Laserfiche WebLink
rn <br />3 <br />3 <br />m <br />rn <br />z <br />N <br />2 <br />Chi <br />0 <br />J <br />N <br />m <br />rn <br />x <br />0 <br />J <br />N <br />0 <br />3 <br />C <br />a <br />N <br />N <br />S. <br />E <br />S <br />C <br />C <br />J <br />N <br />E�. <br />0 <br />3 <br />'o <br />i <br />CL <br />z <br />I <br />Y <br />0 <br />EE <br />N <br />N <br />n <br />0 <br />a <br />N <br />N <br />N <br />ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />200A INDOOR PANEL <br />#14 copper to lights & outlets <br />NEMA 1 #12 <br />200 AMP copper to 20 amp clas <br />#10-2 copper to WH <br />#10.3 copper to Dryer <br />n0 or 4/0 SER Alu <br />200 amp <br />150 amp <br />nnect <br />POWER CO. FEED <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING #4 GROUNDING WIRE <br />TERMINATION PER WITH CODE APPROVED <br />NEC 14, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />GENERAL ELECTRICAL NOTES: Typical 150-200 Amp Electrical Riser Diagram (updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general). In a Flood Zone, all electrical equipment to be at or above DFE. <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 44" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC. <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station cc alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying With UL 2014 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FF <br />DUPLEX OUTLET ABOVE COUNTER <br />wP <br />WEATHERPROOF DUPLEX OUTLET <br />1 4:4 <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />I <br />220 VOLT OUTLET <br />WALL SWITCH <br />�3 <br />THREE-WAY SWITCH <br />�4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />F_o <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />+PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />WP GFI DISC. <br />H. <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />unnM minm on�no <br />Q <br />EXHAUST FAN <br />I <br />--- <br />j <br />WH VERIFY LOCATION <br />�fO <br />GFI <br />----- -----J <br />ELECTRICAL PANEL <br />t`� <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />RECEPT. <br />CH <br />CHIMES (OPTIONAL) <br />FOR ALARM VERIFY METER <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />SYSTEM LOCATION WITHBUILDER <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />a <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />[� <br />THERMOSTAT <br />iu J <br />ELECTRIC METER <br />ELECTRIC PANEL <br />—IIIIIIIIIIIJA <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />ELECTRICAL PLAN - ELEV-B1 <br />SCALE: %4 r=V-0" <br />0 <br />N <br />0 <br />N <br />ti <br />N <br />0 <br />To the best of the Engineers knowledge, Information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 <br />Florida Building Code - <br />Residential Bth Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />38 <br />V <br />LQ <br />M N CV N OND LL LL <br />r- <br />0 <br />M 4D <br />�d T <br />Ci <br />a <br />N N M S w h <br />uj <br />>cLLizrsaY <br />Wfa <br />moo <br />mo�tO m� �0 <br />o <br />W <br />Z <br />i Earn W o a <br />CD N o <br />Q O <br />N a m ZLL U H J <br />Z <br />❑❑❑❑ <br />W <br />0 <br />z <br />a <br />N <br />''znn <br />D Q) <br />V LL <br />�C_/� <br />W <br />� <br />V) <br />!ti <br />`— <br />v <br />a+ <br />C) <br />0 <br />Co <br />W <br />M <br />ILL. <br />H <br />` ? <br />Z <br />Z <br />> R <br />Q <br />n E <br />8 <br />�� <br />n <br />�® <br />E <br />CL <br />Vp <br />a� <br />O� <br />Z <br />N <br />i <br />Z <br />wo <br />ao <br />w Z <br />ro <br />C: <br />C <br />UgLL <br />N <br />mi <br />> Z <br />Z <br />Jm <br />O <br />�Z <br />W <br />U 3 <br />0 <br />aLL <br />�w <br />o <br />�7 <br />CID <br />° 3 <br />J <br />124 <br />> d' <br />ui <br />m <br />� <br />W <br />Q <br />a� <br />O <br />Z o <br />r <br />0''1r <br />p) <br />� <br />� <br />N <br />m <br />W <br />:3 N <br />C7 ` <br />y •- <br />o <br />Z <br />Z <br />F 0 <br />m <br />a <br />10 <br />C <br />c <br />a <br />U <br />JOB <br />NO: <br />20-0558 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />