SOUND LEVEL DATA, AND INSTALLATION DETAILS. <br />B. UNLESS OTHERWISE NOTED, ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH <br />VIBRATION ISOLATING MOUNTINGS TO PREVENT TRANSMISSION OF VIBRATION TO AND <br />WITHIN THE BUILDING STRUCTURE. <br />C. LOCATE ALL MECHANICAL EQUIPMENT SUCH THAT THE MANUFACTURER'S RECOMMENDED <br />SERVICE CLEARANCE (INCLUDING CLEARANCE BETWEEN UNITS), AND THE FBC REQUIRED <br />CLEARANCE TO COMBUSTIBLES IS MAINTAINED. <br />D. INSTALL ALL EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S <br />RECOMMENDATIONS PLUMB, LEVEL, AND SQUARE IN LOCATIONS SHOWN ON PLANS. IF <br />FIELD CONDITIONS PROHIBIT INSTALLATION OF EQUIPMENT IN LOCATIONS SHOWN, SUBMIT A <br />WRITTEN REQUEST FOR INFORMATION TO THE ENGINEER IMMEDIATELY BEFORE PROCEEDING. <br />8. 9. 10. NOT USED. <br />11. FANS <br />A. ALL FANS SHALL BEAR THE AMCA CERTIFIED RATINGS LABEL AND THE UL LABEL. ALL <br />FAN MOTORS SHALL BE PROPERLY GROUNDED. <br />B. ALL FANS SHALL HAVE A SOUND LEVEL RATING NOT IN EXCESS OF THAT SPECIFIED. <br />C. ALL CENTRIFUGAL FANS SHALL HAVE TRUE WHEEL WITH INLET PERPENDICULAR TO <br />DISCHARGE. <br />D. ROOF MOUNTED FANS SHALL HAVE SPUN ALUMINUM HOUSINGS, ROOF CURB, AND <br />DISCONNECT SWITCH MOUNTED INSIDE THE HOUSING. INTEGRAL BACKDRAFT DAMPERS <br />SHALL BE TOTALLY CHATTERPROOF WITH NO METAL CONTACT. <br />E. CEILING EXHAUST FANS SHALL HAVE ACOUSTICALLY LINED HOUSINGS AND SHALL BE <br />PROVIDED WITH A TERMINAL BOX ON THE INSIDE OF THE HOUSING WITH CORD, PLUG, <br />AND RECEPTACLE. ENTIRE FAN, MOTOR, AND WHEEL ASSEMBLY SHALL BE EASILY <br />REMOVABLE WITHOUT DISTURBING THE HOUSING. <br />F. ACCEPTABLE MANUFACTURERS ARE: GREENHECK, COOK, PENN, AND BROAN. <br />12, AIR DISTRIBUTION DEVICES <br />A. PROVIDE AND INSTALL ALL AIR DEVICES IN LOCATIONS INDICATED ON DRAWINGS. VERIFY <br />LOCATIONS AND CEILING TYPES WITH ARCH. PRIOR TO ORDERING. PROVIDE INTEGRAL <br />VOLUME DAMPER FOR ALL AIR DEVICES LOCATED IN HARD CEILINGS AND INTEGRAL <br />RADIATION DAMPER FOR ALL DEVICES LOCATED IN RATED CEILINGS. <br />B. ALL AIR DEVICES SHALL BE ALUMINUM, EXCEPT THOSE INSTALLED IN RATED WALLS OR <br />CEILINGS, OR IN AREAS WHERE SUBJECT TO DAMAGE, WHICH SHALL BE STEEL. FINISH OF <br />ALL DEVICES SHALL BE WHITE UNLESS OTHERWISE NOTED ON PLANS. THE CONTRACTOR <br />SHALL VERIFY FINISH COLOR AND STYLE OF ALL AIR DEVICES WITH THE ARCHITECT PRIOR <br />TO ORDERING. <br />C. ALL SURFACES OF DUCTWORK VISIBLE THROUGH AIR DEVICES SHALL BE PAINTED FLAT <br />BLACK. <br />D. ACCEPTABLE MANUFACTURERS ARE: TITUS, PRICE, METALAIRE, TUTTLE & BAILEY, AND <br />BARBER COLEMAN. <br />13. DUCTWORK <br />A. SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS" AND "FIBROUS GLASS DUCT <br />CONSTRUCTION STANDARDS" SHALL BE CONSIDERED PART OF THE SPECIFICATIONS FOR <br />THIS PROJECT. ANY WORK WHICH DOES NOT CONFORM TO THESE STANDARDS MAY BE <br />REJECTED AT ANY TIME. <br />B. ALL SUPPLY AND