<br />CODES, GUIDELINES, AND STANDARDS
<br />APPLICABLE CODES, GUIDELINES, AND STANDARDS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
<br />THE FLORIDA BUILDING CODE, 7TH EDITION (2020), BUILDING
<br />THE FLORIDA BUILDING CODE, 7TH EDITION (2020), EXISTING
<br />THE FLORIDA BUILDING CODE, 7TH EDITION (2020), MECHANICAL
<br />THE FLORIDA BUILDING CODE, 7TH EDITION (2020), PLUMBING
<br />THE FLORIDA BUILDING CODE, 7TH EDITION (2020), ENERGY CONSERVATION
<br />THE FLORIDA BUILDING CODE, 7TH EDITION (2020), ACCESSIBILITY
<br />THE FLORIDA FIRE PREVENTION CODE, 7TH EDITION (2020)
<br />THE FLORIDA ADMINISTRATIVE CODE, RULE NO.69A-3.012 STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION AND OTHER
<br />STANDARDS ADOPTED
<br />NFPA 70, 2017 EDITION, NATIONAL ELECTRICAL CODE
<br />NFPA 101, 2018 EDITION, THE LIFE SAFETY CODE (FLORIDA SPECIFIC EDITION)
<br />AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A17.1-2016/CSA B44-16, SAFETY CODE FOR ELEVATORS AND ESCALATORS
<br />NATIONAL FIRE PROTECTION ASSOCIATION
<br />NFPA 01-2018 EDITION, THE FIRE CODE (FLORIDA-SPECIFIC EDITION)
<br />NFPA 10-2018 EDITION, STANDARD FOR PORTABLE FIRE EXTINGUISHERS
<br />NFPA 12-2015 EDITION, STANDARD ON CARBON DIOXIDE EXTINGUISHING SYSTEMS
<br />NFPA 13-2016 EDITION, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
<br />NFPA 14-2016 EDITION, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS
<br />NFPA 15-2017EDITION, STANDARD FOR WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION
<br />NFPA 25-2017 EDITION, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER -BASED FIRE PROTECTION SYSTEMS
<br />NFPA 70-2017 EDITION, NATIONAL ELECTRICAL CODE
<br />NFPA 72-2016EDITION, NATIONAL FIRE ALARM AND SIGNALING CODE
<br />NFPA 75-2013 EDITION, STANDARD FOR THE FIRE PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT
<br />NFPA 80-2016 EDITION, STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES
<br />NFPA 9OA-2018 EDITION, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS
<br />NFPA 90B-2018 EDITION, STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS
<br />NFPA 92-2015EDITION, STANDARD FOR SMOKE -CONTROL SYSTEMS
<br />NFPA 99-2018 EDITION, HEALTH CARE FACILITIES CODE
<br />NFPA 101-2018EDITION, THE LIFE SAFETY CODE (FLORIDA-SPECIFIC EDITION)
<br />NFPA 101A-2016 EDITION, GUIDE ON ALTERNATIVE APPROACHES TO LIFE SAFETY
<br />NFPA 105-2016 EDITION, STANDARD FOR SMOKE DOOR ASSEMBLIES AND OTHER OPENING PROTECTIVES
<br />NFPA 110-2016 EDITION, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
<br />NFPA 204-2015 EDITION, STANDARD FOR SMOKE AND HEAT VENTING
<br />NFPA 241-2013 EDITION, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS
<br />NFPA 251-2006 EDITION, STANDARD METHODS OF TESTS OF FIRE RESISTANCE OF BUILDING CONSTRUCTION AND MATERIALS
<br />NFPA 252-2017 EDITION, STANDARD METHODS OF FIRE TESTS OF DOOR ASSEMBLIES
<br />NFPA 253-2015 EDITION, STANDARD METHOD OF TEST FOR CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT
<br />HEAT ENERGY SOURCE
<br />NFPA 255-2006 EDITION, STANDARD METHOD OF TEST OF SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS
<br />NFPA 259-2018 EDITION, STANDARD TEST METHOD FOR POTENTIAL HEAT OF BUILDING MATERIALS
<br />NFPA 286-2015 EDITION, STANDARD METHODS OF FIRE TEST FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO
<br />ROOM FIRE GROWTH
<br />NFPA 288-2017 EDITION, STANDARD METHODS OF FIRE TESTS OF HORIZONTAL FIRE DOOR ASSEMBLIES INSTALLED IN HORIZONTAL
<br />FIRERESISTANT-RATED ASSEMBLIES
<br />NFPA 701-2015 EDITION, STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF TEXTILES AND FILMS
<br />NFPA 703-2018 EDITION, STANDARD FOR FIRE RETARDANT -TREATED WOOD AND FIRE -RETARDANT COATINGS FOR BUILDING MATERIALS
<br />NFPA 704-2017 EDITION, STANDARD SYSTEM FOR THE IDENTIFICATION OF THE FIRE HAZARDS OF MATERIALS FOR EMERGENCY RESPONSE
<br />MISCELLANEOUS STANDARDS AND TESTING COMPANIES
<br />UNDERWRITERS LABORATORIES INC. (UL)-HTTP://DATABASE.UL.COM/CGI-BIN/XYV/TEMPLATE/LISEXT/l FRAME/FIRERESSRCH.HTML
<br />WARNOCK HERSHEY-INTERTEK, INC. (WHI) -HTTP://WWW.INTERTEK.COM/DIRECTORIES/
<br />AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)/SEI 29-2014, STANDARD CALCULATION METHODS FOR STRUCTURAL FIRE PROTECTION
<br />ICC Al 17.1-2009, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
<br />ANSI/BHMA Al56.3-2008, EXIT DEVICES
<br />BHMA Al56.10-2011, STANDARD FOR POWER OPERATED PEDESTRIAN DOORS
<br />BHMA A156.19-2013, STANDARD FOR POWER ASSIST AND LOW ENERGY POWER OPERATED DOORS
<br />FLORIDA PRODUCT APPROVAL, FAC 9N-3
<br />Al CODE SUMMARY
<br />NO SCALE
<br />TYPE OF CONSTRUCTION
<br />FBC TABLE 601 FIRE -RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
<br />BUILDING ELEMENT
<br />TYPE 11
<br />TYPE III
<br />TYPE IV
<br />TYPE V
<br />A
<br />A
<br />B
<br />A
<br />B
<br />HT
<br />A
<br />B
<br />PRIMARY STRUCTURAL FRAMEf
<br />3a
<br />1
<br />0'
<br />1
<br />0
<br />HT
<br />1
<br />0
<br />(SEE SECTION 202)
<br />BEARING WALLS
<br />EXTERIORe, f
<br />3
<br />1
<br />0
<br />2
<br />2
<br />2
<br />1
<br />0
<br />INTERIOR
<br />3a
<br />1
<br />0'
<br />1
<br />0
<br />1/HT
<br />1
<br />0
<br />NONBEARING WALLS & PARTITIONS
<br />SEE TABLE 602
<br />EXTERIOR
<br />NONBEARING WALLS & PARTITIONS
<br />0
<br />0
<br />0
<br />0
<br />0
<br />SEE SECTION
<br />0
<br />0
<br />INTERIORd
<br />2304.11.2
<br />FLOOR CONSTRUCTION AND
<br />ASSOCIATED SECONDARY MEMBERS
<br />2
<br />1
<br />0'
<br />1
<br />0
<br />HT
<br />1
<br />0
<br />(SEE SECTION 202)
<br />ROOF CONSTRUCTION AND
<br />ASSOCIATED SECONDARY MEMBERS
<br />1 1 /2b
<br />1 b, c
<br />0C
<br />1 b, c
<br />0
<br />HT
<br />1 b, c
<br />0
<br />(SEE SECTION 202)
<br />FOR SI: 1 FOOT = 304.8 MM.
<br />a. ROOF SUPPORTS: FIRE -RESISTANCE RATINGS OF PRIMARY STRUCTURAL FRAME AND BEARING
<br />WALLS ARE PERMITTED TO BE REDUCED BY 1 HOUR WHERE SUPPORTING A ROOF ONLY.
