GENERAL STRUCTURAL NOTES: <br />CONCRETE NOTES (CONTINUED): <br />I . ALL WORK SHALL CONFORM TO THE 2023 Oth EDITION OF THE FLORIDA (INTERNATIONAL) <br />10. CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH AS FOLLOWS <br />RESIDENTIAL CODE AND APPLICABLE COUNTY CODE AMENDMENTS. STANDARDS LISTED IN <br />FOUNDATIONS & FOUNDATION WALLS 2500 PSI <br />STRUCTURAL NOTE SECTIONS REFER TO THE VERSION AND EFFECTIVE DATE IDENTIFIED IN THE <br />SLAB -ON -GRADE & CONCRETE BEAMS: 2500 PSI <br />REFERENCED STANDARDS CHAPTER IN THE GOVERNING BUILDING CODE NOTED ABOVE, <br />11. CONTRACTOR SHALL TIE REINFORCING STEEL SECURELY IN PLACE PRIOR TO PLACING <br />2� THE STRUCTURAL NOTES ARE INTENDED TO AUGMENT THE DRAWINGS. SHOULD CONFLICTS <br />CONCRETE AND PROVIDE SUFFICIENT SUPPORTS TO MAJNTAJN THEIR POSITION WITHIN <br />EXIST BETWEEN THE DRAWINGS AND THE STRUCTURAL NOTES. THE STRICTEST PROVISION <br />SPECIFIED TOLERANCES DURING ALL CONSTRUCTION ACTIVITIES. INSERTING DOWELS INTO <br />SHALL GOVERN. <br />WET CONCRETE IS NOT PERMITTED. ANCHOR RODS AND STEEL INSERTS SHALL BE SET BY <br />3. THE STRUCTURAL DRAWINGS FORM AN INTEGRAL PART OF CONTRACT DOCUMENTS, WHICH <br />TEMPLATE TO WITHIN A I1W TOLERANCE IN ANY DIRECTION WITH MINIMUM EMBEDMENT AND <br />INCLUDE ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND CIVIUSITE DRAWINGS, <br />EXACT PROJECTION INDICATED ON THE DRAWINGS, PRIOR TO PLACING CONCRETE. <br />COORDINATE THE STRUCTURAL DRAWINGS WITH THE REQUIREMENTS SHOWN IN THE OTHER <br />12. HOOKED BARS SHALL BE STANDARD 90 DEGREE HOOKS PER ACI UNLESS NOTED OTHERWISE ON <br />COMPONENTS OF THE CONTRACT DOCUMENTS. <br />THE DRAWINGS. MINIMUM LAP SPLICE SHALL BE CLASS B PER ACI 318. LOCATION OF LAP <br />4. TYPICAL DETAILS AND OTHER SECTIONS/DETAILS APPLY TO CONDITIONS THAT ARE SIMILAR TO <br />SPLICES SHALL BE AS INDICATED ON CONSTRUCTION DOCUMENTS. <br />THE CONDITIONS DESCRIBED IN THE SECTIONSIDETAILS. EVEN IF THEY ARE NOT SPECIFICALLY <br />13. DOWELS INTO FOUNDATION SHALL MATCH SIZE AND SPACING OF VERTICAL REINFORCEMENT AT <br />REFERENCED ON THE PLANS. <br />ALL COLUMNS, PIERS AND WALLS, UNLESS OTHERWISE NOTED. <br />5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS, METHODS SEQUENCES AND <br />14. CONTRACTOR SHALL OBTAIN APPROVAL PRIOR TO PLACING OPENINGS OR SLEEVES NOT SHOWN <br />PROCEDURES OF CONSTRUCTION, INCLUDING BUT NOT LIMITED TO TEMPORARY SHORING AND <br />ON THE DRAWINGS, THROUGH ANY STRUCTURAL MEMBER. <br />BRACING. <br />15. ONE OF THE FOLLOWING CONCRETE SLAB ON GRADE CRACK CONTROL METHODS SHALL BE <br />6. DO NOT SCALE STRUCTURAL DRAWINGS. IF DIMENSIONS ARE OMITTED OR NOT CLEAR, <br />USED ICONTRACTOR PREFERENCE): <br />CONTACT THE ENGINEER. <br />. CONTROL JOINTS: SHALL BE FORMED, SAWED, OR TOOLED TO A I"MINIMUM DEPTH WITHIN <br />7� CONSTRUCTION SHALL COMPLY FULLY WITH THE APPLICABLE Pq Do �WM <br />SPEED,,,4 4 ZC WT"NG FOR UNREINFORCED SLAB <br />=.s ONCRETE PLACEMENT. MAXIMUM JO_ <br />LOCAL GOVERNING CODES, CURRENT EDITION, AND ALL REOUIREIDMITIED IN'1`11 <br />CODES SHALL BE ADHERED TO AS IF THEY WERE CALLED FOR OR SHOWN ON THE DRAWINGS. <br />3-1/2- SLAB: 8 FEET D.C. EACH DIRECTION <br />THIS SHALL NOT BE CONSTRUED TO MEAN THAT REQUIREMENTS SET FORTH ON THE DRAWING <br />4" SLAB 10 FEET D.C. EACH DIRECTION <br />MAY BE MODIFIED BECAUSE THEY ARE MORE STRINGENT THAN THE CODE REQUIREMENTS OR <br />WELDED WIRE FABRIC CWW.F.) SX6-Wl AXW1.4. WELDED WIRE FABRIC SHALL BE FURNISHED IN <br />BECAUSE THEY ARE NOT SPECIFICALLY REQUIRED BY CODE. <br />FLAT SHEETS (ROLLS NOT PERMITTED) AND SHALL CONFORM TO ASTM A-1 064 AND HAVE A <br />8, THE ENGINEERS SEAL APPLIES ONLY TO THE STRUCTURAL COMPONENTS ON THIS DOCUMENT. <br />MINIMUM