RETURN AIR DUCTWORK SHALL BE CONSTRUCTED OF 24 GAUGE <br />GALVANIZED STEEL, CROSS -BROKEN, SEALED, AND 'EXTERNALLY INSULATED, SMACNA 1 <br />INCH PRESSURE CLASS, SMACNA "A" SEAL CLASS. <br />C. ALL SUPPLY AND RETURN AIR DUCTWORK SHALL BE CONSTRUCTED OF 1.5" THICK <br />R-6 FOIL FACED FIBERGLASS DUCT BOARD, TAPED AND SEALED, BY KNAUF, JOHNS <br />MANVILLE, OWENS CORNING, OR EQUIVALENT. <br />D. ALL EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED STEEL, SMACNA <br />1 INCH PRESSURE CLASS, SMACNA "A" SEAL CLASS. PROVIDE GRAVITY BACKDRAFT <br />DAMPERS IN ALL EXHAUST DUCTS NEAR THE BUILDING EXIT POINT. <br />E. ALL FLEXIBLE DUCTWORK SHALL BE THERMAFLEX TYPE M-KE R-6 OR EQUIVALENT. NO <br />FLEX DUCT SHALL EXCEED 10'-0" IN LENGTH. <br />F. NOT USED. <br />G. NOT USED. <br />H. DUCT DIMENSIONS SHOWN ARE CLEAR INSIDE DIMENSIONS. DUCT SIZE SUBSTITUTIONS <br />ARE ACCEPTABLE ONLY IF THE CLEAR AREA SUBSTITUTED IS NOT LESS THAN THAT SHOWN <br />AND THE DUCT ASPECT RATIO IS LESS THAN 4 TO 1. <br />J. PROVIDE 45-DEGREE ENTRY ON ALL RECTANGULAR BRANCH CONNECTIONS. PROVIDE <br />CONICAL TAPS WITH DAMPERS ON ALL ROUND BRANCH CONNECTIONS. <br />K. PROVIDE LONG RADIUS ELBOWS, 3-PIECE ELBOWS, OR TURNING VANES AT ALL <br />90-DEGREE TURNS. SUBSTITUTION OF SQUARE ELBOWS IS NOT ACCEPTABLE. <br />L. TEST ALL DUCTWORK FOR LEAKS PRIOR TO INSULATING. MAXIMUM LEAKAGE RATE IS 5 <br />PERCENT. <br />M. DUCTWORK SHALL NOT BE SUPPORTED BY ANYTHING OTHER THAN THE BUILDING <br />STRUCTURE. LIKEWISE, NOTHING SHALL BE SUPPORTED BY THE DUCTWORK. <br />N. PROVIDE VOLUME DAMPERS AT ALL BRANCH TAKE -OFFS OR AS INDICATED ON PLANS, <br />PROVIDE VOLUME DAMPERS IN ALL AIR DEVICES LOCATED IN HARD CEILINGS. <br />P. PROVIDE NORMALLY CLOSED MOTORIZED OUTSIDE AIR DAMPERS TO AUTOMATICALLY <br />OPEN ONLY WHEN THE HEATING OR COOLING SYSTEMS (HEATER OR COMPRESSOR) IS <br />OPERATING. OUTSIDE AIR DAMPERS SHALL NOT BE OPENED WHEN THE AIR HANDLING UNIT <br />IS SET TO "FAN ON" WITHOUT THE REFRIGERANT CIRCUIT ENERGIZED. <br />13. DUCTWORK (CONTINUED) <br />Q. PROVIDE FIRE PROOF FLEXIBLE CONNECTORS AT ALL DUCT CONNECTIONS TO FANS OR <br />AIR HANDLING UNITS, UNLESS SPECIFICALLY NOTED OTHERWISE. <br />R. PROVIDE SUPPLY AND RETURN AIR DUCT SMOKE DETECTORS FOR ALL AIR HANDLING <br />SYSTEMS GREATER THAN 2,000 CFM OR AS NOTED ON PLANS. UPON ACTIVATION, SMOKE <br />DETECTORS SHALL AUTOMATICALLY SHUT DOWN THE AIR HANDLING SYSTEM AND GENERATE <br />A SIGNAL TO THE BUILDING FIRE ALARM (IF PROVIDED). PROVIDE A REMOTE KEY SWITCH <br />WITH PILOT LIGHT IN CEILING BELOW UNIT FOR DETECTOR RESET. <br />14. PIPING <br />A. REFRIGERANT PIPING SHALL BE TYPE "K" OR "ACR" COPPER PIPE WITH WROUGHT <br />COPPER FITTINGS AND SILVER SOLDER JOINTS. REFRIGERANT LINES AND ALL ACCESSORIES <br />SHALL BE SIZED, INSULATED, AND INSTALLED ACCORDING TO THE MANUFACTURER'S <br />INSTRUCTIONS. THE MANUFACTURER SHALL BE MADE AWARE OF THE DISTANCE AND <br />VERTICAL RISE OF REFRIGERANT PIPING BETWEEN EACH AIR HANDLER AND CONDENSING <br />UNIT TO VERIFY PROPER OPERATION. <br />B. CONDENSATE DRAIN PIPING SHALL BE SCHEDULE 40 PVC, PROVIDE A P-TRAP WITH <br />CLEANOUT AT ALL DRAIN PAN LOCATIONS. ALL DRAIN PIPING SHALL BE AT LEAST THE <br />SIZE OF THE COIL DRAIN CONNECTION. SLOPE ALL DRAIN PIPING A MINIMUM OF 1/8" <br />PER FOOT TOWARDS THE DRAIN LOCATION. INSULATE ALL CONDENSATE DRAIN PIPING RUN <br />IN UNCONDITIONED INTERIOR SPACES OR WHERE CONDENSATION MAY CAUSE DAMAGE WITH <br />3/4" CLOSED CELL FOAM INSULATION. <br />C. WHERE MULTIPLE PIPES ARE RUN IN THE SAME AREA, ALL PIPING SHALL BE GROUPED <br />AND RUN PARALLEL IN A NEAT AND ORDERLY MANNER. <br />D. SUPPORT ALL PIPING ACCORDING TO THE FOLLOWING SPACING CRITERIA: <br />HORIZONTAL(FT) VERTICAL (FT) <br />CAST IRON 5 15 <br />COPPER 6 10 <br />CPVC 3 10 <br />PVC 4 10 <br />STEEL 8 10 <br />15. NOT USED. <br />16. FILTERS & BELTS <br />A. FILTERS SHALL BE OF A SIZE AND ARRANGEMENT SUITABLE TO THE REQUIREMENTS OF <br />THE EQUIPMENT. FILTERS SHALL BE THE THROWAWAY TYPE AND PROVIDE 30% EFFICIENCY. <br />B. BELTS SHALL BE REINFORCED RUBBER N" NOTCH TYPE SUITABLE FOR THE <br />EQUIPMENT ON WHICH THEY ARE INSTALLED. <br />C. AIR HANDLING UNITS SHALL NOT BE STARTED UNTIL ALL ROUGH CONSTRUCTION IS <br />COMPLETE OR AS OTHERWISE DIRECTED BY THE MANUFACTURER CHANGE ALL AIR <br />HANDLING UNIT FILTERS AT THE COMPLETION OF ALL CONSTRUCTION ACTIVITIES. <br />D. PROVIDE 2 SPARE SETS OF FILTERS AND BELTS FOR ALL EQUIPMENT. <br />16. INSULATION <br />A. INSULATE ALL SUPPLY, RETURN, AND OUTSIDE AIR METAL DUCTWORK WITH MINIMUM <br />R-6 GLASS FIBER BLANKET TYPE, 2" THICK, WITH FACTORY APPLIED, FLAME RETARDANT, <br />FOIL REINFORCED, KRAFT FACING EQUAL TO OWENS CORNING FIBERGLASS TYPE 150. <br />APPLY IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. ALL INSULATION SHALL BE <br />UL RATED 25/50/50. PROVIDE ALL ACCESSORIES NECESSARY TO MAKE A COMPLETE <br />INSTALLATION SUCH AS TAPES, SEALANTS, FASTENERS, ETC. <br />B. INSULATE ALL REFRIGERANT SUCTION PIPING AND INTERIOR CONDENSATE DRAIN PIPING <br />WITH 3/4" THICK CLOSED CELL FOAM INSULATION SUCH AS ARMAFLEX TYPE AP OR <br />EQUIVALENT. PROVIDE MANUFACTURER'S RECOMMENDED PAINT COATING ON EXTERIOR <br />INSULATION TO PREVENT DECOMPOSITION. <br />17. TEMPERATURE CONTROL <br />A. PROVIDE A THERMOSTAT FOR CONTROLLING EACH AIR CONDITIONING SYSTEM. ALL <br />THERMOSTATS SHALL BE DIGITAL 7-DAY PROGRAMMABLE TYPE, LOW VOLTAGE, WALL <br />MOUNTED, 48" ABOVE FINISHED FLOOR. THE MECHANICAL CONTRACTOR SHALL PROVIDE <br />ALL LOW A PENETRATIONS BEHIND THE <br />RMOSTATS WITH <br />VOLTAGE WIRING SEAL <br />EXPANDABLE FOAM INSULATION. THERMOSTATS SHALL HAVE SETTINGS FOR "HEAT" AND <br />"COOL" TO PROVIDE COOLING AND STAGES OF HEATING AS LISTED IN THE SCHEDULE. <br />THERMOSTATS SHALL ALSO HAVE FAN SETTINGS OF "ON" -"OFF" -"AUTO". <br />B. ALL ELECTRIC HEATERS SHALL BE INTERLOCKED WITH AIR HANDLING UNITS TO PROVIDE <br />HEATER SHUTDOWN IN THE EVENT OF FAN FAILURE. HEATER OPERATION SHALL REQUIRE <br />AIRFLOW. <br />C. ALL EQUIPMENT SHALL BE INTERLOCKED SUCH THAT HEATING AND COOLING <br />OPERATIONS CAN NOT OCCUR SIMULTANEOUSLY, UNLESS EXPRESSLY NOTED ON PLANS <br />AND ALLOWED BY FBC. <br />18. ELECTRICAL <br />A. PROVIDE ALL STARTERS, CONTACTORS, RELAYS, CONTROLS, AND ACCESSORIES TO <br />PROVIDE A COMPLETE POWER AND CONTROL WORKING SYSTEM. THE ELECTRICAL <br />CONTRACTOR SHALL PROVIDE ALL DISCONNECT SWITCHES, CONDUIT, AND WIRING FOR ALL <br />EQUIPMENT. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE <br />ELECTRICAL SPECIFICATIONS OF THESE DOCUMENTS AND THE NATIONAL ELECTRICAL CODE. <br />B. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL WIRING DIAGRAMS, BE RESPONSIBLE <br />FOR PROPER OPERATION OF THE COMPLETE SYSTEM, AND SHALL SUPERVISE ALL WIRING <br />OF MECHANICAL EQUIPMENT. COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH AND <br />PROVIDE ALL WIRING DIAGRAMS TO THE ELECTRICAL CONTRACTOR PRIOR TO THE <br />ELECTRICAL CONTRACTOR BEGINNING ANY WORK <br />C. NO WIRING OF ANY KIND SHALL BE EXPOSED IN FINISHED AREAS. WIRING TO ALL <br />MOTORS OR OTHER ELECTRICAL EQUIPMENT SHALL HAVE HEATER ELEMENTS IN EACH <br />PHASE WITH EITHER THE STARTER OR THE CONTACTOR. ALL MOTORS SHALL BE WOUND <br />FOR THE VOLTAGE SPECIFIED AND SHALL HAVE A NAMEPLATE STATING THAT VOLTAGE AND <br />CORRESPONDING AMPERES. WHERE MORE THAN ONE MOTOR OR OTHER EQUIPMENT IS <br />CONTROLLED BY THE SAME CIRCUIT, OR WHEN THE LOAD EXCEEDS THE CAPACITY OF THE <br />CONTROL EQUIPMENT, THE CONTRACTOR SHALL PROVIDE ALL NECESSARY CONTROLS AND <br />RELAYS. <br />19. WARRANTIES AND MAINTENANCE <br />A. ALL EQUIPMENT SHALL BE STARTED, TESTED, ADJUSTED, LUBRICATED, CLEANED, AND <br />PLACED IN GOOD OPERATING CONDITION BY THE CONTRACTOR. CONTRACTOR SHALL <br />GUARANTEE ALL EQUIPMENT, MATERIALS, AND WORKMANSHIP TO BE FREE OF DEFECTS <br />FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER AND THE <br />CONTRACTOR SHALL REPAIR ANY SUCH DEFECTS AT NO COST TO THE OWNER. ALL <br />EQUIPMENT INCLUDED IN THE PROJECT SHALL BE COVERED BY THE MANUFACTURER'S <br />WARRANTY FOR THE DURATION OF THAT WARRANTY. COPIES OF ALL MANUFACTURER'S <br />WARRANTIES AND CONTRACTOR WARRANTIES SHALL BE PROVIDED TO THE OWNER AT FINAL <br />ACCEPTANCE. <br />B. CONTRACTOR SHALL MEET WITH THE OWNER'S REPRESENTATIVE AND REVIEW ALL <br />OPERATIONS AND MAINTENANCE OF ALL SYSTEMS. CONTRACTOR SHALL PROVIDE THE <br />OWNER WITH BOUND COPIES OF ALL OPERATION AND MAINTENANCE MANUALS INCLUDING <br />PARTS LISTS, MAINTENANCE SCHEDULES, ETC. <br />C. THE CONTRACTOR SHALL CONTINUALLY RECORD ANY AND ALL DEVIATIONS TO THE <br />CONTRACT DOCUMENTS MADE DURING CONSTRUCTION AND PROVIDE A COMPLETE SET OF <br />THESE RECORD DRAWINGS TO THE OWNER WITHIN 30 DAYS OF COMPLETION OF <br />CONSTRUCTION. IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IT