<br />b. EXCEPT IN GROUP F-1, H, M AND S-1 OCCUPANCIES, FIRE PROTECTION OF STRUCTURAL MEMBERS
<br />SHALL NOT BE REQUIRED, INCLUDING PROTECTION OF ROOF FRAMING AND DECKING WHERE EVERY
<br />PART OF THE ROOF CONSTRUCTION IS 20 FEET OR MORE ABOVE ANY FLOOR IMMEDIATELY BELOW.
<br />FIRE -RETARDANT -TREATED WOOD MEMBERS SHALL BE ALLOWED TO BE USED FOR SUCH
<br />UPROTECTED MEMBERS.
<br />c. IN ALL OCCUPANCIES, HEAVY TIMBER COMPLYING WITH SECTION 2304.11 SHALL BE ALLOWED
<br />WHERE A 1 HOUR OR LESS FIRE -RESISTANCE RATING IS REQUIRED.
<br />d. NOT LESS THAN THE FIRE -RESISTANCE RATING REQUIRED BY OTHER SECTIONS OF THIS CODE.
<br />e. NOT LESS THAN THE FIRE -RESISTANCE RATING BASED ON FIRE SEPARATION DISTANCE
<br />(SEE TABLE 602).
<br />f. NOT LESS THAN THE FIRE -RESISTANCE RATING AS REFERENCED IN SECTION 704.10.
<br />FLOOR CONSTRUCTION AND SUPPORTING PRIMARY STRUCTURAL FRAME IS REQUIRED TO HAVE EQUAL
<br />HOUR RATING WHERE SUPPORTING SHAFTS, PER FBC SECTION 711.
<br />FIRE -RESISTANCE RATED CONSTRUCTION
<br />FBC TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS
<br />UNPROTECTED OPENINGS, GREATER THAN 30 FEET: NO LIMIT
<br />FBC SECTION 713.4 SHAFT ENCLOSURES FIRE -RESISTANCE RATING
<br />CONNECTING 4 STORIES OR MORE: 2 HOUR
<br />CONNECTING LESS THAN 4 STORIES: 1 HOUR
<br />(FIRE -RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED NOT EXCEED
<br />2 HOUR)
<br />FBC SECTION 1023.2 EXIT ENCLOSURES FIRE -RESISTANCE RATING
<br />CONNECTING 4 STORIES OR MORE: 2 HOUR
<br />CONNECTING LESS THAN 4 STORIES:1 HOUR
<br />FBC SECTION 508 MIXED OCCUPANCY SEPARATION
<br />1-2 / F-1 : 2-HOUR
<br />MEANS OF EGRESS
<br />FBC SECTION 1005.3 EGRESS WIDTH PER OCCUPANT SERVED
<br />SPRINKLERED: STAIRWAYS (INCHES PER OCCUPANT) 0.3
<br />OTHER EGRESS COMPONENTS (INCHES PER OCCUPANT) 0.2
<br />FBC SECTION 1010.1.1.1 PROJECTIONS INTO CLEAR WIDTH
<br />BETWEEN 34 INCHES AND 80 INCHES ABOVE FINISHED FLOOR, 4 INCHES, MAX
<br />NFPA 101 (FLORIDA SPECIFIC), 7.1.5 -HEADROOM
<br />7 FEET-6 INCHES WITH PROJECTIONS FROM CEILING NOT LESS THAN 6 FEET 8 INCHES, WITH A TOLERANCE
<br />OF -3/4 INCHES, ABOVE FINISHED FLOOR AND MINIMUM CEILING HEIGHT MAINTAINED FOR NOT LESS THAN
<br />TWO-THIRDS OF CEILING AREA.
<br />STAIRS: NOT LESS THAN 6 FEET 8 INCHES MEASURED VERTICALLY ABOVE A PLANE PARALLEL TO, AND
<br />TANGENT WITH, MOST FORWARD PROJECTION OF STAIR TREAD.
