GENERAL NOTES <br />1. THESE DWGS ARE THE PROPERTY OF GLOBAL CONSULTING ENGINEERS, INC. <br />AND SHALL NOT BE USED, REPRODUCED, OR ALTERED IN <br />ANY WAY WITHOUT THE PRIOR EXPRESSED WRITTEN CONSENT. <br />ANY CHANGES, DELETIONS OR ADDITIONS TO THESE DRAWINGS WITHOUT <br />CONSENT IS STRICTLY PROHIBITED. <br />2. ANY AND ALL ITEMS REQUIRED TO FURNISH A COMPLETE CONSTRUCTION, <br />BUT NOT SPECIFICALLY SHOWN OR SPECIFIED ON THE DRAWINGS SHALL BE <br />FURNISHED AND INSTALLED IN CONFORMANCE TO THE FLORIDA BUILDING <br />CODE AND LOCAL ORDINANCES AND IN GOOD WORKMANLIKE MANNER. <br />3. IT IS NOT THE INTENT OF THESE DRAWINGS TO SHOW EVERY DETAIL OF <br />CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL <br />ALL ITEMS REQUIRED TO COMPLETE THE WORK. <br />4. THE ENGINEER IS NOT RESPONSIBLE FOR THE EXISTING BUILDING, BUILDING <br />UTILITIES OR WORK NOT SPECIFICALLY SHOWN OR SPECIFIED ON THESE DRAWINGS. <br />5. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED BUILDING PERMITS, INSURANCES, <br />LICENSES, TAXES, ETC. REQUIRED TO PERFORM THE WORK OUTLINED IN <br />THE DRAWINGS. <br />6. THE CONTRACTOR SHALL COORDINATE AND SUPERVISE ALL THE WORK <br />PERFORMED BY HIS FORCES AND BY SUBCONTRACTORS. THE CONTRACTOR <br />SHALL BE RESPONSIBLE FOR COORDINATION AND VERIFICATION WITH OTHER <br />TRADES TO ASSURE COMPLIANCE WITH THE APPROVED DRAWINGS. <br />7. THE CONTRACTOR SHALL VERIFY SIZES AND LOCATIONS OF ALL MECHANICAL, <br />PLUMBING AND ELECTRICAL EQUIPMENT PRIOR TO COMMENCING THE WORK. <br />8. THE CONTRACTOR SHALL COORDINATE ALL PARKING, STORAGE, TRASH REMOVAL, <br />ETC. WITH THE OWNER OR BUILDING MANAGER. <br />9. ABBREVIATIONS NOTED IN THE DRAWINGS OR SPECIFICATIONS ARE THOSE <br />COMMONLY USED. THE ENGINEER WILL DEFINE ANY ABBREVIATION QUESTIONED <br />UPON REQUEST. <br />10. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY BARRIERS, <br />LIGHTING, COVERING, BRACING, SHORING, FIRE PREVENTION AND OTHER <br />EQUIPMENT NECESSARY TO PROTECT THE SAFETY AND SECURITY OF ALL <br />PERSONS AND THE PROPERTY THROUGHOUT THE ENTIRE PERIOD OF CONSTRUCTION. <br />11. THE CONTRACTOR SHALL REPAIR OR REPLACE ANY EXISTING FINISHES AND/OR <br />ANY ITEMS DAMAGED DURING CONSTRUCTION TO MATCH THE ADJACENT EXISTING. <br />12. THE PLANS ARE NOT TO BE SCALED. THE PLANS AND DIAGRAMS SHOW RELATIVE <br />LOCATIONS AND ACTUAL EXISTING LOCATIONS MAY VARY IN THE FIELD. <br />13. THE CONTRACTOR SHALL REVIEW EXISTING BUILDING SYSTEMS AND UTILITIES AS <br />TO THEIR COMPLIANCE WITH THE FLORIDA BUILDING CODE AND OTHER <br />APPLICABLE CODES AND NOTIFY THE ENGINEER OF ANY NON -CONFORMING <br />ITEMS FOUND. <br />14. SECTIONS AND DETAILS SHOWN TYPICAL ON THE PLANS MAY NOT BE SPECIFICALLY <br />NOTED AT EACH APPLICABLE LOCATION. HOWEVER, THESE DETAILS MAY BE <br />APPLICABLE OR MAY BE REQUIRED IN MORE THAN ONE LOCATION. <br />15. THE CONTRACTOR SHALL COORDINATE HIS CONSTRUCTION SCHEDULES, PLANNED <br />POWER OUTGOS, NIGHTTIME WORK, WEEKEND WORK AND WORK IN OTHER <br />ADJACENT TENANT SPACES WITH THE OWNER PRIOR TO PERFORMING THE WORK. <br />16. THE CONTRACTOR SHALL SUPPLY THE OWNER WITH ALL EQUIPMENT <br />MANUALS AND WARRANTIES. <br />17. THE CONTRACTOR SHALL GUARANTEE IN WRITING ALL MATERIALS AND LABOR FOR <br />A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER <br />AND WILL AT HIS OWN COST REPAIR OR REPLACE ALL WORK OR DAMAGES CAUSED <br />BY THE WORK WHICH BECOMES DEFECTIVE DURING THE TERM OF THE GUARANTEE. <br />AND OTHER SPECIFIC REQUIREMENTS MAY BE MODIFIED OR EXTENDED BY THE <br />OWNER/CONTRACTOR AGREEMENT. <br />18. WHERE DISSIMILAR METALS COME IN CONTACT, THE CONTRACTOR SHALL PROVIDE <br />PROPER INSULATION TO PREVENT GALVANIC OR ELECTROLYTIC ACTION <br />AS WELL AS VIBRATION OR NOISE TRANSMISSION. <br />19. THE CONTRACTOR SHALL PROVIDE THE OWNER WITH A SET OF AS BUILT DRAWINGS <br />INDICATING ALL FILED CHANGES, ADDITIONS OR DELETIONS MADE DURING <br />CONSTRUCTION. <br />20. ALL DEMOLITION SHALL BE COORDINATED WITH THE OWNER PRIOR TO <br />PERFORMING THE WORK. <br />21. ALL NEW MATERIALS/EQUIPMENT SHALL HAVE U.L. (UNDERWRITER'S <br />LABORATORY) APPROVED LABELS AS ACCEPTED BY LOCAL AUTHORITY. <br />22. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH THE UTILITY <br />COMPANIES TO ASSURE THAT IT COMPLIES WITH THEIR REQUIREMENTS. <br />23. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH ALL <br />NATIONAL, STATE, AND LOCAL CODES HAVING JURISDICTION AND WITH ALL <br />REQUIREMENTS OF THE UTILITY COMPANIES WHOSE SERVICES SHALL BE USED. <br />24. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AND <br />SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE DISCOVERED OR <br />DEVIATIONS FROM THE APPROVED PLANS REQUIRED BEFORE PROCEEDING WITH <br />THE WORK INVOLVED. COMMENCEMENT OF THE WORK SHALL CONSTITUTE <br />ACCEPTANCE OF EXISTING CONDITIONS. <br />25. IF DOUBT EXISTS IN THE MIND OF THE BIDDER AS TO THE TRUE MEANING OF <br />ANY PART OF THESE CONSTRUCTION DRAWINGS, BIDDER MUST REQUEST THE <br />INFORMATION IN WRITING FROM THE ENGINEER IMMEDIATELY. <br />26. ALL SHOP DRAWINGS SHALL BE SUBMITTED W/ CONTRACTOR'S REVIEW STAMP <br />TO ENGINEER FOR APPROVAL PRIOR TO FABRICATION. ALLOW 10 BUSINESS <br />DAYS FOR REVIEW. <br />27. ANY SUBSTITUTIONS MUST BE REVIEWED AND APPROVED IN WRITTING BY THE <br />ENGINEER PRIOR TO FABRICATION OR PURCHASING. <br />28. ALL WOOD IN CONTACT WITH MASONRY SHALL BE PRESSURE TREATED <br />29. ALL MATERIALS SHALL HAVE A MINIMUM CLASS "C" FLAME SPREAD RATING. <br />30. PROVIDE ONE TYPE ABC RATED FIRE EXTINGUISHER PER EVERY 3000 S.F. <br />OR FRACTION THEREOF OF BUILDING AREA. (PROVIDE 2 MIN.) <br />31. ALL NEW WALLS SHALL RECEIVE ONE COAT OF PRIMER PRIOR TO RECEIVING <br />TWO COATS OF INTERIOR LATEX PAINT. COLOR AS SELECTED BY OWNER. <br />32. CONTRACTOR SHALL COORDINATE ALL NEW CABINETRY, MILLWORK, EQUIPMENT, <br />AND FINISHES WITH OWNER. <br />33. ALL NEW DRYWALL SHALL BE SMOOTH FINISH UNLESS OTHERWISE NOTED. <br />34. ALL DOOR AND WINDOW FRAMES SHALL BE CAULKED AROUND ENTIRE PERIMETER. <br />35. PROVIDE 2 X 4 BLOCKING AT PERIMETER OF ALL DOOR AND WINDOW OPENINGS. <br />36. IT IS NOT WARRANTED THAT THE EXISTING CONDITIONS SHOWN ARE <br />REPRESENTATIVE OF ACTUAL EXISTING CONDITIONS. ENGINEER ASSUMES NO <br />RESPONSIBILITY FOR