SECOND FLOOR ELECTRICAL PLAN (ELEVATION A AND B' <br />1 /4" = 1'-0" <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST T FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />SEP � � 2022 <br />a�ifed <br />7th <br />rugs h <br />for comb Debra <br />Edition Y <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />io <br />SWITCH ° <br />4 1/2" <br />DOORJAMB DUPLEX 19 <br />OUTLET 'c%) <br />TRIM o <br />0 <br />BASE <br />Jp <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oz <br />S �' <br />SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />HORIZONTAL <br />AT 12" - TOP PLUG IS HOT <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET -VERIFY W/MANUF. SPECS <br />® FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />STRUCTURED WIRE OUTLET <br />-69- SWITCH AT 36" <br />� 3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />-0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />--0 DIMMER SWITCH AT 36" <br />PUSH-BUTTON DOORBELL <br />-- CLG MNT LT FIXTURE <br />-}- CLG MNT PREWIRE - FIXTURE BY OWNER <br />} SURFACE MNT FIXTURE <br />-} WALL MNT FIXTURE <br />NOTE: <br />TUB/SHOWER ND OPALEX - ALTERNATE <br />CANS MAY BE <br />4 50W PAR30 NFL 6" WHITE BAFFLE USED IF <br />APPROVED BY <br />0 50W MR16 4" LOW VOLTAGE OWNER <br />80 50W PAR20 NFL 4" MINI ROUND RECESS <br />�0 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />-F} CLG FAN PREWIRE AND SWITCH <br />cs COMBINATION CARBON MONOIXED DETECTOR/ <br />SMOKE DETECTOR <br />S�J SMOKE DETECTOR <br />-U-18m UNDER CABINET 18" <br />cS-18m SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= SINGLE 24" FLUOR STRIP <br />=D-24= DOUBLE 24" FLUOR STRIP <br />— U-36 UNDER CABINET 36" <br />S-36 — SINGLE 36" FLUOR STRIP <br />D-36 — DOUBLE 36" FLUOR STRIP <br />S-48 SINGLE 48" FLUOR STRIP <br />D-48 DOUBLE 48" FLUOR STRIP <br />® 24"CLG MNT WRAPPED FLUOR LIGHT <br />1 48 48"CLG MNT WRAPPED FLUOR LIGHT <br />F_m 24 -_;9 24" VANITY LIGHTING <br />999-m 36 ;;FR 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />EXHAUST FAN/LIGHT <br />(, EXHAUST FAN <br />DOUBLE FLOOD LIGHT W/ COVERS AND <br />15OW PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />® CEILING MNT SPEAKER <br />IM CHIMES (DELETE W/ INTERCOM) <br />= MASTER STATION <br />ELEC PANEL <br />® VACUM OUTLET AT 12" <br />14 CEILING RETURN AIR <br />IS A/C REGISTER <br />® THERMOSTAT <br />011 SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />W <br />L > `O `? U <br />cMN di <br />N <br />-0- OF W m <br />E co <br />} � o <br />�tuag�< <br />�N <br />W <br />w Q� <br />Oo EM rn <br />L <br />W <br />w <br />w P w J w m' 0 <br />LLLLJ <br />jgQQQ0��U00�0(.5 <br />oz°oi~a <br />oOw00mzz <br />�z <br />wd-WW <br />v <br />ZCL <br />w <br />�o_WwQ?wz <br />m <br />�O IL <br />LL <br />oW �wa <br />o =O o�Qw <br />Q <br />0¢ <br />O <br />N <br />Z <br />O� <br />(n O <br />0 M O <br /><wMp- <br />LL <br />ti <br />QLuQU? <br />co <br />ZUF�- <br />w <br />W <br />_jo <br />O <br />co <br />� <br />I <br />i <br />�— <br />N <br />Cl <br />Cl <br />0 <br />N <br />0 <br />0 <br />N <br />Cl <br />N <br />Cl <br />N <br />N <br />N <br />O <br />.- <br />o0 <br />0 <br />N <br />I <br />I <br />' <br />Z <br />O <br />Lo <br />w <br />o <br />0 <br />0 <br />0 <br />o <br />� <br />c <br />M <br />u^�) <br />w <br />¢z <br />C) <br />W <br />z� <br />0 <br />V <br />WOO <br />UVFn <br />Lo <br />O <br />O�Q <br />Q <br />Z <br />a -a <br />F- <br />W Q <br />N <br />� <br />�,W <br />N <br />?_� <br />..N <br />0zwo <br />�— <br />Z <br />U <br />W� <br />�zLL <br />. <br />� <br />H <br />QZ <br />0V <br />0CL <br />J <br />W <br />z <br />Of <br />Z <br />w <br />w4zt <br />0 <br />LAST PLOT DATE <br />• <br />April 7, 2022 <br />z <br />O <br />2ND FLOOR <br />ELECTRICAL PLAN <br />