THIS DETAIL ONLY REFERS TO THE DIAMOND -MESH <br />EXPANDED METAL LATH ATTACHMENT. <br />METAL LATH <br />16GAxl-1\2" LONG (3/4"-l" CROWN) <br />STAPLES @ 6" O.C. VERT BETWEEN <br />STUDS (NOTED THUS:—) - OFFSET <br />STAPLES BETWEEN STUDS AS SHOWN <br />WALL SHEATHING <br />16GAx1-1/2" LONG (3/4"-1" <br />CROWN) STAPLES @ 6" <br />O.C. VERT INTO STUDS <br />(NOTED THUS:—) <br />METAL LATH ATTACHMENT DETAIL <br />REV. 09.24.21 SCALE: 3/4" = V-0" <br />*DETAIL EXCEEDS THE REQUIREMENTS FOR FBCR 703.7.1 LATH* <br />**ONLY APPLIES TO LENNAR TPA/JAX** <br />10'-0" <br />TANK -LESS W/H <br />CORNER OF <br />HOME H C G <br />GARAGE SIDE O 0 0 <br />5'-0" <br />0CoSTUB-OUT FOR 0 1'-0" o o ;1 <br />GAS METER <br />� U <br />O o <br />CV x <br />• MEASUREMENTS ARE FROM FINISHED FLOOR <br />• ROUGH -IN GAS TO RIGHT (ALWAYS) - 12" OFF -CENTER <br />• ROUGH -IN ELECTRIC TO LEFT (ALWAYS) - 12" OFF -CENTER <br />GAS CONNECTION DETAIL <br />**ONLY APPLIES TO HILLSBOROUGH AND PASCO COUNTY** <br />RAFTER SPAN TABLE <br />MEMBER SIZE AND SPACING <br />MAXIMUM LENGTH <br />MEMBER CONNECTIONS* <br />2" X 4" @ 16" O.C. <br />7-5" <br />(2)16d TOENAILS <br />2" X 6" @ 16" O.C. <br />10'-8" <br />(2)16d TOENAILS <br />2" X 8" @ 16" O.C. <br />13'-9" <br />(3)16d TOENAILS <br />2" X 10" @ 16" O.C. <br />16'-5" <br />1 SIMPSON HTS20 OR 3 16d TOENAILS <br />2" X 12" 16" O.C. <br />19'-3" <br />1) SIMPSON HTS20 OR (4 16d TOENAILS <br />2" X 4" @ 24" O.C. <br />6'-1" <br />(2)16d TOENAILS <br />2" X 6" @ 24" O.C. <br />81-6" <br />(2)16d TOENAILS <br />2" X 8" @ 24" O.C. <br />11'-0" <br />(2)16d TOENAILS <br />2" X 10" @ 24" O.C. <br />13'-0" <br />(3)16d TOENAILS <br />2" X 12" @ 24" O.C. <br />151-4" <br />(1) SIMPSON HTS20 OR (3)16d TOENAILS <br />" TOENAIL CONNECTIONS DESIGNED FOR SHEAR ONLY (i.e. RAFTER TO RIDGEBEAM). <br />** SOUTHERN YELLOW PINE, 55 PSF LOADING <br />Backer and Filler Block Dimensions <br />BCI®Joist <br />Backer Block <br />Thickness <br />Filler Block Thickness <br />Series <br />3/4" or 7/l <br />5000s 1.8/1.7 <br />wood panels <br />Two 3/4" wood panels or 2 x <br />1-1/8" or two 1/2" <br />6000s 1.8/1.7 <br />,Hood panels <br />2 x — + 5/8" or 3/4" wood panel <br />1-1/8" or two 1/2" <br />6500s 1.8/1.7 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 112" <br />602.0 <br />wood panels <br />2 x — + 5/8" or 3/4" wood panel <br />90 2.0 <br />—T— <br />2 x _ lumber <br />Double 2 x —lumber <br />DOUBLE JOIST CONSTRUCTION <br />(Not required if both loaded equally from above) <br />Filler blocking- <br />1/8" gap <br />1) Support back of web during nailing to prevent damage to <br />web -flange connection. <br />2) Block solid between joists for full length of span. <br />3) Leave 1/8" gap between top of filler blocking and bottom of top flange. <br />4) Place joists together and nail from each side with 2 rows of 10d nails <br />2x_: CONTRACTOR TO PROVIDE 2x TO FILL THE HEIGHT at 12" o.c., clinched when possible. Stagger rows from opposite <br />OF THE JOIST ASA REQUIRED LEAVING Y8' GAP @ TOP sides by 6". <br />DOUBLE JOIST CONNECTION <br />N.T.S. <br />SQUASH BLOCKS AT INTERIOR <br />BEARING <br />Vertical load transfer =1900 plf max along load bearing wall. <br />Load bearing wall must stack <br />*Non -stacking walls <br />over squash=20 blocks and <br />require additional <br />wall or beam below.