<br />NFPA 101 (FLORIDA SPECIFIC) SECTION 7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREA
<br />NOT MORE THAN 50 PERCENT OF REQUIRED NUMBER OF EXIT STAIRS SERVING NORMALLY OCCUPIED
<br />AREAS OF EACH FLOOR, AND NOT MORE THAN 50 PERCENT OF EXIT STAIR CAPACITY REQUIRED FOR
<br />NORMALLY OCCUPIED AREAS OF EACH FLOOR, SHALL DISCHARGE THROUGH AREAS ON ANY LEVEL OF
<br />DISCHARGE.
<br />FBC SECTION 1020.2 MINIMUM CORRIDOR WIDTH: 44 INCHES
<br />INTERIOR FINISHES
<br />FBC TABLE 803.11 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY
<br />INTERIOR EXIT STAIRWAYS, RAMPS, AND EXIT PASSAGEWAYS: CLASS B
<br />CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS: CLASS B,
<br />PER FFPC SECTION 38.3.3.2 (MORE STRINGENT)
<br />ROOMS AND ENCLOSED SPACES: CLASS C
<br />FBC SECTION 804 INTERIOR FLOOR FINISH VERTICAL EXITS, EXIT PASSAGEWAYS, AND ACCESS CORRIDORS:
<br />CLASS II (MORE STRINGENT THAN FFPC)
<br />OTHER
<br />ALL FIRE RATED DOORS SHALL HAVE CLOSERS AND POSITIVE LATCHING, SEE SPECIFICATION 08 7100.
<br />ALL DOORS IN THE PATH OF EGRESS, SERVING AND OCCUPANT LOAD OF 50 OR MORE, SHALL BE EQUIPPED
<br />WITH EXIT DEVICES.
<br />ALL DOORS SHALL BE PROVIDED WITH HARDWARE HAVING A SHAPE THAT IS EASY TO GRASP WITH ONE
<br />HAND.
<br />NFPA 10 SECTION 6.2.1.2.2 FIRE EXTINGUISHERS
<br />SHALL BE LOCATED SO THAT THE MAXIMUM TRAVEL DISTANCES SHALL NOT EXCEED 75 FEET.
<br />GENERAL BUILDING HEIGHT AND AREA
<br />FBC SECTION 504 BUILDING HEIGHT AND NUMBER OF STORIES
<br />ALLOWABLE
<br />PROVIDED
<br />HEIGHT (FBC TABLE 504.3a): SPRINKLERED
<br />180'-0"
<br />67'-4"
<br />NUMBER OF STORIES (FBC TABLE 504.4): SPRINKLERED
<br />10
<br />15
<br />FBC TABLE 506.2 ALLOWABLE AREA: SPRINKLERED, MULTI -STORY (SM)
<br />ALLOWABLE
<br />AREA
<br />LEVEL
<br />AREA
<br />PROVIDED
<br />USE AND OCCUPANCY
<br />1-2: CONDITION 2
<br />FACTORY GROUP F-1: ACCESSORY OCCUPANCY
<br />MIXED USE AND OCCUPANCY
<br />FBC SECTION 508.4 SEPARATED OCCUPANCIES
<br />IN EACH STORY, THE BUILDING AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS OF THE ACTUAL
<br />BUILDING AREA OF EACH SEPARATED OCCUPANCY DIVIDED BY THE ALLOWABLE BUILDING AREA OF EACH
<br />SEPARATED OCCUPANCY SHALL NOT EXCEED 1. EACH SEPARATED OCCUPANCY SHALL COMPLY WITH THE
<br />BUILDING HEIGHT LIMITATIONS BASED ON THE TYPE OF CONSTRUCTION OF THE BUILDING IN ACCORDANCE
<br />WITH SECTION 503.1. INDIVIDUAL OCCUPANCIES SHALL BE SEPARATED FROM ADJACENT OCCUPANCIES IN
<br />ACCORDANCE WITH TABLE 508.4.
<br />1. SOLID LINES INDICATE NEW CONSTRUCTION FOR THE PHASE INDICATED. SCREENED LINES
<br />INDICATE EXISTING CONSTRUCTION TO REMAIN OR NEW CONSTRUCTION COVERED IN ANOTHER
<br />DIVISION.
