C <br />v <br />v <br />ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general). In a Flood Zone, all electrical equipment to be at or above DFE. <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 44" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC. <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2014 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />'� <br />DUPLEX CONVENIENCE OUTLET <br />FF <br />DUPLEX OUTLET ABOVE COUNTER <br />� wP <br />WEATHERPROOF DUPLEX OUTLET <br />�&GFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />�3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />#PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />POWER CO. FEED <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEC 14, 250.94 _ / <br />200A <br />INDOOR PANEL <br />CENTER <br />#14 copper to lights & outlets <br />NEMA t <br />200 AMP <br />10 #12 copper to 20 amp clots <br />#10-2 copper to WH <br />#10-3 copper to Dryer <br />METER <br />n <br />2/0 or <br />410 SER Alu <br />200 amp <br />150 amp <br />4 Bare Cu Ground <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />WP DISC. <br />GFI H. <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />unnn ono col=nc <br />O <br />EXHAUST FAN <br />--- <br />j <br />W.H. VERIFY LOCATION <br />- <br />Iry <br />GFI <br />_ _ _ _ _ <br />_ _ _ _ _ <br />J <br />ELECTRICAL PANEL <br />EXHAUST FAN/LIGHT COMBINATION <br />db <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />RECEFIT. <br />CH <br />CHIMES (OPTIONAL) <br />FOR ALARM VERIFY METER <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />SYSTEM LOCATION WITH <br />BUILDER <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />0 <br />TELEVISION (OPTIONAL) <br />©2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />A <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />G J <br />A 1 <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />T J <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />ELECTRICAL PLAN - ELEV-Al <br />SCALE: %4"=1'-0" <br />0 <br />C4 <br />O <br />CV <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained <br />within these <br />drawings comply with the 2017 <br />Florida Building Code - <br />Residential 6th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />M <br />F <br />Q <br />_� E <br />O <br />O—Q� <br />00 <br />N (p <br />5 <br />(0 <br />5N C <br />4t oo <br />LrDEo, <br />® <br />0) <br />2 - J <br />-5 U_ <br />LL J d <br />laWZii <br />N <br />of c) <br />°'ia <br />of ci <br />cc: -0oIX0 <br />LL <br />N <br />a t <br />mo <br />m <br />LL <br />IL <br />Or <br />�rnCD <br />EaO <br />aLIOJnLN <br />NOt` <br />NVN <br />MZ <br />QO <br />Z <br />< <br />U❑ <br />❑0NNp <br />❑ <br />W <br />� M <br />z N <br />o <br />_ � o <br />z " � <br />d N <br />� <br />z <br />o <br />� <br />� LL <br />4 <br />t6 <br />.O <br />Vi Y <br />W a <br />� Q <br />N <br />w <br />� o <br />Ln <br />o2 <br />o <br />� <br />U C° <br />m <br />= 0 8 <br />z'.... <br />C) o <br />¢ o <br />481 <br />14 <br />o <br />� <br />w <br />CJ <br />M <br />i <br />° <br />z <br />� <br />J <br />LL. <br />m <br />zo <br />oo <br />>n <br />zzo <br />® <br />f6 <br />E <br />wj <br />oa <br />(Oo <br />O F <br />jp <br />o <br />O <br />04 <br />L <br />i <br />aoo <br />4 <br />a z <br />tw <br />-.2 <br />d <br />to <br />_ C <br />ZZ$ Z <br />°m <br />°'o <br />z' <br />ZN <br />Cn <br /><w <br />rn <br />o� <br />z <br />z <br />go <br />Q <br />�� <br />a <br />�w <br />U 3 <br />o <br />w <br />rt <br />°z <br />=3 <br />C7 <br />c <br />ok <br />a F <br />° <br />3 <br />�N <br />0 <br />= <br />> d' <br />L <br />� <br />W <br />cc <br />c� <br />\ <br />�y <br />c <br />di <br />co <br />CN <br />/1 <br />0 <br />(0 <br />T <br />O <br />�04T <br />2 <br />rl,- <br />r <br />co <br />r <br />ai <br />M <br />w <br />� N <br />M \ <br />o <br />z <br />Z <br />E 0 <br />tor, <br />N <br />r0 <br />c <br />d <br />U J <br />Q 0 <br />J <br />JOB <br />NO: <br />20-2745 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />