<br />LIGHTING
<br />FIXTURE SCHEDULE
<br />TYPE
<br />SYMBOL
<br />DESCRIPTION
<br />VOLTS LAMP
<br />MOUNTING
<br />REMARKS
<br />NO. TYPE
<br />O2'x4'
<br />A
<br />FLUORESCENT PRISMATIC.
<br />30 NEW
<br />277 13 ENT
<br />32W
<br />CEILING
<br />HUNG 0
<br />LSI #LA125-332FASSO
<br />TS
<br />RECESSED
<br />GEN. WORKOUT
<br />E1
<br />®
<br />6" FLUORESCENT OPEN DOWNLIGHT.
<br />DMF
<br />277 1
<br />26W
<br />CEILING
<br />ODHFH6R-226
<br />PL
<br />RECESSED
<br />GENERAL NOTE:
<br />1) VERIFY ALL COLORS/FINISHES WITH DESIGN PROFESSIONAL
<br />KEYED NOTES:
<br />E1
<br />VERIFY CEIUNG TYPE PRIOR TO BID/PURCHASE.
<br />a2
<br />VERIFY CLEAR CEIUNG SPACE AVAILABLE PRIOR TO
<br />BID/PURCHASE.
<br />a3
<br />MOUNT AT +25' AFF.
<br />❑4
<br />MOUNT AT 24" BELOW 6 FL SLAB ABOVE. COORDINATE EXACT LOCATION WITH ARCHITECTURAL
<br />ELEVATIONS.
<br />F5
<br />COORDINATE EXACT MOUNTING HEIGHT & LOCATION
<br />WITH DESIGN PROFESSIONAL/INTERIOR DESIGNER.
<br />GENERAL NOTES:
<br />I. THE WORK SHALL COMPLY WITH THE LATEST APPLICABLE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, FLORIDA BUILDING CODE O.S.H.A.
<br />REQUIREMENTS AND ALL OTHER LOCAL CODES AND ORDINANCES GOVERNING THIS INSTALLATION, AS A MINIMUM STANDARD, UNLESS SPECIFICATIONS
<br />LISTED HEREIN OR SHOWN ON PLANS REQUIRE A HIGHER STANDARD.
<br />2. THE WORK INCLUDED CONSISTS OF ALL SUPERVISION, LABOR, MATERIALS, EQUIPMENT FACILITIES AND INSTALLATION REQUIRED FOR THE
<br />COMPLETE SATISFACTORY AND APPROVED ELECTRICAL SYSTEMS AS INDICATED ON THE DRAWINGS AND CALLED FOR IN THIS SPECIFICATION, OR AS
<br />MAY BE REASONABLY IMPLIED BY EITHER.
<br />3. ALL NOTES ON THE DRAWINGS PERTAINING TO THE WORK OF THIS TRADE SHALL BE CONSIDERED AS PART OF THIS SPECIFICATIONS AND
<br />CONTRACT.
<br />4. THE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE DRAWINGS AND ANY APPLICABLE SPECIFICATIONS. IF A PROBLEM IS ENCOUNTERED IN
<br />COMPLYING WITH THIS REQUIREMENT, THE CONTRACTOR SHALL NOTIFY THE OWNER OR HIS REPRESENTATIVE AS SOON AS POSSIBLE AFTER
<br />DISCOVERY OF THE PROBLEM, AND SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL THE OWNER HAS DIRECTED THE CORRECTIVE
<br />ACTION TO BE TAKEN. THE CONTRACTOR IS REFERRED TO THE ARCHITECTURAL AND MECHANICAL DRAWINGS AND SPECIFICATIONS. SUCH PLANS
<br />AND SPECIFICATIONS ARE TO BE CONSIDERED PART OF THE ELECTRICAL CONTRACT DOCUMENTS. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO
<br />SHOW APPROXIMATE LOCATIONS AND ARRANGEMENTS ONLY.
<br />5. THE CONTRACTOR SHALL COORDINATE THE PROPOSED LOCATIONS OF ALL ELECTRICAL MATERIALS AND EQUIPMENT WITH THE REPRESENTATIVES
<br />OF THE OTHER TRADES INVOLVED BEFORE STARTING INSTALLATION OF THOSE ITEMS.
<br />6. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES, CONDUIT, AND SLEEVES WITH OTHER STRUCTURAL COMPONENTS, AS THEY
<br />ARE CONSTRUCTED. ALL SLAB AND FIRE WALL PENETRATIONS MUST BE FIRE RATED AND MUST CONFORM TO OWNER'S APPROVAL AS TO LOCATION
<br />AND CONSTRUCTION DETAILS.
<br />7. THE MATERIALS AND EQUIPMENT FURNISHED SHALL BE AS INDICATED ON THE DRAWINGS; SUBSTITUTIONS SHALL NOT BE MADE EXCEPT WHERE
<br />EXPRESSLY APPROVED BY THE OWNER OR HIS REPRESENTATIVE PRIOR TO STARTING INSTALLATION OF THE ITEMS. THE ELECTRICAL MATERIALS AND
<br />EQUIPMENT FURNISHED SHALL BE LISTED OR LABELED BY UNDERWRITERS LABORATORIES OR OTHER RECOGNIZED TESTING ORGANIZATION, AND SHALL
<br />BE ACCEPTABLE TO THE LOCAL BUILDING AUTHORITY.
<br />8. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250, NEC. PROVIDE GROUND WIRES IN ALL CONDUITS UNLESS OTHERWISE NOTED.
<br />9. ELECTRICAL METALLIC TUBING (EMT) SHALL BE INSTALLED ONLY IN DRY LOCATIONS, IN CONCRETE ABOVE GRADE, AND WHERE NOT SUBJECT TO
<br />PHYSICAL DAMAGE. ALL ABOVE CEIUNG CONDUITS SHALL BE ROUTED TIGHT AGAINST THE STRUCTURE AND SHALL BE PARALLEL OR PERPENDICULAR
<br />TO THE BUILDING FEATURES. NO NEW CONDUITS SHALL BE SUPPORTED BY EXISTING CONDUITS, CEILING SYSTEMS OR AIR CONDITIONING HANGERS
<br />OR OTHER SYSTEMS.
<br />10. ALL EXPOSED CONDUITS SHALL BE RUN AS NEAT AND INCONSPICUOUS AS POSSIBLE AND PAINTED TO MATCH COLOR OF SURROUNDINGS.
<br />11. FLEXIBLE CONDUITS SHALL BE USED FOR CONNECTION TO ALL VIBRATING EQUIPMENT SUCH AS MOTORS, UGHTING FIXTURES, ETC. FLEXIBLE
<br />CONDUIT SHALL BE "LIQUID TIGHT" WHEN EXPOSED TO WEATHER.
<br />12. CONDUCTORS SIZE #8 AND LARGER SHALL BE TYPE THWN STRANDED, COPPER. CONDUCTORS SIZE #10 AND SMALLER SHALL BE COPPER,
<br />TYPE THHN SOUD, UNLESS NOTED OTHERWISE. CONDUCTORS SHALL CONSIST OF 98X CONDUCTIVITY COPPER AS INDICATED. SIZES ARE AWG. ALL
<br />CONDUCTORS SHALL BE RUN IN CONDUIT EXCEPT AS NOTED ON PLANS.
<br />13. POWER, UGHTING, AND GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN #12 AWG. EXCEPT WHERE OTHERWISE INDICATED. CONTROL
<br />CONDUCTORS SHALL NOT BE SMALLER THAN #14 AWG. CONDUCTORS SHALL BE CONTINUOUS FROM DEVICES WITHOUT SPLICES EXCEPT WITHIN WIRE
<br />WAY OR JUNCTION BOXES. MARK CONDUCTORS IN PANELS, PULL BOXES OR WIREWAYS AND TERMINAL STRIP TERMINALS FOR IDENTIFICATION OF
<br />CIRCUITS.