* <br />consideration. Check <br />local building <br />1/16 <br />code for appropriate <br />details in <br />One 10d box <br />areas=20 of high <br />or=20 sinker <br />lateral load. <br />nail each side <br />at bearing. <br />Squash block <br />(2x4 minimum) <br />Bearing wall, Versa -Lam LVL or <br />Glulam Beam <br />NO HOLES (EXCEPT <br />KNOCKOUTS) ALLOWED <br />IN BEARING ZONES —� <br />DO NOT cut, notch <br />or drill flanges <br />Boise Joist Blocking <br />Use 3" f 10d1 nails at 6" o.c. <br />Provide adequate bearing <br />J for each lapped joist. <br />10dnails SECTION @ INT. BRG. WALL <br />N.T.S. <br />MINIMUM SPACING = 2x GREATEST <br />D DIMENSION OF LARGEST HOLE <br />(see table below) (KNOCKOUT EXEMPTS) D <br />(see table below) <br />FILL CELL STD. 900 HOOK BOND BEAM <br />rn- <br />w <br />cc <br />CONT. #5 > STD. 90° <br />HOOK <br />BAR <br />W"M I <br />BOND BEAM STEP <br />SCALE: N.T.S. <br />CONT, #5 <br />BAR <br />— #5 CONT. <br />FROM <br />FOUNDATION <br />TO HIGHEST <br />BOND BEAM <br />2nd FLOOR <br />INTERIOR/EXT WALL SEE <br />PLAN FOR MORE INFO <br />CONT. BASE PLATE <br />BEARING COLUMN <br />-� <br />.._ <br />PLYWOOD FLOOR <br />SEE PLAN FOR REQ'DSHEATHING <br />PER PLAN <br />COLUMN AND <br />CONNECTION <br />TJI TO BE CUT TO ALLOW <br />FOR BLOCKING/TJI <br />MASONRY WALL OR <br />1 ' <br />INTERIOR BRG. WALL <br />TJI PER PLAN <br />r = • <br />OTHERWISE SOLID <br />BLOCKING TO MATCH <br />L Solid block all posts from <br />2nd FLOOR <br />above to bearing below. <br />STUU DS <br />S <br />SECTION @ INT. BRG. WALL <br />N.T.S. <br />1/8" min. 2" min. <br />}Small gap „ <br />2" max. 4 max. - <br />� Web Stiffener Fastener Schedule <br />Joist Bearing Location - <br />a --- <br />_— BCS5000s®i 9 8" i 2nd Intermediate � <br />I 14" 1 2-8d� <br />Clinch nails 9-1/2"2-8d 2-8I d <br />I <br />when BC160005 11-7%8" 2-8d 3-8d <br />possible BC 6500 ® 14' 2-� <br />16" 2-Sd 6-8d <br />11-7/8" 2-8d 3-8d <br />_ - - BCI 60s 14 2-8d 5-8d <br />Tight fit ---16" 2-8d 6-8d- <br />1 -7/ " 3-16d 3-16d _.. --- <br />2x4/Plywood/OSB web stiffener 2" min. LBCI0s® 14" 4" max. 5-16d 5-16d <br />required when indicated or 16" 6-16d 6-16d <br />- Hangers with side nailing. <br />- Hangers with sides not containing WEB STIFFENER <br />top flange of joist. <br />- Birdsmouth cuts. N.T.S. <br />- Under 2nd floor column w/ loads <br />higher than 15001b. <br />BLOCKING PANEL, INTERIOR <br />Vertical load transfer =1900 plf max. along bearing wall <br />Required on interior walls : - for vertical load transfer <br />when load bearing - for lateral support when joists <br />meet over wall, or wall stacks directly over wall or <br />beam below Load bearing wall must stack over <br />blocking and wall or beam below.