ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />200A INDOOR PANEL <br />#14 copper to lights & outlets <br />NEMA 1 <br />200 AMP #12 copper to 20 amp ckts <br />#10-2 copper to WH <br />#10-3 copper to Dryer <br />MAIN <br />O2/0 <br />or 4/0 SER Alu <br />200 amp <br />150 amp <br />Disconnect <br />POWER CO. FEED <br />INTERSYSTEM <br />4 Bare Cu Ground <br />BONDING <br />#4 GROUNDING WIRE <br />TERMINATION PER <br />WITH CODE APPROVED <br />NEC 14, 250.94 <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />GENERAL ELECTRICAL NOTES: Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general) <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 42" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC, 406.11 <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2017 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />IQWP <br />WEATHERPROOF DUPLEX OUTLET <br />� <br />' vGFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />f`-�V <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />CS <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />1-0 <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />Ps <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />W 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT, CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G T J <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />PATIO <br />GFI <br />i CAFE <br />FAMILY ROOM <br />12-------------------------- <br />\ ROUGH -IN FbR \ <br />\ OPT. CLG. F�N/ LIGHT \ <br />PRE -WIRE <br />� I \ <br />rrm <br />I � \ <br />I � <br />I F fr—i�, .Fl, I � <br />k/ 1-1 11 \ <br />OW�R'S <br />�l1 ITE <br />ROUGH -IN FOR <br />I OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />H.B. <br />W.I.C. --\ <br />111, IF, I Le <br />- OEM _ <br />PENDANT AS <br />PER SPECS <br />- -- — J. <br />II:SINKw/: <br />D I S P <br />GFF <br />o DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE C.M <br />HOOD PER SPECS <br />'• •' <br />INN I LIGHT PREiWIR�; <br />J .- . <br />BEDROOM 2 <br />I�AM06 ff <br />0 <br />AHU <br />H. <br />I <br />ENTRY <br />I <br />WP <br />f,HGFI 1 <br />l� IRRIGATION <br />GFI @ 44" A.F.F. <br />------------ <br />W.H. <br />II 11 I <br />I I I <br />I 11 I <br />L_ —v_ J <br />I <br />1 <br />W.'GARAGE <br />GARAGE DOOR <br />\ LIGHT AS I GFI <br />VP + PE+R SPEC % <br />J I <br />1� o <br />LIJ <br />r Q J <br />I UOQ I <br />LL LU <br />U I <br />U_I _I <br />> w GFI @ 44" L — — — — — — — — — — — — <br />A A.F.F. <br />— C.M S.D ---------------- <br />\ o <br />HALL <br />S. \ \ <br />\ I EDROOM 4 <br />\ `� �12 <br />12 <br />\ <br />ROUGH -IN FOR_J�/ , ROUGH -IN FOR <br />LIPT. CLG. FANIGHT PRE -WIRER E D �OO M 3 OPT. CLG. FAN/ <br />L <br />\ LIGHT PRE -WIRE <br />VERIFY METER LOCATION <br />WITH BUILDER <br />MAIN ELECTRICAL PLAN <br />SCALE: %4"=1'-0" <br />J <br />Q O <br />0 <br />a <br />l <br />M � <br />N O <br />_ a o <br />z o <br />Q <br />J M <br /><Z N <br />M <br />nF V) z <br />o <br />� � <br />r � Y <br />fa W o <br />o <br />u, <br />o <br />Vaa <br />� � <br />c)L.0 m <br />�- m- E <br />— 0 8 <br />i <br />o <br />x <br />C) <br />c rn <br />o <br />o <br />40— <br />.N. N <br />v� N <br />w <br />Z `LU $M zo a <br />- <br />m U W W <br />'W � a m�.oA a <br />a�w� <br />ZC <br />.^ N . E N <br />��/ � E � <br />LU N Q M 4 O <br />O U U F <br />❑❑ <br />rn <br />O <br />CV <br />oo <br />0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 Florida Building Code - <br />Residential 6th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />w <br />if■ <br />M <br />M <br />ma <br />o <br />z <br />J <br />E <br />zo <br />0 <br />� <br />Z <v <br />Q <br />w <br />j <br />od <br />r6 <br />O E <br />�0 <br />O q <br />az <br />Up <br />o < <br />ZO <br />ao <br />0 <br />4 <br />az <br />w <br />L <br />C <br />_ C <br />a <br />oz <br />Y <br />U <br />.2 <br />m o <br />o <br />O u <br />z r <br />Qz <br />m <br />o <br />o <br />z <br />go <br />w <br />a <br />mw <br />U � <br />eo <br />�k <br />O <br />z <br />~ <br />�o <br />cD <br />co <br />d <br />5 <br />3 <br />c C)0 <br />�L. <br />\W <br />C <br />N <br />co <br />J <br />C) <br />Q <br />U <br />N <br />Z <br />o <br />LO <br />T <br />N 8 N <br />r <br />cj N <br />0.:m <br />3 N �; <br />Z <br />Z <br />c <br />E <br />f6 <br />c <br />it <br />U _j Q p <br />JOB <br />NO: 19-5900 <br />SCALE : AS NOTED <br />SHEET NO. <br />4.0 <br />