<br />14. CONDUCTORS SHALL BE JOINED USING COMPRESSION SPUCES, EXCEPT THAT CONDUCTORS #10 AND SMALLER MAY BE JOINED USING WIRE NUT
<br />TYPE CONNECTORS. CONDUCTORS SHALL BE TERMINATED USING COMPRESSION SPLICES USED ON CONDUCTORS #10 AWG. AND USING 3M #33+ OR
<br />#88 PLASTIC TAPE. SPLICES IN WET LOCATIONS SHALL BE INSULATED WITH ELECTRICAL TAPE AND ENCAPSULATED WITH SCOTCH CAST OR EQUAL
<br />POTTING COMPOUND.
<br />15. LOW VOLTAGE CONDUCTORS RUN THROUGH THE RETURN AIR PLENUM SHALL BE PLENUM RATED.OF THE BUILDING AND THE WORK OF OTHER
<br />TRADES WILL PERMIT.
<br />16. RECEPTACLES SHALL BE 20A, 120V, 2 POLE, 3 WIRE SINGLE OR DUPLEX GROUND TYPE EXCEPT WHERE SPECIFIC PURPOSE, LOCKING OR HIGHER
<br />RATED RECEPTACLES ARE SHOWN ON THE DRAWINGS.
<br />17. WALL SWITCHES SHALL BE OF THE TOTALLY ENCLOSED TUMBLER TYPE WITH BODIES OF PHENOUC COMPOUND. HANDLES SHALL BE WHITE
<br />COLORED.
<br />18. CONTRACTOR SHALL VERIFY ALL EQUIPMENT NAMEPLATE DATA FOR WIRING AND OVER CURRENT PROTECTION REQUIREMENTS BEFORE
<br />PERFORMING ROUGH -IN WORK.
<br />19. PROVIDE AND INSTALL JUNCTION AND PULL BOXES WHERE INDICATED AND WHERE NECESSARY TO TERMINATE, TAP OFF, OR REDIRECT MULTIPLE
<br />CONDUIT RUNS, OF SIZE INDICATED OR AS REQUIRED BY NEC. WHERE FEEDER SPLICES ARE TO BE MADE, INSTALL BOXES LARGE ENOUGH TO
<br />PROVIDE AMPLE WORK SPACE.
<br />20. LIGHTING FIXTURES SHALL BE AS INDICATED ON THE DRAWINGS AND SHALL BE INSTALLED COMPLETE WITH LAMPS. THE CONTRACTOR SHALL
<br />BE RESPONSIBLE FOR VERIFICATION OF CEILING CONSTRUCTION BEFORE ORDERING OR INSTALLING LIGHT FIXTURES.
<br />21. CONTRACTOR SHALL VISIT THE SITE AND DETERMINE THE EXTENT OF REVISIONS TO EXISTING EQUIPMENT AND WIRING TO ACCOMMODATE
<br />ARCHITECTURAL CHANGES AND ADDITIONS. ALL THE NECESSARY REROUTING AND/OR REMOVAL OF EXISTING EQUIPMENT, WIRING ETC., SHALL BE
<br />INCLUDED IN THE SCOPE OF WORK. CONTRACTOR SHALL REMOVE ALL EXISTING EQUIPMENT AND MATERIALS THAT WILL NOT BE REUSED IN
<br />CONSTRUCTION INCLUDING PIPES, CONDUITS, WIRES, TELEPHONE LINES, COMPUTER CABLE OR WIRING THAT PASSED THROUGH THE SITE OF THIS
<br />CONSTRUCTION AND RELOCATE THESE MATERIALS THAT SERVE ADJACENT BLDG. THAT ARE TO REMAIN.