* <br />1-When joists meet over wall, provide <br />1 3/4" minimum bearing for each. <br />Use 10dx3" nails at 6"o.c. for all joist <br />blocking panel "Non -stacking walls <br />require additional consideration. — <br />dC k.,U I HIV T VVrICRC IIV CANTILEVER <br />THE WEB. PROVIDE AT <br />LEAST 3" OF CLEARANCE <br />FROM OTHER HOLES <br />MINIMUM DISTANCE FROM SUPPORT, LISTED BELOW, IS REQUIRED FOR ALL HOLED GREATER THAN 1Y2" <br />NOTES: <br />DO NOT CUT HOLES <br />LARGER THAN 1Y" <br />ROUND IN <br />CANTILEVERS. <br />1. JOISTS MUST BE PROPERLY DESIGNED TO MEET BUILDING CODE REQUIREMENTS. <br />2. TABLE IS FOR UNIFORMLY LOADED MAXIMUM LOADS OF 40 PSL(LIVE) AND 15 PSF (DEAD) ON SIMPLE SPAN APPLICATIONS ONLY. <br />3. REFER TO JOIST SPECIFIER GUIDE FOR INSTALLATION AND OTHER INFO. <br />4. SELECT A TABLE ROW BASED ON JOIST DEPTH AND THE ACTUAL JOIST SPAN ROUNDED UP TO THE NEAREST TABLE SPAN. SCAN ACROSS <br />THE ROW TO THE COLUMN HEADED BY THE APPROPRIATE ROUND HOLE DIAMETER OR RECTANGULAR HOLE SIDE. USE THE LONGEST SIDE OF <br />A RECTANGULAR HOLE. THE TABLE VALUES IS THE CLOSEST THAT THE CENTERLINE OF THE NEAREST SUPPORT. <br />5. THE ENTIRE WEB MAY BE CUT OUT. DO NOT CUT THE FLANGES. HOLES APPLY TO EITHER SINGLE OR MULTIPLE JOISTS IN REPETITIVE <br />MEMBER CONDITIONS. <br />6. FOR MULTIPLE HOLES, THE AMOUNT OF UNCUT WEB BETWEEN HOLES MUST EQUAL AT LEAST TWICE THE DIAMETER (OR LONGEST SIDE) OF <br />THE LARGEST HOLE. <br />7.1y" ROUND KNOCKOUTS IN THE WEB MAY BE REMOVED BY USING A SHORT PIECE OF METAL PIPE AND HAMMER. <br />8. HOLES MAY BE POSITIONED VERTICALLY ANYWHERE IN THE WEB. THE JOIST MAY BE SET WITH THE 1Y2" KNOCKOUT HOLES TURNED WITHER <br />UP OR DOWN. <br />9. THIS TABLE WAS DESIGNED TO APPLY TO THE DESIGN TO APPLY TO THE DESIGN CONDITIONS COVERED BY TABLES ELSEWHERE IN HIS <br />PUBLICATION. USE THE BC CALC SOFTWARE TO CHECK OTHER HOLE SIZES OR HOLES UNDER OTHER DESIGN CONDITIONS. IT MAY BE <br />POSSIBLE TO EXCEED THE LIMITATIONS OF THIS TABLE BY ANALYZING A SPECIFIC APPLICATION WITH THE BC CALC SOFTWARE. <br />HOLE CUTTING CHART <br />N.T.S. <br />Plumbing <br />Joist <br />I -Joist can be offset <br />up to 3" to avoid <br />vertical plumbing <br />3" max <br />JOISTS OFFSET <br />N.T.S. <br />Backer block (12" wide min.) <br />Nail with 10-10d nails. <br />',,, Install tight to, top flange. <br />Joist hanger <br />\ y' Filler block. <br />Nail with <br />10-10d nails. <br />Backer block required where top <br />mount hanger load exceeds 250 lbs. <br />Install fight to top flange. <br />t 1/4"-2" gap ?2 <br />i I <br />' Backer Block 1 <br />"Top Mount" "Face Mount" <br />Backer block shall be tight Backer block shall be tight <br />to bottom of top flange with to top of bottom flange with <br />1/4%2" gap at top of bottom 1/4%2" gap at bottom of top <br />flange. flange. <br />Web stiffner as <br />Web stiffeners are not required when top required if hanger <br />flange is laterally supported by joist hanger. doesn't meet <br />height <br />requirements <br />0.6 X Joist <br />p � depth <br />I -JOISTS BUCKETS <br />N.T.S. <br />SIMPSC <br />w/ (22) <br />NAILS T <br />5/8"0 <br />THRU <br />BOLT <br />SIMPSC <br />w/(22)' <br />NAILS T <br />R TRUSS <br />OP PLATE <br />TYPICAL SIMPSON MGT TO <br />BUILT-UP COLUMN DETAIL <br />TYPICAL SIMPSON LUS/HUS/HUC <br />INSTALLATION <br />NIN. EMBEDMENT <br />SCHEDULE FOR <br />AND QUANTITY <br />W FASTENERS <br />TYPICAL SIMPSON META12 / <br />META12 TSS INSTALLATION <br />A/C CHASE 4" PVC <br />SLEEVE THRU STEM <br />WALL <br />SLEEVE