Laserfiche WebLink
A .1 <br />Single Family Dwelling <br />Plan Review Comments <br />1. F.F.E. Shall be a minimum of 8" above the road elevation and a engineered site plan. <br />2. Lots shall be graded to comply with R401.3 of the F.B.C.. <br />3. Compaction test required if 24" or more of fill dirt is brought in at any one place. <br />4. Tie in survey required before pouring concrete. <br />5. Driveways require a R.O.W. use permit. <br />6. All setbacks shall be met. <br />7. All property markers shall be uncovered and marked at time of first inspection. <br />8. All A.D.A. requirements shall be met. <br />9. No electric, plumbing, mechanical, or framing shall be covered without an inspection and <br />approval first. <br />10. All Garages shall comply with section R309.2 of the F.B.C. (Fire Separation). <br />11. Appliances shall not be installed in a location where subject to mechanical damage unless <br />protected by approved barriers. M303.4 of the F.B.0 <br />12. Water heaters shall comply with section P607.3 of the .F.B.0 <br />13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M 1308.1 <br />14. Return air in all bedrooms. F.B.C. M1620.4 <br />15. Smoke detectors are to be installed in accordance with R313.1 of the F.B.C. <br />16. All glazing requirements are to be in accordance with R308.4 of the F.B.C. <br />17. All means of egress are to be in accordance with R311 of the F.B.C. <br />18. "Green gypsum board" shall not be used as a backer in showers or tubs. R702.4.2 F.B.C. <br />19. Combination -type AFCI breakers are required at all locations requiring a AFCI type breaker. <br />20. Carbon monoxide alarms will be required in new construction that uses fossil -burning heating <br />or appliances or an attached garage. They shall be installed in accordance with the F.B.C. <br />21. All plumbing, mechanical, and electrical shall be separate from unit to unit. This includes all <br />underground plumbing and electric. <br />22. All 2008 N.E.C. Codes will be enforced. <br />23. Tamper- Resistant Receptacles in accordance with 406.11 of the 2008 N.E.0 <br />22. In accordance with the Land Development Code, lots shall be sodded before final at least 10 <br />feet around the structure. <br />F.F.E.-Finished Floor Elevation <br />F.B.C- Florida Building Code (2010) <br />R.O.W.-Right Of Way <br />A.D.A.- Americans with Disabilities Act <br />N.E.C.- National Electric Code (2008) <br />