<br />22. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY CONTROL WIRING FOR ALL EQUIPMENT. ELECTRICAL POWER AND CONTROL
<br />WIRING FOR HVAC AND MECHANICAL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. SEE MECHANICAL
<br />DRAWINGS AND SPECIFICATIONS FOR WIRING DIAGRAMS AND REQUIREMENTS. MECHANICAL EQUIPMENT REQUIRING STARTER SHALL BE PROVIDED BY
<br />THE MECHANICAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
<br />23. PANEL DIRECTORIES SHALL BE TYPED ACCURATELY TO SHOW AS BUILT CONDITIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY
<br />BALANCING ALL BRANCH CIRCUITS BETWEEN THE PHASES OF THE SYSTEM REGARDLESS OF CIRCUITING INDICATED. ELECTRICAL PANELS SHALL BE
<br />CONSTRUCTED WITH COPPER MAIN BUSSES AND TERMINALS.
<br />24. ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH THE DESIGN PROFESSIONAL BEFORE ROUGH INSTALLATION OF LIGHTS,
<br />RECEPTACLES AND SWITCHES FOR EXACT LOCATION.
<br />25. ALL SERVICES INTERRUPTIONS SHALL BE SCHEDULED WITH THE AUTHORIZED REPRESENTATIVE OF THE LANDLORD. ALL REMOVAL AND DISPOSAL
<br />WORK SHALL BE COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE LANDLORD.
<br />26. THE ENTIRE INSTALLATION SHALL BE PERFORMED IN •A FIRST-CLASS WORK MANNER. THE CONTRACTOR SHALL TOUCH-UP OR REFINISH THE
<br />FACTORY FINISH OF EQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION.
<br />27. TESTS: AFTER EACH SYSTEM HAS BEEN COMPLETED, A FUNCTIONAL TEST SHALL BE PERFORMED TO DEMONSTRATE THAT THE SYSTEM
<br />OPERATES IN ACCORDANCE WITH THE REQUIREMENTS OF THE DRAWINGS. THE TEST SHALL BE PERFORMED BY THE CONTRACTOR IN THE PRESENCE
<br />OF THE OWNER OR HIS REPRESENTATIVE. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF
<br />FINAL ACCEPTANCE. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL REMOVE ALL RUBBISH CAUSED BY HIS WORK AND SHALL
<br />THOROUGHLY CLEAN ALL ELECTRICAL EQUIPMENT.
<br />28. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN A COMPLETE AND SATISFACTORY INSTALLATION. AN ATTEMPT HAS
<br />BEEN MADE TO SEPARATE AND COMPLETELY DEFINE THE WORK IN SEPARATE SECTIONS OF THE SPECIFICATIONS; . HOWEVER, SUCH SEPARATION
<br />SHALL NOT RELIEVE THE CONTRACTOR FROM FULL RESPONSIBIUTY OF COMPLIANCE WITH THE WORK OF HIS/HER TRADE WHICH MAY BE INDICATED
<br />ON ANY OF THE DRAWINGS AND OTHER SECTIONS OF THE SPECIFICATIONS.
<br />29. THE CONTRACTOR SHALL CAREFULLY EXAMINE THE ARCHITECTURAL AND MECHANICAL DRAWINGS AND SPECIFICATIONS. IN ADDITION TO THE
<br />ELECTRICAL AND OTHER RELATED TRADES AND SECTIONS, THIS COORDINATION SHALL BE DONE PRIOR TO SUBMITTING THE BID.
<br />30. THE ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER THE ELECTRICAL DRAWINGS WITH REFERENCE TO BUILDING CONSTRUCTION AND
<br />DIMENTIONS. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC BUT ARE TO BE FOLLOWED AS CLOSELY AS THE ACTUAL CONSTRUCTION OF THE
<br />BUILDING AND THE WORK OF OTHER TRADES WILL PERMIT.
<br />NOTE
<br />CONSULT UTILITY FOR AIC RATING AVAIUABUTY -
<br />FUSE PER UTIUTY
<br />NOTE:
<br />REFER TO LATEST ED OF NEC FOR
<br />REQUIRED MEANS OF SERVICE DISCONNECT
<br />VOLTAGE SHALL BE 120/208
<br />W
<br />EXISTING GUTTER
<br />EXIST COLD WATER PIPE
<br />EXIST GROUND RODS
<br />CONNECTED TO EXIST
<br />BUILDING STEEL
<br />PANEL A
<br />125 A
<br />42 CIF
<br />PROP 125A/3P DIS
<br />PROP125A/3P
<br />PANEL B PANEL C
<br />E
<br />S BEEN VERIFIED THAT BUILDING SERVICE
<br />MPATIBLE WITH THE SERVICES AS SHOWN
<br />ARE NO INCREASED SERVICE LOADS PROPOSEDTENT NOTE
<br />EXIST. ELECTRICAL RISER
<br />SCALE: N15
<br />IMPORTANT ELECTRICAL SERVICE NOTE:
<br />#2/0 BARE COPPER
<br />EACH EXISTING SPACE CONTAINS A 125A SERVICE. CONTRACTOR SHALL UTILIZE
<br />THESE 3 SEPERATE 125A SERVICES AS SHOWN
<br />SITE SPECIFIC NOTES:
<br />1. EACH EMERGENCY LIGHTS SHALL BE TIED TO LIGHTING CURCUIT IN SAME ROOM OR AREA AS
<br />LOCATION OF FIXTURE PER NEC-700-12
<br />2. EMERGENCY LIGHTS SHALL HAVE BATTERY BACKUP & BE IN A FULLY RECESSED CABINET
<br />3. ALL AS -BUILT REVISIONS ARE SHOWN AS REPORTED BY THE CONTRACTOR ON [show dote].
<br />CONTRACTOR SHALL VERIFY THAT AS-BUILTS LOADS ARE PROPERLY PROTECTED AND THAT THESE
<br />LOADS DO NOT OVERLOAD THE ELECTRICAL SYSTEM. CONTRACTOR SHALL INFORM THE CUENT AND
<br />ENGINEER IN WRITING OF ANY SCENARIOS IN WHICH AS -BUILT MODIFICATIONS HAVE REDUCED SYSTEM
<br />SPARE CAPACITY TO 109: OR LESS.
<br />4. SMOKE DETECTOR, 120V WITH BATTERY BACK-UP. HARD WIRED TO BATHROOM LIGHTING CIRCUIT.
<br />INTERCONNECT FOR SIMULTANEOUS OPERATION. MOUNT AT LEAST 3' FROM A/C SUPPLY GRILLS.
<br />0
<br />z
<br />CL
<br />LLN
<br />ALL EQUPIMENT SHALL MATCH AIC RATN6 OF POMER COMPANY PER NEC 110.9
<br />EXIST PANELBOARD SCHEDULE "A"EnNG:
<br />MAIN: 125A MAIN LUGS ONLY VOLTAGE: 120/208V, 3PH, 4 WAR
<br />SUERMAACE MIN. AIC: 106
<br />DESCRIPTION
<br />WIRE/CND
<br />TRIP
<br />CKT
<br />L A
<br />L
<br />L
<br />CKT
<br />TRIP
<br />WIRE/CND
<br />DESCRIPTION
<br />SIGN
<br />2#12 & 1#12G IN 1/2
<br />20
<br />1
<br />.An2
<br />In
<br />W10
<br />ans14
<br />i28
<br />i34
<br />20
<br />2 2 & 1#12G IN 1 2"
<br />TV RECEPT
<br />TREADMILL
<br />2012 & 10212 IN 1 2
<br />20
<br />3
<br />4
<br />20
<br />2 01 2 & 1 fl 2G IN 1 2"
<br />TREADMILL
<br />TREADMILL
<br />2#12 & 1#12G IN 1/2N
<br />20
<br />5
<br />6
<br />20
<br />2 012& 1 12G IN 1 2"
<br />TREADMILL
<br />FLOOR RECEPT
<br />2#12 & 1 #120 IN 1 /27
<br />20
<br />7
<br />8
<br />20
<br />2 #12 & lfl2G IN 1 2"
<br />TREADMILL
<br />A/C
<br />3#6 & 1#100 IN 1"
<br />60
<br />20
<br />2 #12 & 1#12G IN 1 2"
<br />TREADMILL
<br />11
<br />12
<br />13
<br />15
<br />16
<br />17
<br />18
<br />19
<br />20
<br />21
<br />22
<br />23
<br />24
<br />25
<br />26
<br />271
<br />291
<br />30
<br />311
<br />32
<br />331
<br />1351
<br />38
<br />37
<br />38
<br />39
<br />40
<br />41
<br />42
<br />LOAD
<br />CONT. (CL)
<br />NON CONTINUOUS
<br />TOTAL LOAD
<br />CONT. (CL)
<br />_2000-
<br />21258 / 208 / 1.732 = 59 A
<br />NON CONTINUOUS
<br />CONNECTED
<br />CODE
<br />■ LOCK ON CUIRCUIT BREAKER . ROUTE THRU LIGHTING CONTROL ENC. CL - CONTINUOUS LOAD
<br />EXIST PANELBOARD SCHEDULE "B"
<br />MAIN: 125A MAIN LUGS ONLY VOLTAGE: 120/208V, 3PH, 4 WIRE
<br />MOUNTING: SURFACE MIN. AIC. 10,000
<br />TYPE: NEMA 1
<br />DESCRIPTION
<br />WARE/CND
<br />TRIP
<br />CKT
<br />L
<br />A
<br />I L A
<br />CKT
<br />TRIP
<br />WARE/CND
<br />DESCRIPTION
<br />MAIN LIGHTS
<br />2012 & 1#12G IN 1 2
<br />20
<br />1
<br />jAn4
<br />1 RAn
<br />'
<br />2
<br />20
<br />2 012 & lfI2G IN 1 2"
<br />WEST WALL RECEPT
<br />MANAGER OFFICE
<br />2#12 & 1#12G IN 1/2m
<br />20
<br />3
<br />20
<br />2 2 & 1 2G IN 1 2"
<br />FIRE ALARM
<br />MANAGER OFFICE
<br />2#12 & 1#12G IN 1/2
<br />20
<br />5
<br />6
<br />20
<br />2 #12 & 1#12G IN 1 2"
<br />SPARE
<br />MAIN LIGHTS
<br />2012 & 1#120 IN 1 2
<br />20
<br />1 7
<br />8
<br />20
<br />2 f12& 1#12G IN 1 2"
<br />SPARE
<br />A/C
<br />3#8 & 1#100 IN 1"
<br />40
<br />9
<br />10
<br />20
<br />2 #12 & 1012G IN 1 2"
<br />SPARE
<br />11
<br />12
<br />20
<br />2 f12 & lfI2G IN 1 Ir
<br />SPARE
<br />13
<br />14
<br />20
<br />2 2 & 1 2G IN 1 2"
<br />SPARE
<br />WEST WALL RECEPTACLES
<br />2#12 & 1#120 IN 1/2
<br />20
<br />15
<br />16
<br />20
<br />2 #12 & lfI2G IN 1 2"
<br />SPARE
<br />171
<br />18
<br />20
<br />2 012 & 1012G IN 1 2"
<br />SPARE
<br />19
<br />20
<br />20
<br />2 012& 11112G IN 1 2"
<br />SPARE
<br />21
<br />22
<br />20
<br />2 012A 11112G IN 1 2"
<br />SPARE
<br />23
<br />24
<br />25
<br />26
<br />27
<br />28
<br />29
<br />30
<br />31
<br />32
<br />33
<br />34
<br />35
<br />38
<br />37
<br />38
<br />39
<br />40
<br />41
<br />42
<br />LOAD
<br />CONT. (CL)
<br />NON CONTINUOUS
<br />TOTAL LOAD
<br />CONT. (CL)
<br />15535 / 208 / 1.732 = 44 A
<br />NON CONTINUOUS
<br />CONNECTED
<br />CODE
<br />■ LOCK ON CUIRCUIT BREAKER . ROUTE THRU UGHTING CONTROL ENC. CL - CONTINUOUS LOAD.