SHALL BE THE <br />RESPONSIBILITY OF THE CONTRACTOR TO SECURE THE SERVICES OF A LICENSED <br />PROFESSIONAL ENGINEER TO PROVIDE SIGNED AND SEALED RECORD DRAWINGS. <br />20 TEST AND BALANCE <br />A. THE MECHANICAL CONTRACTOR MAY TEST, ADJUST, AND BALANCE THE SYSTEM. <br />ALL PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH AABC OR NEBB <br />STANDARDS. NOTE THAT FAN SELECTION POINTS REPRESENT DESIGN AIR FLOW RATES <br />WITHOUT CONSIDERING DUCT LEAKAGE. PROVIDE ADDITIONAL DUCT SEALS AND ADJUST <br />FANS TO COMPENSATE FOR DUCT LEAKAGE. PERFORM ALL TESTS NECESSARY TO <br />ESTABLISH AND CONFIRM CAPACITY, QUALITY, AND COMPLETED STATUS OF WORK. <br />B. SPECIFIC TESTS INCLUDE (BUT ARE NOT LIMITED TO): <br />TEST & ADJUST SUPPLY FAN RPM TO DESIGN REQUIREMENTS. <br />TEST & RECORD MOTOR LOAD AMPERES. DO NOT EXCEED NAMEPLATE RATING.IFIC <br />TEST & RECORD SYSTEM STATIC PRESSURES. <br />TEST & RECORD INDOOR COIL ENTERING & LEAVING AIR CONDITIONS. <br />TEST & RECORD INDOOR COIL LEAVING AIR CONDITIONS. <br />TEST & ADJUST EACH AIR DISTRIBUTION DEVICE TO PROVIDE AIRFLOW <br />WITHIN 10 PERCENT OF DESIGN. <br />TEST & VERIFY OPERATION OF ALL ELECTRIC HEATERS. <br />DCH PROJECT NUMBER: 11-002' <br />TO THE BEST OF THE KNOWLEDGE OF THE ARCHITECTS AND <br />ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE <br />2007 FLORIDA BUILDING CODE WITH 2O09 SUPPLEMENTS AND THE <br />APPLICABLE MINIMUM FIRE SAFETY STANDARDS, <br />ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE <br />CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED <br />TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. <br />THE DRAWINGS & DESIGN ARE VALID FOR 12 MONTHS FROM DATE <br />OF ORIGINAL SEAL. <br />m <br />U <br />z <br />w <br />N <br />G✓ <br />w <br />z <br />a✓ <br />w <br />I <br />d <br />z <br />z <br />w <br />0 <br />w <br />N <br />0 <br />0 <br />N <br />0 <br />r <br />a <br />0 <br />c-) <br />ISSUE <br />DATE <br />REVIEW <br />1 /27/11 <br />PERMIT <br />1/27/11 <br />REV. <br />REV. <br />REV. <br />REV. <br />THESE DOCUMENTS, DESIGNS, NOTES, DETAILS AND <br />SPECIFICATIONS AND CONCEPTS ARE THE SOLE <br />PROPERTY OF FRAZE DESIGN, INC. AND SHALL NOT BE <br />REPRODUCED, RE -USED OR COPIED FOR OTHER <br />PROJECTS, IN WHOLE OR PART WITHOUT THE WRITTEN <br />CONSENT OF FRANK FRAZE, ARCHITECT, AIA. <br />ALL RIGHTS ARE RESERVED BY THE ARCHITECT IN <br />ACCORDANCE WITH U.S. COPYRIGHT AND PATENT <br />LAWS. UNAUTHORIZED REPRODUCTION WILL BE <br />PROSECUTED TO THE FULL EXTENT OF THE LAW. <br />PROFESSIONAL SEAL <br />t� It co oL,EON <br />s ,p <br />m <br />® d NOcrll <br />•- ()� ® w <br />.rFL O��`am�®® <br />• s mge ®e • � ®� <br />VINCENT C"alLfi iApeo <br />FLORIDA P.E. #58009 <br />k <br />�! <br />u <br />• <br />k <br />_fflN <br />- ----------- <br />s <br />• <br />SHEET TITLE <br />MECHANICAL <br />SPECIFICATIONS <br />SHEET NUMBER <br />M_ 2 <br />