Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14, Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24'. The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />[Q7- <br />HALF -SWITCHED DUPLEX OUTLET <br />I � <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />�3 <br />THREE-WAY SWITCH <br />14 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />P� <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />PM <br />ELECTRIC METER <br />_ia <br />ELECTRIC PANEL <br />_�► <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />L J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />J� I <br />HANSON <br />BOX <br />I I <br />3 VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT <br />LAV <br />I LAV <br />I <br />I <br />--__ I u W/C <br />LAV T\- <br />_I 1 3" SHOWER <br />L TUB/ <br />W/C SHOWER ` <br />3" \nd F FLR <br />STUDOR <br />VENTTI , DBL SINK <br />T' W/ DISP. <br />LAV I W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -C- (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />1 5200 <br />TOTAL: 31878 <br />LOAD WATTS -- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA 1 <br />200 AMP <br />TER MA N <br />1 0-200 A P IT/ —Serial Cable <br />NEM <br />3R <br />Power Co. Feed --. I -I I , #4 Solid COPPER Ground <br />C.O. <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 -17, LOCAL CODES AND THE LOCAL POWER CO. <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />0 <br />DISCONNECT <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I— — — — — — — — — — — — — — <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. / \� <br />FAN/LIGHT `� `' GFI <br />.n. <br />-QD -- -mil <br />1 <br />DINING <br />KITCHEN 1 <br />/ __ <br />FI O <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />194 <br />GREAT ROOM <br />/,^ROUGH -IN\ <br />` FOROPT. <br />FAN/LIGHT' <br />I <br />I <br />I / <br />RY <br />T AS - 0 <br />SPECS <br />u <br />\LLJ <br />LL Q 0 <br />��o� <br />�m <br />I <br />I <br />I <br />I <br />I <br />I <br />rGF1—j <br />C.M <br />DEDICATED <br />RECEPTACLE .. <br />�••�MICROWAVE <br />RANGE HOOD PER <br />�•�� � <br />J UPSTAIRS F <br />@ 44" <br />`� `� W.H. <br />A.F.F. <br />1 ` 0 <br />/ <br />1 <br />I <br />I GARAG E <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I <br />I <br />I <br />10 Z <br />I <br />IQ d <br />I <br />10 Q <br />I <br />L U <br />I <br />Iw <br />5 W <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL -UNIT-C 1624 <br />SCALE: A"=V-0" <br />2ND ELECTRICAL -UNIT-C 1624 <br />SCALE: Ya"=1'-0" <br />�O <br />� N <br />co <br />to 'LL t� <br />-0(--) <br />C <br />Z L) <br />0 <br />Q <br />o <br />t C-7 <br />r. <br />.; <br />�_ 1- <br />_7 <br />✓ � O <br />O 0 <br />U <br />l 2 0 L1J <br />0 <br />N <br />0 <br />N <br />N <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is onty for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />CD <br />a E `m r, <br />a <br />o M8 CW pat <br />N N O1 it LL <br />V <br />Q <br />r0 <br />W <br />a <br />� r- r' a LL W 0- <br />y' m Q N Y <br />J LL (L <br />'ri <br />z <br />L 0 <br />OL <br />MLu <br />� CZl of <br />Win�piO' <br />¢ a a <br />Z <br />IL <br />00 a <br />N MZ Xro0 <br />0 <br />O U U J y <br />Z <br />W <br />❑I�❑ <br />Z N <br />z � <br />Q � <br />J <br />N <br />- N <br />Z o <br />C.7 0 <br />� a <br />V <br />O <br />W $ <br />'�Ly <br />v <br />N <br />U <br />Lu <br />J <br />G <br />Q <br />-0 <br />O <br />W <br />O <br />� <br />Lj_ <br />n. 0 <br />g <br />og <br />�z <br />�® <br />oa <br />N U <br />qg. <br />U <br />O <br />0W¢�a>a <br />Nt <br />Z2z <br />Z� <br />ial <br />oW <br />o <br />Nw <br />O <br />O <br />o r <br />> d' <br />rn <br />N <br />� <br />M <br />cfl <br />r <br />cfl <br />N <br />Cn <br />N <br />M <br />N <br />o <br />O <br />U) m <br />V I <br />O <br />50 <br />r <br />4. <br />CD <br />`CV <br />N <br />CV <br />00 <br />NO <br />� <br />L17 <br />�' <br />T <br />o <br />W <br />Z 0 <br />Li <br />Z <br />E 10 <br />E <br />N <br />W <br />a <br />U .-°r <br />Q O <br />JOB <br />NO: 21-17091-17908 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />15 <br />