Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G .F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />FiF <br />HALF -SWITCHED DUPLEX OUTLET <br />Lph <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />3 <br />THREE-WAY SWITCH <br />14 <br />FOUR-WAY SWITCH <br />R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />Ja <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� �7 <br />J <br />ROUGH -IN FOR OPT. CEILING FAN <br />G <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />GG <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />— I <br />r I <br />I I <br />I I <br />I I <br />LAV `I_ <br />� I <br />1Ll TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />LAV <br />LAV <br />SON I <br />I <br />Zl W/C <br />SHOWER <br />_ `end p FAR <br />STUDOR <br />VENTTt , DBL SINK <br />T' W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SO. F.T. <br />1625 S,F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1560 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />st 10 KIN at <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />1 5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service <br />Same As Underground <br />150 Or 200 Amp Service <br />1 <br />Power Co. Feed <br />200A <br />Indoor Panel <br />Center <br />NEMA1 <br />RMAN <br />200 AMP <br />NEM <br />3R <br />Cable <br />#4 Solid COPPER Ground <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 -17, LOCAL CODES AND THE LOCAL POWER CO. <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT WP <br />GFI <br />1 <br />1 <br />DINING <br />KITCHEN 1 <br />r <br />GFI ( <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />114 <br />GREAT ROOM <br />^� /,^TROUGH -IN\ <br />FOR OPT. 1 <br />FAN/LIGHT 1 <br />I <br />I <br />1 / <br />FOYER <br />DB <br />0<1 NTRY WPo- <br />IGHTAS b FI® <br />ER SPECS <br />DB & GFI TO <br />BE ALIGNED I <br />VERTICALLY <br />I � _ <br />wz <br />- LU <br />IX U 0 - <br />.—M - <br />0 <br />I <br />I <br />I <br />I <br />I <br />C.M <br />1 UPSTAIRS P <br />GFI <br />@ 44" <br />` \ <br />` \ <br />W.H. <br />A.F.F. <br />1 \ 0 <br />I <br />I <br />GARAGE <br />I <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />r-------- <br />I <br />------- <br />I <br />I <br />I <br />J <br />I <br />I <br />I0uj <br />Z <br />I <br />IQ t1 <br />I <br />I0 Q <br />I <br />IJ U <br />I <br />I � <br />I <br />i I7XW <br />1 I> W <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL— UNIT—C 1624 <br />SCALE: Ya"=V-0" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />F_ --_ __ — — — — . __ ----� <br />2ND ELECTRICAL -UNIT-C 1624 <br />SCALE: X"=T-0" <br />CV <br />c <br />c� <br />ao <br />C= <br />CX <br />Cl- <br />V9 <br />d, <br />c y r <br />M <br />0 <br />N <br />u_o) <br />,ee�ttz;I r o <br />"J <br />Id0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only <br />for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />W <br />W <br />Q <br />€ <br />� <br />N <br />0 <br />N <br />in�nw <br />fNM 0 LL <br />Q LL LL LL 0 <br />Z <br />= m °i o <br />zr C <br />W <br />IL Z <br />to N � O <br />0 ��pj 0 m w <br />NO NZ d <br />Z(14OU <br />g <br />W <br />❑ ❑ <br />C <br />Z <br />z F <br />V7 <br />�-J <br />z v <br />s <br />l� <br />O <br />N <br />w <br />o <br />g <br />V1 <br />c <br />®AN <br />U <br />w 2 <br />E <br />28 <br /><� <br />_ <br />jig <br />So a2 <br />Q Y <br />W <br />• <br />N <br />s eo <br />ti <br />o <br />C'rJ <br />J <br />o <br />w <br />Z <br />d <br />z <br />J <br />L.L C <br />aC <br />p <br />U <br />� <br />z o <br />�� <br />o° <br />�z <br />> <br />z <br />b <br />z® <br />°a <br />Z <br />QQ <br />I� <br />°o <br />10 <br />o <br />� <br />1z <br />ra <br />mg <br />° LL <br />Z <br />j C <br />m tL <br />J <br />�o <br />ia� <br />z <br />qz <br />iN <br />33 <br />U ]U <br />W <br />U]az <br />3 <br />soF <br />a� <br />-Ir <br />r <br />w< <br />o <br />v <br />0 <br />o 's <br />0 <br />O <br />rn <br />M <br />N <br />� <br />� <br />N <br />H <br />M <br />CoQO <br />10 <br />CV <br />LO <br />CV <br />V <br />a <br />E: <br />00 <br />U) .2 <br />U <br />T- <br />O <br />�- <br />O <br />O) <br />In <br />LO <br />M <br />LO <br />co <br />QLO <br />O <br />rn N <br />LO <br />Lo <br />r <br />z <br />O <br />c� <br />Z <br />c <br />m <br />E 7— <br />U <br />v Qi <br />cc <br />c <br />a <br />,° <br />Q p <br />JOB <br />NO: 23-00582-00577 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />