Laserfiche WebLink
:R <br />FIRST FLOOR ELECTRICAL PLAN A <br />1 /4" = 1'-0„ <br />LINE OF ROOF <br />—.• <br />SECOND FLOOR ELECTRICAL PLAN A <br />1 /411 = 1'-011 <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST T FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES. <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />200A INDOOR PANEL <br />CENTER <br />10 <br />#15 copper to lights & outlets <br />NEMA 1 <br />200 AMP <br />#12 copper to 20 amp ckts <br />00 <br />#10-2 copper to WH <br />#10-3 copper to Dryer <br />METER <br />2/0 or 4/0 SER Alu <br />MAIN <br />0 <br />200 amp <br />150 amp <br />Disconnect <br />POWER CO. FEED <br />4 Bare Cu Ground <br />Footer STEEL <br />Groundrod tied to footer steel <br />OR <br />4 Bare attached to footer steel <br />GROUNDING PER 250.50 AND <br />250.52 NEC <br />TYPICAL 150-200 AMP ELECTRICAL RISER DIAGRAM <br />NTS <br />AUG 2 d 202x <br />VRA <br />Virtual Review Assisi 1! 1C. <br />Plans Review ccin�IF. - :, and appro <br />for compliance with tree 2020 FBC 7th <br />Edition by Debra Anne Klahr PX2300 <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />�4 <br />SWITCH ° <br />4 1/2" <br />DOOR JAMB DUPLEX <br />OUTLET ih <br />TRIM <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />o <br />S <br />SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />AT 12" - TOP PLUG IS HOT <br />HORIZONTAL <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET - VERIFY W/MANUF. SPECS <br />® FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />® STRUCTURED WIRE OUTLET <br />�9-- SWITCH AT 36" <br />3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />-O PUSH BUTTON FOR GARAGE DOOR OPENER <br />DIMMER SWITCH AT 36" <br />-� PUSH-BUTTON DOORBELL <br />CLG MNT LT FIXTURE <br />{- CLG MNT PREWIRE - FIXTURE BY OWNER <br />SURFACE MNT FIXTURE <br />-6- WALL MNT FIXTURE <br />NOTE: <br />40W A 6" ROUND OPALEX - <br />ALTERNATE <br />TUB/SHOWER <br />CANS MAY BE <br />4� <br />50W PAR30 NFL 6" WHITE BAFFLE <br />USEDIF <br />APPROVED BY <br />6 <br />50W MR16 4" LOW VOLTAGE <br />OWNER <br />4Z 50W PAR20 NFL 4" MINI ROUND RECESS <br />�0 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />} CLG FAN <br />PREWIRE AND SWITCH <br />CS COMBINATION CARBON MONOIXED DETECTOR/ <br />SMOKE DETECTOR <br />Q SMOKE DETECTOR <br />°U-18' <br />UNDER CABINET 18" <br />cS-18- <br />SINGLE 18" FLUOR STRIP <br />=U-24= <br />UNDER CABINET 24" <br />=S-24= <br />SINGLE 24" FLUOR STRIP <br />=D-24= <br />DOUBLE 24" FLUOR STRIP <br />— U-36 = <br />UNDER CABINET 36" <br />— S-36 — <br />SINGLE 36" FLUOR STRIP <br />— D-36 — <br />DOUBLE 36" FLUOR STRIP <br />— S-48 <br />SINGLE 48" FLUOR STRIP <br />— D-48 <br />DOUBLE 48" FLUOR STRIP <br />24 <br />24"CLG MNT WRAPPED FLUOR LIGHT <br />14 <br />48"CLG MNT WRAPPED FLUOR LIGHT <br />F;: 24 ;;R <br />24" VANITY LIGHTING <br />gFuF36:;-uR <br />36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />EXHAUST FAN/LIGHT <br />O EXHAUST FAN <br />j5„a DOUBLE FLOOD LIGHT W/ COVERS AND <br />V 150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />® CEILING MNT SPEAKER <br />(M CHIMES (DELETE W/ INTERCOM) <br />=r MASTER STATION <br />1111111ii-0 ELEC PANEL <br />® VACUM OUTLET AT 12" <br />® CEILING RETURN AIR <br />® A/C REGISTER <br />® THERMOSTAT <br />SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />N <br />N <br />o <br />N <br />LID <br />tY <br />W <br />-80 <br /><', • 1 <br />a <br />2 <br />w <br />z <br />A' E <br />A\ > 0 M O <br />W L <br />Q M" ; <br />. <br />N V Q y° 2 Mo <br />� •� r <br />C:�� �o <br />�t Upg °'< <br />.N LU Q� <br />L E 5 <br />W o0 <br />W w <br />WFF--Q M�� � YzW Z <br />(� <br />< Q <br />Q <br />W <br />0 <br />�0-�QOQ��LLU00 <br />jOox Z�(y,LLOZ200E-QF- <br />0 <br />L) <br />- <br />5 0 <br />F- <br />0 <br />Z <br />Ov)w4a0 Owoomz-, <br />'O4a.8zyo�-zLL­`0M'aF06WWOR <br />0 <br />WWFa-FZ�Z��v�Q. <br />OM o 0 o<ZgQ¢ <br />¢ <br />ILL <br />LL <br />O <br />O <br />Z <br />W <br />0� <br />F- cM O <br />Q U) M <br />lt <br />V)�I,- <br />F— W a- cM <br />01 13- � <br />Z U F- <br />Z <br />W <br />Wo <br />J <br />O <br />mi <br />N <br />N <br />O <br />N <br />ti <br />N <br />i <br />O <br />0 <br />00 <br />N <br />cflao0aC) <br />N <br />N <br />N <br />C)O <br />N <br />O <br />N <br />O <br />N <br />C) <br />N <br />C:) <br />N <br />C) <br />N <br />C) <br />N <br />ob <br />O <br />6 <br />a0 <br />O <br />A <br />16 <br />N <br />c? <br />NN <br />N <br />� <br />j <br />o <br />o <br />Q <br />oC! <br />LO <br />N <br />M <br />d <br />LO <br />CO <br />t-- <br />CO <br />Z Z <br />O <br />p}' <br />W <br />W W W <br />U �'- <br />O <br />UoQ <br />F—OLO <br />a <br />0 <br />x <br />un <br />Z <br />a. <br />III <br />W I- <br />F—m0Z <br />F- Of <br />N <br />�Z <br />W <br />00 <br />�MzW <br />M <br />Z'Z U- <br />N <br />w N <br />O�2z <br />U°->- <br />=QZ <br />O <br />Z <br />U <br />� <br />OU <br />O <br />W <br />� <br />Z <br />Z <br />z <br />w <br />J <br />" <br />W <br />N <br />O <br />C) <br />LAST PLOT DATE <br />Jul. 21, 22 <br />z <br />�O <br />1 ST & 2ND FLOOR <br />J <br />ELECTRICAL <br />PLAN <br />A <br />