ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />150A/200A INDOOR <br />PANEL CENTER <br />#14 to lights & outlets <br />NEMA 1 0 #12 to appllances and GFI <br />150 AMP/ <br />200 AMP 10 #10 to WH <br />#8 to Range <br />#6 to HVAC <br />R <br />50=2/0 <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND <br />Disconnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM <br />4 Bare Cu Ground <br />BONDING <br />O <br />#4 GROUNDING WIRE <br />TERMINATION PER <br />71 WITH CODE APPROVED <br />NEC 17, 250.94 <br />J CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />GENERAL <br />ELECTRICAL <br />NOTES. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, <br />h ' <br />f <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />1. Electrical outlet eights as measured rom finished floor to center tine 0f the box to be. 16 AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />24 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />;O) <br />EXHAUST FAN/LIGHT COMBINATION <br />�D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PD <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />T� 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />own <br />ELECTRIC PANEL <br />_ n" <br />DISCONNECT SWITCH <br />�_Z/� <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G r J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />0 <br />wiT�Nl:, <br />PLUMBING RISER <br />NOTE: PLUMBING RISER IS SCHEMATIC TO SCALE: NTS <br />BE VERIFIED WITH PLUMBER <br />DEDICATED RECEPTACLE <br />u <br />ELECTRICAL PLAN — ELEV—Al <br />SCALE: %4"=1'-0" <br />�ffi <br />c <br />> w <br />i ram. O <br />-ci a r� C= <br />m <br />-a X <br />N N © tO <br />tN <br />�., lu <br />Ga <br />�ce- Lo >, <br />Cc' <br />Cc <br />ca- �* <br />6',_. <br />N <br />N <br />O <br />N <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural <br />plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural <br />engineering portions of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />H <br />W <br />Q <br />aE <br />N <br />U <br />R o <br />w oho <br />0 <br />t» <br />��00 <br />ANC) <br />Q <br />13 <br />0 <br />fU co C' LL <br />c: J LL W <br />J LL LL o <br />Z_ <br />r m <br />o <br />W <br />Y O <br />N(O 0 <br />C~ <br />Lin <br />LL Z <br />m <br />LO MZ Q J <br />ZN <br />OU 0 <br />W <br />M � <br />z N M <br />O <br />z <br />Z o <br />2 <br />J <br />E3 <br />� <br />M <br />� a <br />(Dra <br />� o <br />w <br />� <br />U <br />� <br />0 <br />Ln <br />Ln <br />w o <br />w <br />CJ � <br />w <br />Nis <br />i <br />(�. <br />8 <br />N <br />z <br />/Z <br />V N <br />Q <br />N m <br />o <br />w <br />C13 <br />z ¢ <br />0 <br />Z <br />4 <br />J <br />LL_ <br />Q <br />E <br />Wo <br /><� <br />za <br />OCL a <br />¢`r <br />C0 <br />N fu <br />Qz <br />o <br />O 4 <br />-Z <br />LQ <br />'_' <br />m <br />f6 <br />C <br />oY <br />U <br />O <br />O� <br />Z F <br />Z <br />J <br />m <br />�W <br />Q W <br />W <br />oa <br />ZZ <br />3o <br />n <br />LL <br />d <br />OW <br />W <br />U ?� <br />40LL <br />¢g <br />o ;z <br />xG <br />�_ <br />3 <br />= <br />�o <br />O <br />t9 <br />u� <br />a <br />r7 <br />z¢ <br />5� <br />(fl <br />J <br />L / <br />1 O <br />�► <br />M rn <br />m <br />Q <br />M <br />co <br />r <br />:3 C:) <br />Q <br />� <br />� <br />r <br />W <br />m <br />L0 <br />Q� <br />O <br />N <br />o <br />O <br />'r <br />N <br />� <br />� <br />r <br />Q <br />� <br />r <br />E <br />C <br />o <br />z <br />f0 <br />z <br />� <br />E r <br />fA <br />'� <br />`m <br />c <br />d <br />E <br />U <br />Q p <br />JOB <br />NO: <br />22-08312 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />