ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general). In a Flood Zone, all electrical equipment to be at or above DFE. <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 44" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC. <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2014 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />WEATHERPROOF DUPLEX OUTLET <br />GFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />Liph <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />13 <br />THREE-WAY SWITCH <br />24 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />+PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />0 EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />P9 PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />®2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />_ I <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />POWER CO. <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEC 14, 250.94 <br />200A INDOOR PANEL <br />CENTER <br />10 e14 copper to lights & outlets <br />NEMA DOAMP 1 <br />200 A <br />10 p12 topper to 20 amp ckts <br />10 M10.2 copper to WH <br />10 M10.3 copper to Dryer <br />METER <br />MAIN <br />O2/0 <br />or <br />4/0 SER Au200 <br />amp <br />150 amp <br />4 Bare Cu Ground <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />r- — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — - <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />t <br />I <br />L_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />UPPER FLOOR ELECTRICAL PLAN <br />SCALE:1/4'=1'-0" <br />O <br />O <br />co <br />0 <br />N <br />0 <br />N <br />r— <br />N <br />M <br />0 <br />To the best of the Engineer's knowledge, Information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 <br />Florida Building Code - <br />Residential Btft Edition. Engineer's signature and seal is only for <br />fhe structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />18 Nm <br />O O cs N <br />ci <br />J <br />eq LL <br />�-J LLLLa <br />ILL "' <br />dj W <br />LL n.waW, <br />a <br />z <br />> <br /><��, 0=o <br />19 <br />�tv8 ccmo <br />4 m <br />o&� <br />ET ao� <br />7" <br />ILW <br />IL <br />N O Q O 5 NQc�Z V <br />Z <br />H J <br />< <br />d OOP <br />W <br />0 <br />z <br />z n <br />z g <br />d N <br />Z .2 <br />o <br />■ <br />^' <br />VJ <br />LL <br />CO <br />W <br />o <br />lJ <br />< <br />V) <br />yzv) <br />� <br />W <br />U <br />c <br />¢� <br />• <br />s <br />o <br />M <br />W <br />z <br />M <br />_j <br />a <br />ao <br />< <br />Q <br />a 0 <br />E U <br />a� <br />zo <br />Z <br />i_ (6� <br />CIL <br />o E <br />oa <br />ffo <br />w <br />�z <br />Cx <br />C <br />H� <br />i�` <br />r <br />Z <br />$ <br />o <br />�z <br />W <br />i <br />Dz <br />CI <br />wLL <br />W <br />v <br />z1 < <br />0 <br />c°� 3 <br />•-c2 T <br />Z <br />> (y <br />W <br />� <br />c� <br />Z <br />�> <br />N <br />W <br />Q <br />� � <br />Q <br />� <br />in <br />Z <br />� <br />00 <br />Z O <br />N <br />= <br />CD <br />r <br />E <br />N <br />CIO <br />Z <br />E O <br />Go <br />N <br />`m <br />c <br />c <br />as <br />E <br />v _j <br />d <br />¢ o <br />JOB <br />NO: <br />20-1787 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4.1 <br />