<br />ELECTRICAL NOTES
<br />CAL PLAN ,.-�-2' 121ELECTR I CAL PLAN
<br />El I 2MCj. Storu
<br />ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO ALL APPLICABLE CODES SUCH AS THE NATIONAL
<br />ELECTRICAL CODE 201-1, LOCAL ORDINANCES AND POWER COMPANY REGULATIONS.
<br />SUBCONTRACTOR SHALL BE LICENSED, CARRY ALL APPLICABLE.INSURANCE, AND HAVE A CURRENT COUNTY
<br />OCCUPATIONAL LICENSE. AS ALLOWED, CONNECT ADDITIONAL ELECTRICAL TO EXISTING CIRCUITS.
<br />SUBCONTRACTORS SHALL INCLUDE ALL SPECIAL FEES AND PERMITS, LABOR AND MATERIAL, EQUIPMENT AND
<br />ELECTRICAL ENGINEERING NECESSARY TO PROVIDE AN APPROVED WORKING SYSTEM. LIGHT FIXTURES EXCLUDED
<br />EXCEPT FOR FLUORESCENT FIXTURES AND RECESSED LIGHTS.
<br />CONCRETE -ENCASED ELECTRODE. AN ELECTRODE ENCASED BY AT LEAST 2" OF CONCRETE, LOCATED WITHIN
<br />AND NEAR THE BOTTOM OF THE CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH THE
<br />EARTH, CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER ELECTRICITY
<br />CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT LESS THAN 1/2 INCH DIAMETER, OR CONSISTING
<br />OF AT LEAST 20 FEET OF BALM COPPER CONDUCTOR NOT SMALLER THAN 4 AWG REINFORCING BARS SHALL BE
<br />PERMITTED TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS."
<br />210.12 ARC -FAULT CIRCUIT -INTERRUPTER PROTECTION.
<br />(A) DEFINITION: ARC -FAULT CIRCUIT NTERRUPTER (AFCI). A DEVICE INTENDED TO PROVIDE PROTECTION FROM
<br />THE EFFECTS OF ARC FAULTS BY RECOGNIZING CHARACTERISTICS UNIQUE TO ARCING AND BY FUNCTIONING TO
<br />DE -ENERGIZE THE CIRCUIT WHEN AN ARC FAULT IS DETECTED.
<br />(15) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS
<br />INSTALLED IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
<br />BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, AND OTHER SPECIFIED ROOMS OR AREAS
<br />SHALL BE
<br />PROTECTED BY A LISTED ARC -FAULT CIRCUIT INTERRUPTER, COMBINATION -TYPE, INSTALLED TO PROVIDE
<br />PROTECTION OF THE BRANCH CIRCUIT.
<br />CARBON MONOXIDE ALARMS
<br />R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR
<br />WHICH A PES "IT FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL -FUEL -BURNING HEATER OR APPLIANCE, A
<br />FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS A
<br />BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET
<br />(304S mm) OF EACH ROOM USED FOR SLEEPING PURPOSES.
<br />EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR
<br />REPAIR UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN SECTION R315.13.
<br />R315.IJ CARBON MONOXIDE ALARM. THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY PROVIDING FOR
<br />ONE OF THE FOLLOWING ALARM INSTALLATIONS:
<br />(1) A HARD -WIRED CARBON MONOXIDE ALARM.
<br />(2) A BATTERY-POIJERED CARBON MONOXIDE ALARM.
<br />(3) AHARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE ALARM.
<br />(4) A BATTERY -POWERED COMBINATION CARBON MONOXIDE AND SMOKE ALARM.
<br />5'315.12 COMBINATION ALARMS. COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE LISTED AND LABELED
<br />BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
<br />R315.13 ADDITION SHALL MEAN: AN EXTENSION OR INCREASE IN FLOOR AREA, NUMBER OF STORIES OR HEIGHT OF A
<br />BUILDING OR STRUCTURE
<br />250S4 BONDING FOR OTHER SYSTEMS. AN INTERSYSTEM BONDING TERMINATION
<br />FOR CONNECTING INTERSYSTEM BONDING AND GROUNDING CONDUCTORS
<br />REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
<br />ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE DISGONNECTINCs MEANS
<br />FOR ANY ADDITIONAL BUILDING%$ OR STRUCTURES. THE INTERSYSTEM BONDING
<br />TERMINATION SHALL BE ACCESSIBLE FOR CONNECTION AND NSPECTION. THE
<br />INTERSYSTEM BONDING TERMINATION SHALL HAVE THE CAPACITY FOR
<br />CONNECTION OF NOT LESS THAN THREE INTERSYSTEM BONDING CONDUCTORS.
<br />THE INTERSYSTEM BONDING TERMINATION DEVICE SHALL NOT INTERFERE WITH
<br />OPENING A SERVICE OR METERING EQUIFMENT ENCLOSURE.
<br />THE INTERSYSTEM BONDING TERMINATION SHALL BE ONE OF THE FOLLOWING•.
<br />(1) A SET OF TERMINALS SECURELY MOUNTED TO THE METER ENCLOSURE
<br />AND ELECTRICALLY CONNECTED TO THE METER ENCLOSURE. THE
<br />TERMINALS SHALL BE LISTED AS CAWLINDNG AND BONDING
<br />EQUIPMENT.
<br />(2) A BONDING BAR NEAR THE SERVICE EQUIPMENT ENCLOSURE, METER
<br />ENCLOSURE, OR RACEWAY FOR SERVICE CONDUCTORS. THE
<br />BONDING BAR SHALL BE CONNECTED WITH A MINIMUM 6 AU*
<br />COPPER CONDUCTOR TO AN E(AJIPMENT GROUNDING
<br />CONDUCTORS) IN THE SERVICE EQUIPMENT ENCLOSURE, METER
<br />ENCLOSURE, OR EXPOSED NOWLEXIBLE METALLIC RACEWAY.
<br />(3) A BONDING BAR NEAR THE GROUNDING ELECTRODE CONDUCTOR
<br />THE BONDING BAR SHALL BE CONNECTED TO THE GROUNDING
<br />ELECTRODE CONDUCTOR WITH A MINIMUM 6 AIL* COPPER
<br />CONDUCTOR
<br />(3)2/0,4G Cu, 2 "C
<br />METER
<br />(3)2/0 Cu, 2 "C
<br />TO UTILITY
<br />TRANSFORMER
<br />�V
<br />200A MLO
<br />120/240V
<br />1? 3 WIRE SN
<br />NO. 4CU
<br />GROUND IN ACCORDANCE
<br />WITH NEC 250
<br />ELECTRICAL RISER
<br />NTS
<br />INTERIOR ELECTRICAL OUTLET LOCATIONS
<br />PADDLE FAN SWITCH
<br />(LOCATE OVER FAN
<br />LIGHT SWITCH)
<br />LIGHT SWITCH
<br />DUPLEX OUTLET AT
<br />KITCHEN COUNTER, R:EFRIG.,
<br />° WASHER AND GARAGE OUTLETS
<br />DUPLEX OUTLET AT
<br />VANITY COUNTER
<br />STANDARD
<br />DUPLEX OUTLET
<br />0
<br />0
<br />n
<br />LOAD SUMMARY
<br />DESCRIPTION kVA
<br />GENERAL LIGHTING
<br />680 Sq. Ft. @ 3 Watts per Sq. Ft_ = 2.0
<br />SMALL APPLIANCE LOAD
<br />2-20A ckts @ 1.5 ea. = 3.0
<br />LAUNDRY 1.5
<br />RANGE 8.0
<br />DRYER 5.0
<br />WATER HEATER 4.5
<br />OPTIONAL GARBAGE DISPOSAL 1.2
<br />OPTIONAL DISHWASHER 1.2
<br />TOTAL 26.4
<br />First 10 kW @ 100% _
<br />Remainder at 35%
<br />HEATING
<br />1 AH w/Heat =
<br />1-HP =
<br />10.0
<br />16.4 kw x .35 = 5.75
<br />6.8
<br />6.7
<br />TOTAL CALCULATED 29.3
<br />Calculated load for service size is 29.3 kW
<br />divided by 230V = 127.2 Amps (Amps
<br />200A SERVICE.
<br />ALL ELECTRICAL SWITCHES,
<br />OUTLETS, ETC. TO SE MOUNTED
<br />45OVE THE BASE FLOOD
<br />ELEVATION. (SEE SITE PLAN
<br />FOR 8,46E ELEVATION)
<br />ELECTRICAL S`I' 150LS LEGEND
<br />CEILING LIGHT EfSO 200 AMP. PANEL ® TELEVISION PRE -WIRE
<br />{R}- RECESSED CAN LIGHT — — — — — — — - LED STRIP LIGHTING TELEPHONE PRE -WIRE
<br />110V DUPLEX RECEPTACLE '------- I @ SMOKE ALARM
<br />TX 4' FLUORESCENT
<br />1 � ® CARBON MONOXIDE
<br />220V OUTLET 1 LIGHT DETECTOR
<br />f l 110V G.F.I. OUTLET OJ JUNCTION BOX
<br />--�-- TRACK LIGHTING
<br />SWITCHED DUPLEX REG. 4 PUSH BUTTON (G.D.O.,
<br />�Cp�Qp�p� BEAUTY BAR LIGHT T CHIMES, ETC.)
<br />® OUTLET (HWH, AH, ETC.) FLOOD LIGHT
<br />$ SINGLE POLE SWITCH �` ® BRACE a DOOR BELL CHIME
<br />$3 THREE WAY LIGHT SWITCH 1\ / PRE -WIRE ��� ELECTRICAL WIRING
<br />FOR FAN
<br />Vy GARAGE DOOR OPENER �� �� EXHAUST FAN
<br />L J
<br />.�- SCONCE LIGHTING L IGHT/EX. FAN
<br />6
<br />C
<br />Q
<br />D
<br />O
<br />L
<br />CD
<br />rn
<br />N
<br />C
<br />O
<br />L
<br />N
<br />C
<br />O
<br />0
<br />PO
<br />N
<br />O
<br />N
<br />d
<br />O
<br />0
<br />Thomas L Digitally signed b
<br />g y g y Signed and sealed by T.L. Hanson
<br />Thomas L using a Digital Signature and date. \Q�p -N - 4,
<br />Printed
<br />H a n so n:A01410 Pr rated copies of thisdocument _ tires
<br />Hanson:A01410D00000 are not considered signed and
<br />D00000177EF31 177EF31134E000015ADA Sealed and the signature must be
<br />A
<br />verified on any electronic co
<br />Date: 2023.10.24 %��'• FLOR��P'?���`
<br />B4E000015ADA 11:19:13-04'00'
<br />►l
<br />
|