THRU STEMS <br />SEE PLAN FOR •• • . • <br />FOUNDATION INFO It a • 4' <br />STEM FOUNDATION <br />GRADE <br />` A/C CHASE 4" PVC <br />SLEEVE THRU FOOTING <br />MONO FOUNDATION <br />REINF. SEE PLAN <br />(2) #5 REBAR <br />TYP. FND. PENETRATIONS <br />SCALE: N.T.S. <br />SIMPSON META12 / META12 TSS <br />INSTALLATION @ MID SPAN <br />NOTE: <br />UPLIFT VALUE <br />IS BASED ON <br />S.P.F. <br />LOCATION OF <br />SECOND H10A <br />SIMPSON H10A • • *' (WHEN <br />w/ (18)10d x 1 1/2" REQUIRED) <br />NAILS <br />UPLIFT = 1015# <br />TYPICAL SIMPSON H10A <br />INSTALLATION <br />TYPICAL SIMPSON MTS <br />/ HTS INSTALLATION <br />TOP (2) #5's x 4'-0" v <br />CENTERED @ PIPE <br />PENETRATION <br />I ° ° <br />a • <br />— d. d; d Q ° <br />12" BELOW <br />GRADE <br />PLUMBING LINE <br />PVC OR SCH40 SLEEVE <br />° <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE VERTICAL THRU FND. <br />TOP (2) #5's x 4'-0"— <br />CENTERED @ PIPE <br />PENETRATION <br />d <br />PVC OR SCH40 SLEEVE <br />PLUMBING LINE <br />d n <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE PERPENDICULAR TO FND. <br />TOP (2) #5's x 4'-0" PVC OR SCH40 SLEEVE <br />CENTERED @PIPE <br />PENETRATION PLUMBING LINE <br />7 Q b .d d° d All G <br />Ir �� L� a a <br />�L11 <br />Jill <br />T <br />0 <br />SEE FND. PLN. <br />SIZE & REINF. <br />e.a <br />f� <br />ca <br />C� <br />o <br />-o <br />2 <br />a <br />aC. � o <br />m <br />r C L,L d <br />C <br />{n .D N L <br />N N �O <br />'Q <br />3= dY <br />oa tz � c <br />E s c <br />C ra <br />% <br />�o <br />a� <br />0 <br />l <br />• NS ' <br />'/t <br />"• F L p <br />��%•�*ArOFESS10N <br />a <br />�\\ <br />To the best of the Engineees knowledge, Information and belief, <br />the structural plans and spedficadons contained within these <br />drawings comply wide the 2020 Florida Building Code - <br />Residential <br />7th Edition. Engineers signature and seat is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />H <br />$� <br />Cb <br />r_9_� <br />C <br />dl <br />Q <br />r'n04Q1? <br />gLLLL u <br />Z <br />a <br />4m e 52 <br />tag <br />oc <br />tpl-,R 2 dot <br />2 Qj 0) m w <br />Z <br />ILWrn <br />= <br />�, N Z d k <br />N OU <br />W <br />0 <br />❑ ❑ <br />a <br />a <br />/� <br />IY <br />Cn LL <br />0 <br />�(Z <br />w <br />C 42, <br />a C3 <br />M <br />19 <br />U` <br />t03 ! <br />Q <br />E <br />C v0 <br />aLL <br />a <br />zo <br />a <br />�_ <br />�0 <br />e° <br />Z <br />E <br />off <br />L <br />Z <br />C <br />_ <br />So <br />N� <br />�F <br />° <br />aLL <br />>wz <br />(fib <br />�� <br />W <br />v 3 <br />� <br />am <br />N Y <br />�IH7 <br />�o <br />IIIIi <br />2I <br />r <br />�r <br />N <br />T <br />C6 <br />ca <br />3 <br />r` <br />r <br />� <br />T <br />UM_ <br />O <br />O <br />ao <br />T <br />CV <br />t--- <br />T— <br />O <br />W O <br />LO <br />O <br />iC <br />,,,., <br />M N <br />p N <br />1 <br />Q d- <br />c <br />OCI,N a <br />�' <br />00 <br />6 <br />E <br />c O <br />00 <br />T <br />f. <br />T <br />Z <br />c• <br />E O <br />c <br />m <br />a. <br />J _J <br />ili <br />v <br />Q O <br />c <br />_J <br />JOB <br />NO : 22-12560-12553 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />SN 1 <br />