SIDE AND END LAP OF 8 INCHES. <br />ALL DIMENSIONS ARE TO BE VERIFIED WITH THE ARCHITECTURAL DRAWINGS. ANY DEVIATIONS <br />MICRO- OR MACRO- SYNTHETIC FIBER REINFORCEMENT <br />OR DISCREPANCIES ON THESE PLANS MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF <br />FIBER LENGTHS SHALL BE 1/2"TO 2-1/4" IN LENGTH. DOSAGE AK40UNT SHALL BE FROM 314 TO <br />THE ENGINEER OF RECORD. BACK CHARGES WILL NOT BE ACCEPTED, REGARDLESS OF FAULT, <br />3.0 POUNDS IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. SYNTHETIC <br />WITHOUT PRIOR NOTIFICATION BY BUILDER WITHIN 48-HOURS AND INVESTIGATION BY <br />FIBERS SHALL COMPLY WITH ASTM C1 116. THE MANUFACTURERISUPPLIER SHALL PROVIDE <br />FIELDSTONE. <br />CERTIFICATION OF COMPLIANCE WITH ASTM CI 116 WHEN REQUESTED BY THE BUILDING <br />9. THE TERMS'CONCRETE SCREW AND'MASONRY SCREW SHALL BE USED INTERCHANGEABLY <br />OFFICIAL. <br />WITHIN THESE DRAWINGS. CONCRETE/MASONRY SCREWS AS GENERICALLY SPECIFIED WITHIN <br />16. CONTROL JOINTS SHALL BE FURNISHED WITH A FULL-LENGTH KEYWAY CENTERED ON MEMBERS. <br />THESE DRAWINGS SHALL REFER TO ONE OF THE FOLLOWING ACCEPTED MANUFACTURER <br />WHERE THE SIZE OF KEY IS NOT SHOWN ON THE DRAWINGS, THE KEY SHALL BE 25% OF THE <br />PRODUCTS: SIMPSON STRONGTIE TITEN TURBO. GENUINE TAPCON. OR HILTI KWIK-CON 11. <br />CROSS-SECTION DIMENSION OF THE MEMBER AND MINIMUM 1-1/2 INCHES INTO THE FIRST POUR <br />10. CONTENT LINKED WITHIN OR CODES THAT MAY BE SHOWN WTH THE DRAWING SET ARE FOR <br />OF CONCRETE. <br />INFORMATIONAL PURPOSES ONLY AND THE PROFESSIONAL SEAL ON THIS DRAWING DOES NOT <br />17. PROVIDE POCKETS OR RECESSES IN CONCRETE WORK FOR COLUMNS AND BEAMS AS REQUIRED <br />APPLY TO CONTENT CONTAWINED WITHIN ANY QR CODES. <br />EVEN IF NOT SHOWN ON THE DRAWINGS. PROVIDE CONCRETE FILL AFTER BEAM ERECTION. <br />11. POST INSTALLED EPDXY ANCHORAGE GENERICALLY NOTED WITHIN THESE DRAWINGS SHALL BE <br />18. CURING OF CONCRETE SURFACES SHALL CONFORM TO ACI 308.1 "STANDARD SPECIFICATION <br />EITHER SIMPSON STRONG TIE SET-313, OR HILTI HIT-HY-150 <br />FOR CONCRETE CURING* AND ACI 308R'GUIDE TO CURING CONCRETE". <br />DESIGN CRITERIA: <br />FOUNDATION NOTES: <br />1. BUILDING RISK CATEGORY <br />2. VERTICAL LOADING: <br />ROOF TOP CHORD LIVE LOAD <br />PSF (REDUCIBLE) <br />ROOF TOP CHORD DEAD LOAD <br />=7 PSF <br />ROOF TOP CHORD DEAD LOAD (TILE) <br />15 PSF <br />ROOF BOTTOM CHORD LIVE LOAD (./ STORAGE) <br />=20 PSF <br />ROOF BOTTOM CHORD LIVE LOAD (W/o STORAGE) <br />10 PSF <br />ROOF BOTTOM CHORD DEAD LOAD_= <br />10 PSF <br />FLOOR UVE LOAD <br />=40 PSF <br />FLOOR LIVE LOAD (SLEEPING ROOMS) <br />=30 PSF <br />FLOOR DEAD LOAD <br />15 PSF <br />DECK/BALCONY LIVE LOAD <br />=40 PSF <br />NOTE TO TRUSS & I -JOIST MANUFACTURERS - ROOF & FLOORSYSTEM DELEGATED DESIGN <br />SMALL CONFORM TO THE FOLLOWING DESIGN STANDARDS: <br />LOCATION <br />r TOTAL <br />EFLECTION <br />ROOF TRUSSES <br />j LJ240 <br />L/240 <br />1 . <br />�1/2- <br />DOR JOISTSITRUSS <br />i LJ360 <br />i I14An <br />NOTES: <br />1. MAXIMUM TOTAL LOAD DIFFERENTIAL DEFLECTION BETWEEN ADJACENT PARALLEL <br />MEMBERS SHALL BE 5Ar <br />2. ANY MEMBER SUPPORTING BRICK/MASONRY SHALL BE LIMITED TO A TOTAL LOAD <br />DEFLECTION OF LJ600 <br />3. FIELDSTONE AE CANNOT BE HELD RESPONSIBLE FOR ANY STRUCTURAL ISSUES RELATED <br />TO ANY BUILDING COMPONENT IF COMPONENT SHOP DRAWINGS ARE NOT SUBMITTED TO <br />FAE FOR REVIEW PRIOR TO FABRICATION, DELIVERY, OR INSTALLATION <br />3. LATERAL LOADING <br />WIND CRITERIA: <br />BASIC WIND SPEED 140 MPH <br />EXPOSURE CATEGORY -C <br />INTERNAL PRESSURE COEFFICIENT 0. 18 (ENCLOSED) <br />SEISMIC CRITERIA <br />SITE CLASS <br />SEISMIC DESIGN CATEGORY <br />4 EARTH PRESSURE LOADING: <br />ALLOWABLE SOIL BEARING CAPACITY <br />TOTAL LOADS (INCLUDING V41NO & SEISMIC) =2000 PSF <br />LATERAL EARTH EQUIVALENT FLUID PRESSURE <br />WALLS UNBRACED AT TOP =40 PCF <br />WALL BRACED AT TOP =55 PCF <br />5 GUARDRAIL/HANDRAIL LOADING <br />ALL GUARDRAIL/HANDRAILS SHALL MEET 20-0 Les (MINIMUM) CONCENTRATED FORCE APPL11" <br />IN ANY DIRECTION. IN -FILL COMPONENTS OF GUARDRAJL SHALL MEET 50 PSF. THESE LOADS <br />ARE TO BE EVALUATED INDEPENDENTLY AND ARE NOT TO ACT CONCURRENTLY WITH ANY <br />OTHER LIVE LOAD. DEFLECTION OF GUARDRAIL SHALL MEET THE CRITERIA SET FORTH BY THE <br />INTERNATIONAL CODE COUNCIL EVALUATION SERVICES (ICC-ES) AC 273 - 'ACCEPTANCE <br />CRITERIA FOR PLANDRAILS AND GUARDS! <br />CONCRETE NOTES: <br />I . STRUCTURAL CONCRETE HAS BEEN DESIGNED IN ACCORDANCE PER ACI 332'RESIDENTIAL <br />CODE REQUIREMENTS FOR STRUCTURAL CONCRETE'. <br />2 CONCRETE PRODUCTION AND PLACEMENT SHALL CONFORM TO THE REQUIREMENTS OF ACI 332 <br />"RESIDENTIAL CODE REQUIREMENTS FOR STRUCTURAL CONCRETE' EXCEPT AS MODIFIED BY <br />STRUCTURAL REQUIREMENTS NOTED ON THE DRAWINGS. <br />3. CEMENT SHALL CONFORM TO ASTM C1 SO'SPECIFICATION FOR PORTLAND CEMENT." CONCRETE <br />SHALL BE NORMAL WEIGHT, UNLESS INDICATED OTHERWISE. <br />4. CONCRETE AGGREGATES SMALL CONFORM TO ASTM C33'SPECiFICATION FOR CONCRETE <br />AGGREGATES.' <br />5� REINFORCING SHALL CONFORM TO ASTM A-615 GRADE 60. <br />& REINFORCEMENT SMALL BE FABRICATED AND ERECTED ACCORDING TO THE ACI STANDARDS: <br />'DETAILS AND DETAILING OF CONCRETE REINFORCEMENr, ACI 315 - ANDWANUAL OF <br />ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE STRUCTURES', ACi 315R. <br />7. REINFORCING STEEL AND WELDED WRE FABRIC SHALL BE PLACED WITH MINIMUM CONCRETE <br />COVER AND TOLERANCES AS FOLLOWS: <br />SLAB4WORADE. WITHIN UPPER 2/3 OF SLAB AND 3/4' MINIMUM COVER AT INTERIOR <br />CONDITIONS; 1-1/2'MINIMUM COVER AT EXTERIOR CONDITIONS <br />CONCRETE (FOUNDATIM AGAINST EAffrH: 3' <br />FORMED CONCRIETE.' 1-1/2- (#5 REBAR OR SMALLER) 2- (#6 REBAR OR LARGER) <br />TOLERANCE +/- 3/8" <br />8. REINFORCING STEEL SHALL NOT BE CUT, BENT OR STRAIGHTENED IN THE FIELD UNLESS <br />APPROVED BY THE STRUCTURAL ENGINEER OR AS INDICATED ON THE DRAWINGS. <br />9 WELDING OF REINFORCING STEEL IS PROHIBITED UNLESS SPECIFICALLY DETAILED. WELDING <br />WHERE DETAILED SHALL CONFORM TO AWS DIA SPECIFICATION. <br />1. CONTRACTOR SHALL VERIFY ALL CONDITIONS, INCLUDING UNDERGROUND UTILITIES AND FIELD <br />MEASUREMENTS AT JOB SITE AND REPORT ANY DISCREPANCIES TO OWNERS REPRESENTATIVE. <br />2. TOP OF SPREAD FOOTING ELEVATIONS NOTED ON PLAN ARE MINIMUM ELEVATIONS. IN ALL CASES <br />FOOTINGS ARE TO BEAR ON UNDISTURBED NATURAL SOILS OR ENGINEERED FILL HAVING A <br />MINIMUM NET ALLOWABLE BEARING CAPACITY OF 2000 PSF. <br />3. SIDES OF FOUNDATIONS SHALL BE FORMED UNLESS CONDITIONS PERMIT EARTH FORMING. <br />FOUNDATIONS POURED AGAINST THE EARTH REQUIRED THE FOLLOWING PRECAUTIONS: SLOPE <br />SIDES OF EXCAVATIONS AS APPROVED BY GEOTECHNICAL ENGINEER AND CLEAN UP SLOUGHING <br />BEFORE AND DURING CONCRETE PLACEMENT. PROVIDE POLYETHYLENE VAPOR RETARDER <br />COMPLYING WITH GOVERNING BUILDING CODE LISTED ON THIS SHEET AGAINST SOILS WHERE <br />CONCRETE IS TO BE PLACED; LAP ALL EDGES 6 INCH (MINIMUM) AND SEAL WITH ADHESIVE. <br />4. WHERE FOOTING STEPS ARE NECESSARY, THEY SHALL BE NO STEEPER THAN ONE VERTICAL TO <br />TWO HORIZONTAL U.N.O. <br />5. FOOTINGS SHALL BE CENTERED UNDER COLUMNS AND WALLS UNLESS SPECIFICALLY DETAILED <br />OTHERWISE ON THE DRAWINGS. <br />6, NO FOOTINGS OR SLABS SHALL BE PLACED ON OR AGAINST SUB -GRADE CONTAINING FREE <br />WATER, FROST OR ICE. SHOULD WATER OR FROST. HOWEVER SLIGHT, ENTER A FOOTING <br />EXCAVATION AFTER SUB -GRADE APPROVAL. THE SUB -GRADE SHALL BE RE -INSPECTED BY THE <br />GEOTECHNICAL ENGINEER/ TESTING LABORATORY AFTER REMOVAL OF WATER OR FROST. <br />7. CONTRACTOR SHALL FURNISH ALL REQUIRED DE -WATERING EQUIPMENT TO MAINTAIN A DRY <br />EXCAVATION UNTIL I&ACKFILL IS COMPLETE. <br />8. A GEOTECHNICAL ENGINEER REGISTERED IN THE STATE OF WORK PERFORMED SHALL INSPECT <br />THE CONDITION AND ASSURE THE ADEQUACY OF ALL SITE PREPARATION, SUBGRADES. FILLS, <br />BACKFILLS BEFORE PLACEMENT OF FOUNDATIONS, FOOTINGS, SLABS AND WALLS. HE SHALL <br />SUBMIT REPORT TO THE ARCHITECTIENGINEER DESCRIBING HIS INVESTIGATIONS OF ANY <br />NON -CONFORMING WORK <br />BACKFILLING: <br />I . DO NOT PLACE BACKFILL AGAINST FOUNDATION WALLS - DESIGNED AS SUPPORTED AT TOP AND <br />BOTTOM - UNTIL BASEMENT LEVEL AND FIRST FLOOR SYSTEM ARE IN PLACE. SHORE AND/OR <br />BRACE WALLS AS REQUIRED IF BACKFILLING OPERATIONS ARE TO BE CARRIED OUT PRIOR TO <br />PLACEMENT OF FLOOR SYSTEM. <br />2. WHERE BACKFILL IS TO BE PLACED ON BOTH SIDES OF FOUNDATION WALLS, PROVIDE A <br />BALANCED BACKFILL AGAINST FOUNDATION WALLS TO ELIMINATE LATERAL LOAD EFFECTS, OR <br />PROVIDE NECESSARY TEMPORARY LATERAL SUPPORT TO THE TOP OF THE WALL UNTIL <br />PERMANENT SUPPORT IS INSTALLED. <br />3. BACKFILL MATERIAL SHALL CONSIST OF CLEAN, WELL GRADE GRANULAR SOILS, FREE OF <br />ORGANIC MATERIAL AND BE COMPACTED TO 95% OF MAXIMUM DENSITY, AS DETERMINED BY <br />THE MODIFIED PROCTOR METHOD (ASTM DI 557), IN LIFTS NOT EXCEEDING 8 INCHES. <br />MASONRY NOTES: <br />I � CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH ACI 530,'BUILDING CODE <br />REQUIREMENTS FOR MASONRY STRUCTURES"AND SHALL BE CONSTRUCTED IN ACCORDANCE <br />NTH ACI 530.1, -SPECIFICATIONS FOR MASONRY STRUCTURES.- <br />2. CONCRETE MASONRY SHALL CONFORM TO ASTM C90 AND HAVE A MINIMUM COMPRESSIVE <br />STRENGTH Prn = 1,500 PSI U.O.N. MASONRY SHALL HAVE A TEXTURE SUITABLE FOR STUCCO <br />APPLICATIONS WHERE ARCHITECTURAL DRAWINGS INDICATE STUCCO APPLICATION. <br />3. CONCRETE MASONRY UNITS SHALL BE LAID IN RUNNING BOND. <br />4. MORTAR FOR ALL MASONRY SHALL CONFORM TO ASTM C270 WITH MINIMUM COMPRESSIVE <br />STRENGTH OF 2,000 PSI. MORTAR BELOW GRADE SHALL BE TYPE M. ELSEWHERE MORTAR MAY <br />BE EITHER TYPE M OR S UNLESS SPECIFICALLY INDICATED OTHERWISE. USE EITHER PORTLAND <br />CEMENT/LIME OR MASONRY CEMENT FOR MORTAR. <br />5. GROUT SMALL CONFORM TO ASTM C476 WTH MINIMUM 28-DAY COMPRESSIVE STRENGTH OF <br />2,500 PSI. <br />6. STEEL BAR REINFORCEMENT SHALL CONFORM TO ASTM A615. GRADE 60. <br />7. VERTICAL CELLS CONTAINING REINFORCING AND GROUT SHALL FORM A CONTINUOUS CAVITY, <br />FREE OF MORTAR DROPPINGS. <br />8. VERTICAL CMU WALL REINFORCING SHALL BE AS NOTED ON THE DRAWINGS. DOWELS TO <br />CONCRETE FOUNDATION TO MATCH SIZE AND SPACING OF VERTICAL REINFORCING UNLESS <br />NOTED OTHERWISE. REINFORCE CMU CORE AT CORNERS, EACH SIDE OF CONTROL JOINTS AND <br />EACH SIDE OF WALL OPENINGS WITH (1)-#5 CONTINUOUS VERTICAL REINFORCING BARS.. <br />9. HORIZONTAL BOND BEAM AND VERTICAL REINFORCING SHALL BE CONTINUOUS U.O.N. LAP <br />SPLICE REINFORCING PER THE SCHEDULE OR USE MECHANICAL SPLICES ADEQUATE FOR 125% <br />OF SPECIFIED YIELD STRENGTH OF THE BAR. LAP VERTICAL REINFORCEMENT WITH M1141- <br />DOWELS OF SAME SIZE AND SPACING THAT HAVE BEEN PREVIOUSLY INSTALLED IN THE <br />FOUNDATIONS. DOWEL EMBEDMENT IN CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF <br />THE CONCRETE NOTES. <br />BAR SIZE <br />LAP SPLICE LENGTH <br />BEND DIAMETER <br />ACI HOOK <br />#4 <br />20, <br />3' <br />io, <br />#5 <br />25' <br />3-3/4' <br />10, <br />#6 <br />34' <br />4-1/2' <br />"ij <br />MASONRY NOTES (CONTINUED): <br />10. REINFORCING BARS SHALL BE HELD IN POSITION BY WIRE TIES OR OTHER APPROVED MEANS TO <br />ENSURE DESIGN LOCATION AND LAP. PLACE BARS AND LAP PRIOR TO GROUTING. <br />11. GROUTING OF MASONRY WALLS SHALL CONFORM TO RECOMMENDED PROCEDURE FOR'LOW <br />LIFT GROUTING'OR *HIGH LIFT GROUTING"AS OUTLINED IN THE NCMA-TEK 3-2A - GROUTING <br />FOR CONCRETE MASONRY WALLS AND ACI SWASCE 5 SPECIFICATION FOR MASONRY <br />STRUCTURES. GROUT LIFTS SHALL NOT EXCEED 5 FEET WITHOUT MECHANICALLY <br />CONSOLIDATED (VIBRATED) GROUT POURS. <br />12. LIFTS OF GROUT SHALL BE KEYED 4 INCHES INTO THE PREVIOUS COURSE OF MASONRY BELOW. <br />13. MASONRY BELOW GRADE SHALL BE GROUTED SOLID. <br />14. CONTRACTOR SHALL BRACE MASONRY WALLS TO RESIST WIND LOADS UNTIL FLOORS AND <br />ROOFS ARE IN PLACE. AND THE MASONRY HAS REACHED 75% OF THE REQUIRED STRENGTH rm. <br />BRACING SHALL BE PROVIDED IN ACCORDANCE WITH OSHA - CONSTRUCTION SAFETY <br />STANDARDS FOR MASONRY WALL BRACING AND NCMA TEK 34B - "BRACING CONCRETE <br />MASONRY WALLS DURING CONSTRUCTION.' <br />WOOD FRAMING NOTES: <br />1 . STRUCTURAL SAWN LUMBER, STRUCTURAL COMPOSITE LUMBER, AND CONNECTIONS HAVE <br />BEEN DESIGNED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATION FOR WOOD <br />CONSTRUCTION.- (NDS) <br />2. PLYWOOD HAS BEEN DESIGNED IN ACCORDANCE WITH'PANEL DESIGN SPECIFICAnON."AND <br />SHALL CONFORM TO 'VOLUNTARY PRODUCT STANDARD PSI CONSTRUCTION AND INDUSTRIAL <br />PLYWOOD., <br />3. ORIENTED STRAND BOARD (OSB) SHALL CONFORM TO -VOLUNTARY PRODUCT STANDARD PS2 <br />PERFORMANCE STANDARD FOR WOOD -BASED STRUCTURAL -LISE PANELS'. <br />4. ALL BEAMS AND HEADERS SHALL BE (2)-PLY U.N.O. <br />5. WOOD SILL PLATES AND WOOD WALLS SUPPORTED ON CONTINUOUS CONCRETE OR MASONRY <br />SHALL BE ANCHORED WITH 1/2"DLAMETER CAST -IN -PLACE ANCHOR BOLTS WITH 7- EMBEDMENT, <br />4- (MINIMUM) AND 12- (MAXIMUM) FROM END OF SILL PLATE(S), LOCATED WITHIN THE MIDDLE <br />THIRD OF THE SILL PLATE, WITH NUT AND 3"x3".0.229" WASHERS AT THE ANCHOR SPACING <br />BELOW: <br />MAXIMUM ANCHOR BOLT SPACING= T-O"O.C. <br />REFER TO "PRE -APPROVED FIELD REPAIR NOTES" SECTION FOR ALTERNATE ANCHORAGE <br />APPROVALS. FOR OTHER ANCHORS NOT LISTED, SUBMIT TO ENGINEER OR RECORD FOR <br />REVIEW. <br />6. ALL LUMBER IN CONTACT WITH EARTH, CONCRETE, OR MASONRY - AND WOOD BEAMS <br />POCKETING INTO CONCRETE OR MASONRY WALLS HAVING CLEARANCES LESS THAN 1/2'ON <br />TOP. SIDES, AND END(S) SHALL BE PRESSURE TREATED OR SEPARATED WITH AN IMPERVIOUS <br />MOISTURE BARRIER. <br />7. STRUCTURAL SAWN LUMBER SHALL BE SPRUCE -PINE -FIR NO.1 /NO.2 OR BETTER U.N.O. WITH <br />BASE DESIGN VALUES: <br />F.= 875 PSI F, = 425 PSI FT = 450 PSI F�= 1150 PSI IF,= 135 PSI E= 1400 KSI <br />WITH THE MOISTURE CONTENT OF THE WOOD IN SERVICE WILL NOT EXCEED 19%. <br />& BEARING AND EXTERIOR WALL STUDS SHALL BE CAPPED WITH DOUBLE (2X) TOP PLATES <br />INSTALLED TO PROVIDE OVERLAPPING AT CORNERS AND AT INTERSECTIONS. END JOINTS IN <br />DOUBLE (2X) TOP PLATES SHALL BE OFFSET AT LEAST 24 INCHES AND SHALL BE NAILED WITH <br />NOT LESS THAN (8)-0.162-.2-1/2- FACE NAILS ON EACH SIDE THE JOINT. DOUBLE (2X) TOP PLATES <br />OF EXTERIOR WALLS AND INTERIOR LOAD BEARING WALLS SHOWN ON DRAWINGS SHALL BE <br />SOUTHERN YELLOW PINE NO.2 OR BETTER WITH BASE DESIGN VALUES: <br />F,- 110OPSI F,= 565 PSI FT= 675 PSI FC= 145OPSI IF,= 175PSI E= 140OKSI <br />WITH THE MOISTURE CONTENT OF THE WOOD IN SERVICE WILL NOT EXCEED 19%. <br />9. STRUCTURAL COMPOSITE LUMBER SHALL CONFORM TO ASTM D 5456 WITH THE FOLLOWING <br />ALLOWABLE DESIGN STRESSES <br />MICROULAM LVL PARALLAM PSL TIMBERSTRAND LSL <br />E = 2000 KSI E = 1800 KSI E 1300 KSI <br />F� = 26M PSI F� = 2400 PSI F� 1700 