<br />2. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IMPACTING THE WORK AND
<br />REPORT DISCREPANCIES TO THE ARCHITECT AND OWNER'S REPRESENTATIVE.
<br />3. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO
<br />OWNER OCCUPIED AREAS ADJACENT TO NEW CONSTRUCTION OR OCCUPIED AREAS WHERE
<br />VARIOUS SYSTEM CONNECTIONS OR EXTENSIONS ARE REQUIRED.
<br />4. ALL DIMENSIONS ARE FROM FINISH FACE OR GRID LINE.
<br />5. WHEN SURFACES APPEAR ADJACENT TO EACH OTHER THE FINISH SURFACES MUST ALIGN.
<br />6. IF, DURING RENOVATION OR NEW CONSTRUCTION, THE EXISTING SMOKE DETECTORS, FIRE
<br />ALARM PULLS, EXIT LIGHTS, ETC. ARE HIDDEN OR DISABLED, THEN THESE DEVICES SHALL BE
<br />TEMPORARILY RELOCATED OR REPLACEMENTS PROVIDED TO MAINTAIN THE LIFE SAFETY
<br />REQUIREMENTS OF THE OCCUPIED AREAS.
<br />A10 GENERAL CONSTRUCTION NOTES
<br />NO SCALE
<br />1 ■ 2 ■ 3 ■ 4 ■ 5 ■ 6 ■ 7 ■ 8 ■ 9 ■ 10 ■ 11 ■ 12 ■ 13 ■ 14 ■ 15
<br />PROJECT NORTH
<br />NORTH REFERENCE
<br />TRUE NORTH
<br />HEIGHT--,
<br />100'-0" ELEVATION TARGET
<br />1ST LEVEL
<br />POINT OF TOP OF PARAPET
<br />ELEVATION
<br />DETAILED
<br />DETAIL NUMBER AREA
<br />Al SIM �� DETAIL REFERENCE
<br />01 /
<br />SHEET NUMBER
<br />SECTION NUMBER Akllt6s'
<br />IM
<br />1
<br />101 SECTION REFERENCE
<br />SHEET NUMBER
<br />ELEVATION NUMBER > Al SIM
<br />ARROWS POINT TO��
<br />ELEVATIONS DRAWN A101 ELEVATION REFERENCE
<br />SHEET NUMBER
<br />rf
<br />0
<br />NEW EXISTING COLUMN DESIGNATION
<br />I COLUMN i COLUMN
<br />i
<br />�F—REVISION NUMBER
<br />—SCOPE OF REVISION
<br />DOORS ARE TO RECEIVE
<br />THE NUMBER OF THE ROOM
<br />WHICH IT SERVES. IF MORE THAN 200-A DOOR NUMBER
<br />ONE DOOR SERVES THE ROOM A
<br />LETTER DESIGNATION FOLLOWS
<br />THE DOOR NUMBER
<br />CONFERENCE ROOM ROOM NAME & NUMBER
<br />101
<br />SEAL
<br />2I -- WALL TYPE NUMBER
<br />K000 MATERIAL NOTE
<br />REFERENCE
<br />G000 GENERAL NOTE
<br />REFERENCE ARASH AHANI KAMANGAR, AIA AR95990
<br />A1010-100 EQUIPMENT NOTE Is
<br />REFERENCE AdventHealth
<br />ZEPHYRHILLS
<br />EXTERIOR GLAZING ID
<br />GENERATOR ADDITION
<br />INTERIOR GLAZING ID
<br />CEILING
<br />BASE XX-01 WALL
<br />-01 XX-0 ROOM FINISHES
<br />XX-0
<br />FLOOR
<br />Hunton 091
<br />ARCHITECTS
<br />DATE SUBMISSION NO
<br />ACCENT WALL FINISH 12.17.21 CONSTRUCTION DOCUMENTS
<br />AND LIMITS
<br />II-01 MISCELLANEOUS FINISH
<br />OR NOTE
<br />A16 SYMBOL LEGEND
<br />NO SCALE
<br />ARCHITECTURAL NOTES & SYMBOLS &
<br />PROJECT DATA