<br />EXIST PANELBOARD SCHEDULE "C"
<br />MAIN: 125A MAIN LUGS ONLY VOLTAGE: 120/208V, 3PH, 4 WAR
<br />FETING- SUURRFACE MIN. AIC: 10,000000
<br />DESCRIPTION
<br />WIRE/CND
<br />TRIP
<br />CKT
<br />l
<br />A
<br />A
<br />CKT
<br />TRIP
<br />WIRE/CND
<br />DESCRIPTION
<br />RECEPT
<br />2012 & 10120 IN 1/20
<br />20
<br />1
<br />79171
<br />1
<br />2
<br />20
<br />2 #12 & 1#12G IN 1/2"
<br />TANNING
<br />BATH RECEPT
<br />2#12 & 1#12G IN L/20
<br />20
<br />3
<br />4
<br />BATH LIGHT AN
<br />2012 & 1#12G IN 1/20
<br />20
<br />5
<br />6
<br />20
<br />2 #12 & 1 12G IN 1 2"
<br />SPARE
<br />OFFICE RECEPT
<br />2#12 & 1#120 IN 1/2
<br />20
<br />7
<br />8
<br />60
<br />306 & 1#100 IN 1"
<br />AC
<br />SPARE
<br />2012 & 10120 IN 1/2
<br />2010
<br />SPARE
<br />2#12 & 1#12G IN 1/2
<br />20fill
<br />1
<br />12
<br />SPARE
<br />2#12 & 1012G IN 1/20
<br />20
<br />131
<br />14
<br />20
<br />2 2 & 1#12G IN 1 2"
<br />TELEPHONE
<br />15
<br />18
<br />30
<br />2 #10 & 1#IOG IN 3/4"
<br />WATER HEATER
<br />17
<br />18
<br />19
<br />20
<br />21
<br />22
<br />23
<br />24
<br />25
<br />28
<br />27
<br />28
<br />29
<br />30
<br />31
<br />32
<br />33
<br />34
<br />35
<br />38
<br />37
<br />38
<br />39
<br />40
<br />41
<br />42
<br />El
<br />I
<br />LOAD
<br />CONT. (CL)
<br />NON CONTINUOUS
<br />TOTAL LOAD
<br />CONT. (CL)
<br />208 / 1.732 = 58 A
<br />NON CONTINUOUS
<br />ANVi21048/
<br />CONNECTED
<br />qjnjA
<br />. LOCK ON CUIRCUIT BREAKER .ROUTE THRU LIGHTING CONTROL ENC. CL - CONTINUOUS LOAD
<br />ENGINEER OF RECORD:
<br />COOL AND COBB
<br />ENGINEERING CO.
<br />CERT OF AUTHIZAT10N #29713
<br />FL LIKEN " #16921
<br />1
<br />J
<br />203 WEST MA•I ST.
<br />AVON PARK, FL 33825
<br />PH. 863.657.2323
<br />DRAFTING SERVICES BY:
<br />MICHAEL GARRISON
<br />224 DATURA ST. #401
<br />WEST PALM BEACH, FL 33401
<br />561.835.9744
<br />.TENT:
<br />'ORANGEWOOD
<br />BUILDERS
<br />DDRESS:
<br />1105 WEST CIRCLE ST
<br />AVON PARK, FL 33825
<br />863.452.6400
<br />0
<br />.J
<br />Q
<br />Q
<br />o _ o
<br />vNi
<br />lZu G�M W
<br />Q co
<br />�-4N
<br />Q
<br />IT o'` a
<br />W N .N.
<br />Q a
<br />W
<br />�.i
<br />W
<br />U
<br />-, 0
<br />W
<br />0
<br />REVISIONS/SUBMITTALS:
<br />ID DESC DATE
<br />PERMIT SUBMITTAL 112.19.11
<br />I AS BUILTS 6.11.121
<br />BY: MSG
<br />BY: COOL&COB
<br />PROJECT #: ..
<br />DATE: 5.11.12
<br />E 2
<br />Kam..... f
<br />J4