PSI <br />I') - 'BOOZER BEAM 2.IE' ARE AN ACCEPTED ALTERNATE TO PSL COLUMNS SPECIFIED <br />ON PLANS PROVIDED THE'BOOZER BEAM 2.1 CIS OF EQUAL OR GREATER SECTION <br />DIMENSION TO THE PSL COLUMN AND OF EQUAL OR LESSER HEIGHT <br />10. FLOOR SHEATHING SHALL BE 23/32 INCH. APA RATED SHEATHING, 48124 MIN., EXPOSURE 1. <br />INSTALL WITH THE LONG DIMENSION OR STRENGTH AXIS OF THE PANEL ACROSS SUPPORTS <br />AND WITH PANEL CONTINUOUS OVER TWO OR MORE SPANS. PANEL EDGES SHALL BE <br />TONGUE -AND -GROOVE. FLOOR SHEATHING SHALL BE GLUED AND NAILED TO SUPPORTING <br />MEMBERS. ADHESIVE SHALL MEET APA SPECIFICATION AFG.01, APPLIED IN ACCORDANCE WITH <br />THE MANUFACTURERS RECOMMENDATIONS. PROVIDE 0.1 31"x2-1/2" COMMON NAILS AT 6 INCH <br />O.0 ALONG SUPPORTED PANEL EDGES AND 12 INCH O.0 AT INTERMEDIATE SUPPORTS. <br />11. FOR INTERIOR WALL HEADERS PROVIDE (I)-2X JACK STUD AND (I)-2X KING STUD U.N.O. ON <br />DRAWINGS. <br />12. FOR EXTERIOR WALL HEADERS PROVIDE (I)-2x JACK STUD AND (l)-2x KING STUD, MINIMUM, <br />REFER TO CHART BELOW U.N.0 ON DRAWINGS: <br />WINDSPEEDOF <br />� = 140 EXP. C <br />WALL HEIGHT <br />8FT <br />9FT <br />I DFT <br />STUD <br />SIZE <br />HEADER SPAN <br />(FT) <br />4 <br />1J/1K <br />IJ/1K <br />1J/1K <br />6 <br />1J/1K <br />IJ/1K <br />I J/2K <br />IJ/IK <br />I J/2K <br />1 J/3K <br />10 <br />1 J/2K <br />1J/2 <br />4 <br />20 <br />12 <br />1 J/2K <br />1 J/3K <br />1 J/4K <br />14 <br />1 J/2K <br />1J/4K <br />ENG <br />-- <br />-1J/3K <br />1 J/4K <br />EN1.7 <br />- _3 <br />1J/3K <br />-EING <br />ENG <br />WINDSPEED OF <br />140 EXP. C <br />FWALL HEIGHT <br />BFT <br />9FT <br />10FT <br />STUD <br />SIZE <br />HEADER SPAN <br />(FT) <br />4 <br />1J/1K <br />1J/1K <br />IJ/IK <br />6 <br />IJ/1K <br />1J/IK <br />IJ/IK <br />8 <br />IJ/IK <br />1J/IK <br />IJ/1K <br />10 <br />IJ/1K <br />IJ/IK <br />1J/IK <br />2x6 <br />12 <br />IJ/IK <br />IJ/IK <br />1J/1K <br />14 <br />IJ/IK <br />IJJiK <br />IJ/IK <br />16 <br />1 <br />18 <br />1J/IK <br />IJ/1K <br />IJ/IK <br />13. WALLS SHOWN ON THE FRAMING PLANS ARE LOAD BEARING WALLS; WALLS NOT SHOWN ON <br />STRUCTURAL FRAMING PLANS ARE INTERIOR NON -LOADING BEARING PARTITION WALLS. <br />14. LOAD BEARING WALLS SHALL BE CONSTRUCTED WITH 2X STUDS AT 16"O.C. MAXIMUM U.N.O. <br />NON -LOAD BEARING PARTITION WALLS SHALL BE CONSTRUCTED WITH 2X OR METAL STUDS (18 <br />Gk MIN�) @ 24- O.C. MAXIMUM. <br />15. STUD COLUMNS UNDER LOAD BEARING POINTS OF GIRDERS/BEAMS SHALL MATCH THE <br />GIRDERIBEAM PLY COUNT WITHIN 1/2' TOLERANCE (2-PLY STUD COLUMN MINIMUM). SOLID <br />BLOCK ALL GIRDER/BEAMS THRU FLOOR SYSTEMS AND TO THE FOUNDATION. <br />16. WHEN NOT SHOWN ON DRAWINGS OR DETAILS, THE NAILING SCHEDULE FOR WOOD FRAMING <br />ELEMENTS SHALL COMPLY WITH THE IRC TABLE R602.3(l). <br />17. FLOOR SYSTEMS ARE DESIGNED BY THE TRUSS AND/OR WOOD I- JOIST MANUFACTURERS <br />DELEGATED ENGINEER AND BE IN CONFORMANCE WITH THE LOADS & DEFLECTIONS IDENTIFIED <br />IN THE DESIGN CRITERIA NOTES SECTION. INSTALL PER MANUFACTURERS RECOMMENDATIONS, <br />NOTES, AND DETAILS. FLOOR FRAMING CONCEPT LAYOUTS SHOWN WITHIN THE DRAWINGS ARE <br />FOR ILLUSTRATIVE PURPOSES ONLY TO DEPICT FLOOR SYSTEM -TO -WALL CONNECTIONS, <br />CHANGES TO THE CONCEPTUAL FLOOR LAYOUT SHOWN IS NOT PERMITTED WITHOUT A LETTER <br />AND REVIEW FROM THE ENGINEER OF RECORD. PREFABRICATED WOOD I -JOIST SHALL <br />CONFORM TO ASTM D 5055. <br />JURISDICTION SPECIFIC NOTES: <br />I � FOR PARTIALLY ENCLOSED AREAS, INCLUDING BUT NOT LIMITED TO LANAIS, PORCHES, AND <br />BALCONIES A 1/7 (MINIMUM) EXTERIOR GRADE SOFFIT BOARD WITH A CEMENTiTIOUS <br />KNOCKDOWN FINISH IS ACCEPTABLE PROVIDED THAT IT IS PAINTED MEETING THE <br />REQUIREMENTS OF ASTM C932 TO GIVE THE CEILING WATER RESISTANCE. THE SOFFIT BOARD <br />PRODUCT SMALL BE ATTACHED PER MANUFACTURER SPECIFICATIONS TO BE IN COMPLIANCE <br />NTH R703.1. <br />2. THE SOFFIT DESIGN PRESSURE IS AS NOTED IN THESE DOCUMENTS. WTH KAYCAN VINYL SOFFIT <br />INSTALLED IN ACCORDANCE WTH MANUFACTURERS REOUIRMENTS AND ICC-ES EVALUATION <br />REPORT ESR-1495 THE SOFFIT WILL COMPLY WITH R703.1. <br />PRE-ENGINEERED ROOF TRUSS NOTES: <br />I . ROOF TRUSS SHOWN ON STRUCTURAL DRAWINGS IN CONCEPTUAL ONLY TO ILLUSTRATE <br />TRUSS -TO WALL CONNECTIONS AND DOES NOT SERVE AS A ROOF TRUSS DESIGN. ROOF <br />TRUSSES SHALL BE DESIGNED AND MANUFACTURED IN CONFORMANCE FOR THE INDICATED <br />LOADS NTH ANSI/TPI I "NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD <br />TRUSS CONSTRUCTION.' FINAL PRE-ENGINEERED ROOF TRUSS FRAMING LAYOUT AND DESIGNS <br />TO BE BY ROOF MANUFACTURERS DELEGATED ENGINEER <br />2. ROOF TRUSSES SHALL BE DESIGNED FOR THE SUPERIMPOSED LOADS IDENTIFIED IN THE <br />DESIGN CRITERIA NOTES SECTION. <br />3. THIS PLAN IS DEVELOPED FROM THE REVIEW OF MASTER TRUSS FILES. ANY LOT THAT DEVIATES <br />FROM THE MASTER TRUSS FILE ON RECORD,OR FOR PLANS FIELDSTONE AE IS NOT <br />CONTRACTED TO PERFORM TRUSS REVIEW ON, THE CONTRACTOR IS RESPONSIBLE TO ASSURE <br />THE DIRECT COMPLIANCE OF TRUSS MANUFACTURER LAYOUT TO THESE DRAWINGS & VERIFY <br />ALL TRUSS CONNECTORS ARE SUFFICIENT TO WITHSTAND THE UPLIFT/LATERAL LOADS IMPOSED <br />4� TRUSS MANUFACTURER SHALL PROVIDE HANGERS AND CONNECTIONS ADEQUATE FOR LOADS <br />AT ALL TRUSS -TO -TRUSS. TRUSS -TO -BEAM, AND BEAM -TO -TRUSS CONNECTIONS. <br />5� REFER TO ARCHITECTURAL DRAWINGS FOR TRUSS SHAPE, OVERHANG, DIMENSIONS, SLOPES, <br />SPANS, DRAINAGE, BEARING WALL HEIGHTS, ETC. <br />6. THE POSITIONS, WEIGHTS, AND METHODS OF ATTACHMENTS OF ALL MECHANICAL UNITS, <br />ELECTRICAL FIXTURES, PLUMBING. FIRE SPRINKLERS, ETC SHALL BE INCLUDED IN THE DESIGN <br />OF THE TRUSSES BY THE TRUSS MANUFACTURER. SEE ARCHITECTURAL DRAWINGS FOR ATTIC <br />ACCESS SIZE AND LOCATIONS. <br />7. SUPERIMPOSED LOADS FROM SECONDARY FRAMING (I.E. SOFFITS, PARAPETS, VALLEY FRAMING, <br />UPPER TRUSSES. ETC) SMALL BE INCLUDED IN THE DESIGN OF SUPPORTING TRUSSES. <br />8 CONTRACTOR TO PROVIDE TRUSS BRACING PER BCSI-B3 IN ADDITION TO PERMANENT BRACING <br />SHOWN ON THE TRUSS DESIGN PROVIDED BY THE DELEGATED TRUSS ENGINEER. <br />PRE -APPROVED FIELD REPAIR NOTES: <br />I MISPLACED DOWEL REPAIR: THIS NOTE DESCRIBES ALTERNATES TO MITIGATE THE CASTING OF <br />REBAR VERTICAL REINFORCEMENT AT AN INCORRECT LOCATION. <br />IF THE WALL HAS NOT BEEN BUILT: DRILL AND EPDXY #5 REBAR (36" LG.) INTO THE THICKENED <br />EDGE OF SLAB AT THE CORRECT LOCATION. AS WALL IN CONSTRUCTED, LAP REBAR IN <br />ACCORDANCE WITH MASONRY NOTES LAP SCHEDULE, PLACING A HOOKED BAR WITH 12' LAP AT <br />THE TOP OF WALL WITH THE CONTINUOUS REBAR IN THE TIE BEAM/BOND BEAM. COMPLETE <br />GROUTING OF WALL. <br />IF THE WALL HAS ALREADY BEEN BUILT: PRIOR TO GROUT PLACEMENT, OPEN THE WALL AT THE <br />CORRECT LOCATION APPROXIMATELY 16" (H) x 4" (" AT FLOOR LEVEL. DRILL AND EPDXY #5 <br />REBAR (32- LG.) INTO THE THICKENED EDGE OF SLAB. LAP VERTICAL REINFORCEMENT IN <br />ACCORDA14CE WITH MASONRY NOTES LAP SCHEDULE, PLACING A HOOKED BAR WTH 12"LAP AT <br />THE TOP OF WALL WITH THE CONTINUOUS REBAR IN THE TIE BEAM/BOND BEAM. COMPLETE <br />GROUTING OF WALL. <br />2. MISSING/MISPLACED ANCHOR BOLT: ALTERNATE SILL PLATE ANCHORAGE SOLUTIONS <br />INTO CONCRETE: <br />A 1/2'x6" TITEN HD WITH 1-3/4" MINIMUM EDGE DISTANCE AND 6"MINIMUM END DISTANCE IS A <br />DIRECT 1: 1 REPLACEMENT FOR A 1/2" DIAMETER ANCHOR BOLT WTH 7" EMBEDMENT INTO <br />CONCRETE. <br />A 1/2"THREADED ROD SET-3G EPDXY 7" EMBEDMENT NTH "/4"MINIMUM EDGE DISTANCE AND <br />7-1/2" MINIMUM END DISTANCE IS A DIRECT 11 REPLACEMENT FOR A 1/2" DIAMETER ANCHOR <br />BOLT WITH 7' EMBEDMENT INTO CONCRETE. <br />INTO GROUT FILLED MASONRY (GFCMtJ): <br />A 1/2"x6"TITEN HD NTH 1-3/4" MINIMUM EDGE DISTANCE AND 8"MINIMUM END DISTANCE AT 4'-B" <br />O.C. REPLACES A 1/2- DIAMETER ANCHOR BOLT WITH 7- EMBEDMENT AT 9-0- O.C.; LIKEWISE A <br />1/2'x6* TITEN HD WITH 1-3/4" MINIMUM EDGE DISTANCE AND 8' MINIMUM END DISTANCE AT 2-8' <br />O.C. REPLACES A 1/2- DIAMETER ANCHOR BOLT WITH 7- EMBEDMENT AT 4'-0- O.C., <br />3 SIMPSON MASA SILL ANCHORS MAYBE USED AS AN ALTERNATE TO THE ANCHOR BOLTS AND <br />SPACING NOTED HERE -IN ACCORDING TO THE FOLLOWING TABLE <br />BASIC WIND <br />SPEED (MPH) <br />MAXIMUM <br />SPACING <br />� 1 <br />140 <br />ISO <br />V-3" <br />NOTES: <br />1. MASA SPACING BASED ON NO MORE THAN ONE IN THREE INSTALLED WITH ONE LEG <br />INSTALLED VERTICALLY ATTACHED TO STUD <br />4 MISSfNGIMISPLACED TRUSS STRAP ANCHOR REFER TO "MISSED TRUSS STRAP REPAIR" DETAIL <br />WITHIN DRAWINGS. <br />FOR MISLOCATED TRUSS ANCHORS WHICH ARE GREATER THAN 1/8"BUT LESS THAN 1-1/2"FROM <br />THE FACE OF THE TRUSS, A SHIM SHALL BE PROVIDED AND NAIL LENGTH INCREASED TO <br />PENETRATE THROUGH BOTH PLYS OF MATERIAL (I.E. 3- L& NALS). WHEN GAP IS GREATER THAN <br />1-1/2", INSTALL NEW ANCHORS. <br />5 MASONRY WALL OVERHANGING SLAB <br />BLOM OVERIAAW REPAIR <br />� 5/8' NO REPAIR REO'D <br />5/8" < OVERHANG < 1-1/2' GROUT SOLID BOTTOM 3 COURSES OF AFFECTED WALL LENGTH <br />�1-1 12" CONTACT ENGINEER OF RECORD FOR REPAIR <br />6. NOTCHED TOP PLATES & STUDS REQUIRING REPAIR <br />AT STUDS: STRUCTURAL REPAIR IS REQUIRED AT STUDS WHEN A STUD IS NOTCHED TO A DEPTH <br />GREATER THAN 25% OF THE WIDTH IN BEARING WALLS, OR 40% IN NON -LOAD BEARING WALLS; <br />OR WHEN A HOLE IS DRILLED/BORED TO A DIAMETER EXCEEDING 40% OF THE STUD WIDTH IN <br />BEARING WALLS, OR 60% OF THE STUD WIDTH IN NON -BEARING WALLS. IF THE MAXIMUM <br />HOLE/NOTCH SPECIFICATIONS ARE EXCEEDED THEN A STUD SHOE MUST BE INSTALLED. STUD <br />SHOE REPAIRS ARE AS FOLLOWS: FOR 2X STUD USE HSS2-SDS1.5 WITH (I 2).1/4'XI -1/2"SDS <br />SCREWS. FOR MULTI -PLY 2X STUDS USE HSS2-'#--SDS3 WITH (12)-1/4-X3- SDS SCREWS, WHERE <br />"#'CORRESPONDS TO THE NUMBER OF STUDS IN THE MULTI -PLY. <br />ATTOP PLATE& A HOLE, CUT, OR NOTCH THAT IS GREATER THAN 50% OF THE PLATE WIDTH IS <br />REMOVED FOR PIPING (EXCEPT WHEN THE SIDE OF THE WALL WITH THE NOTCH OR CUT IS <br />COVERED BY WOOD STRUCTURAL PANEL SHEATHING), OR THE PLATES ARE CUT THROUGH. THE <br />REQUIRED REPAIR IS A GALVANIZED 16-GAUGE METAL TIE THAT IS AT LEAST i-1/2'WIDE AND <br />MUST BE FASTENED WITH (8)-16D NAILS ON EACH SIDE OF THE OPENING. <br />ORD Fieldstone <br />C.O.A.# ARCHITECURE: <br />AA26002802 <br />C.O.E.# ENGINEERING: N <br />29349 <br />E3 IBRAHEM ELAYEB, PE =.a <br />P.E.# 91476 <br />E BENJAMIN NIESE, PE --0 EO <br />oo <br />P.E.# 86025 <br />05/15/2024 MAL. <br />jjj%�\ <br />DATE 111111 III\\\ <br />g - <br />1-92 <br />Michigan <br />3400 Auburn Rd <br />Suite 200 <br />Auburn Hills, Ml 48326 <br />+1 248,622,4035 <br />Florida <br />12906 Tampa Oaks Blvd. <br />Suite 150 <br />Tampa, FIL 33637 <br />+1 813.466.3310 <br />www.fieldsioneae.com <br />C0 I <br />0 <br />z <br />0 LU <br />-zm <br />F C,) <br />Uj LU 0 <br />_j -J - <br />LU Q rr <br />0 <br />E0 <br />L (0 LL <br />w <br />LU U) -J <br />< cc <br />cc )- <br />< Z-7; <br />to <br />- C') W <br />0 <br />0 N <br />- <br />Lo <br />F- <br />SWAT <br />-J, <br />FDRAw-N BYT- FAE 11 <br />VERSIONL.5.0 <br />SHEET NAME <br />COVER SHEET <br />SHEET # <br />so 1 1-140 <br />