SECOND FLOOR ELECTRICAL PLAN (ALL ELEVATIONS' <br />1 /4" = 1'-011 <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST T FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />OCT 2 8 2022 <br />VR/\ <br />Virtual Review Assist. Inc. Plans Review completed and approved <br />for compliance with the 2020 FBC 7th Edition <br />by Debra Anne Klahr PX2300 <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />io <br />SWITCH- <br />4 1/2" <br />DOORJAMB <br />DUPLEX <br />OUTLET co <br />TRIM <br />o <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oZ <br />A—'SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />110V DUPLEX OUTLET AT 12" <br />Q� <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />1HORIZONTAL <br />AT 12" - TOP PLUG IS HOT <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET - VERIFY W/MANUF. SPECS <br />FOR LOCATION & TYPE <br />.1 TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />STRUCTURED WIRE OUTLET <br />SWITCH AT 36" <br />3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />—0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />—o DIMMER SWITCH AT 36" <br />—fl PUSH-BUTTON DOORBELL <br />} CLG MNT LT FIXTURE <br />{- CLG MNT PREWIRE - FIXTURE BY OWNER <br />-{}- SURFACE MNT FIXTURE <br />} WALL MNT FIXTURE <br />NOTE: <br />40W A 6" ROUND OPALEX - ALTERNATE <br />TUB/SHOWER CANS MAY BE <br />0 50W PAR30 NFL 6" WHITE BAFFLE USEDIF <br />APPROVED BY <br />6 50W MR16 4" LOW VOLTAGE OWNER <br />0 50W PAR20 NFL 4" MINI ROUND RECESS <br />0 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />{} CLG FAN PREWIRE AND SWITCH <br />COMBINATION CARBON MONOIXED DETECTOR/ <br />cs SMOKE DETECTOR <br />SMOKE DETECTOR <br />rU-18= UNDER CABINET 18" <br />rS-18a SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= <br />SINGLE 24" FLUOR STRIP <br />=D-24= <br />DOUBLE 24" FLUOR STRIP <br />— U-36 = <br />UNDER CABINET 36" <br />— S-36 — <br />SINGLE 36" FLUOR STRIP <br />— D-36 — <br />DOUBLE 36" FLUOR STRIP <br />— S-48 <br />SINGLE 48" FLUOR STRIP <br />— D-48 <br />DOUBLE 48" FLUOR STRIP <br />24 24"CLG MNT WRAPPED FLUOR LIGHT <br />1 48 48"CLG MNT WRAPPED FLUOR LIGHT <br />9;:24:;;g 24" VANITY LIGHTING <br />F7mF36--FuR 36" VANITY LIGHTING <br />5----48 48" VANITY LIGHTING <br />® EXHAUST FAN/LIGHT <br />0 EXHAUST FAN <br />DOUBLE FLOOD LIGHT W/ COVERS AND <br />150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />® CEILING MNT SPEAKER <br />M CHIMES (DELETE W/ INTERCOM) <br />In--<: MASTER STATION <br />�i..l ELEC PANEL <br />® VACUM OUTLET AT 12" <br />CEILING RETURN AIR <br />E3 A/C REGISTER <br />® THERMOSTAT <br />SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />E <br />0 U <br />_W\ <br />In M <br />-I.. <br />V) V -0 :0 `— <br />M <br />L <br />0 <br />O <br />g <br />-2` <br />° `L C) C <br />vd" <br />.—.0 <br />N V w SD N c <br />0 ri <br />W L <br />Iz, a 06 <br />ow vi WOF- <br />~LU <br />WWL-QQ0(D Wj)�00=oaao <br />= <br />J <br />OUWWOZm �U <br />Z� <br />a5 <br />z <br />gQOWQ55Wz <br />¢OW1-F- <br />°— <br />2Wx�OZ <br />�OO " <br />(A LL <br />Ow OozQaF-LL <br />MWQ <br />� <br />O <br />Z <br />W <br />F- <br />D ti <br />O <br />cM <br />Q w M <br />LL <br />w � <br />z <br />< W < Ln <br />F'-IYaM <br />W CL <br />Z V <br />2: 3: <br />W <br />Wo <br />O <br />OO <br />o0000 <br />O <br />O <br />�- <br />N <br />N <br />O <br />M <br />N <br />O <br />0-0N <br />O <br />tP <br />O <br />O <br />N <br />CoO <br />' <br />z <br />O <br />Nwo <br />> <br />o <br />N <br />aoo <br />CM <br />V <br />Lo <br />; <br />Z~ <br />W <br />v, <br />¢ z <br />w <br />Q <br />W <br />000 <br />M <br />O <br />U <br />�z5; <br />Lo <br />—0 <br />0 <br />ow — <br />a <br />Z <br />CL-a <br />CL <br />Q <br />w <br />~p ~O <br />N <br />W <br />ZOM <br />. . <br />W <br />QED <br />N <br />O <br />ZWO <br />Z <br />U <br />dZw <br />Z <br />Uz <br />U <br />� <br />H <br />p <br />_o <br />W <br />z <br />z <br />w <br />� <br />W <br />J <br />c, <br />0 <br />LAST PLOT DATE <br />• <br />May 2, 2022 <br />z <br />0 <br />2ND FLOOR <br />ELECTRICAL PLAN <br />