EXISTING CONDITIONS WHICH ARE SHOWN ONLY FOR <br />REFERENCE. CONTRACTOR TO VERIFY ALL CONDITIONS, MEASUREMENTS, & <br />ELEVATIONS BEFORE START OF CONSTRUCTION OR FABRICATION. INFORM <br />ENGINEER IN WRITING OF ANY DISCREPANCIES. <br />37. UNLESS OTHERWISE NOTED, DIMENSIONS ARE GIVEN TO FACE OF <br />STUD & FACE OF CMU, TYPICALLY. <br />38. WHERE NEW CONSTRUCTION ABUTS EXIST. CONSTRUCTION THAT IS <br />TO REMAIN, ALL ADJACENT MATERIALS & FINISHES SHALL BE <br />REPAIRED & REFINISHED TO LIKE NEW FINISH. <br />39. WHERE EXISTING CEILING, WALLS & FLOORS HAVE BEEN DAMAGED <br />DUE TO DEMOLITION & NEW CONSTRUCTION UNDER THIS CONTRACT, <br />CONTR. SHALL REPAIR & REFINISH AS REQ'D. TO LIKE NEW FINISH. <br />40. EXISTING CONDITIONS SHALL BE FIELD MEASURED/VERIFIED <br />PRIOR TO CONSTRUCTION. <br />41. CONTRACTOR SHALL ERECT DUST/SECURITY BARRIERS AS REQ'D <br />FOR DURATION OF CONTRACT. BARRIERS SHALL CONSIST OF 2x4 <br />CONSTRUCTION W/ \" OSB OR PLYWD ONE SIDE FOR SECURITY <br />PURPOSES & VISQUEEN ON CONSTRUCTION SIDE FOR DUST <br />CONTROL. EXTEND DUST/ SECURITY WALL FROM FLOOR TO EXIST <br />GWB CLG, TYPICALLY. <br />42. FIELD VERIFY ALL CONDITIONS, INCLUDING UNDERGROUND WHENEVER <br />POSSIBLE. <br />43. TERMITE TREAT FOR SUBTERRANEAN TERMITES BENEATH FLOOR SLABS <br />ON GRADE FILL AND ALONG EXTERIOR OF ALL FOUNDATION WALLS. <br />44. ASSUMED SOIL BRG. PRESSURE IS 1500 PSF. <br />45. PROPORTIONING OF REINFORCED CONCRETE MEMBERS & THEIR STEEL <br />REINFORCING ARE BASED ON AN ULTIMATE STRENGTH DESIGN IN <br />ACCORDANCE W/ "BUILDING CODE REQUIREMENTS FOR REINFORCED <br />CONCRETE", ACI 318-83. <br />46. ALL CONCRETE SHALL BE CLASSIFIED AS NORMAL WEIGHT W/ A UNIT WT. <br />OF 145 PCF AND 3,000 PSI. <br />47. ALL REINFORCING SHALL COMPLY WITH ASTM 615 GRADE 60, DEFORMRD. <br />48. UNLESS NOTED, LAP ALL HORIZONTAL BARS 30 DIAMETERS AND ALL <br />VERTICAL BARS 24 DIAMETERS. <br />49• HORIZONTAL REINFORCEMENT IN FOOTINGS, TURNDOWN SLABS & WALLS <br />SHALL BE CONTINUOUS AROUND CORNERS. <br />50. CONTRACTOR TO PROVIDE ALL NECESSARY BRACING AND SHORING <br />DURING CONSTRUCTION. <br />51. MASONRY CONCRETE UNITS SHALL BE 8" CMU. <br />52. LUMBER SHALL COMPLY WITH PS 20 SOFTWOOD LUMBER STANDARDS. ALL <br />LUMBER SHALL BE S4S SEASONED LUMBER WITH 19% MOISTURE <br />CONTENT. <br />53. STRUCTURAL LUMBER SHALL BE NO. 2 YELLOW PINE, Fb= 1200 PSI. <br />54. CONSTRUCTION PANELS SHALL COMPLY WITH AMERICAN PLYWOOD <br />ASSOCIATION AND MARKED WITH APA STAMP. <br />55. GYPSUM WALL BOARD SHALL COMPLY TO ASTM 36, 1 /2" THICK WITH <br />TAPERED EDGES. GENERAL CONTRACTOR SHALL SELECT GYPSUM WALL <br />FINISH. <br />56. ROOF ASSEMBLY SHALL COMPLY WITH FLORIDA BUILDING CODE <br />SECTION 104.2.1.1. ROOF ASSEMBLY TO BE DESIGNED & PERMITTED BY <br />TRUSS MANUFACTURER. <br />57. A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY <br />SHALL BE ON THE SITE FOR THE BUILDING INSPECTOR USE. OR, ALL PROPERTY <br />MARKERS SHALL BE EXPOSED AND A STRING STRETCHED FROM MARKER TO <br />MARKER TO VERIFY REQUIRED SETBACKS. <br />58. ALL PLUMBING, ELECTRICAL, AND MECHANICAL ROUGH -INS MUST BE COMPLETE, <br />INSPECTED AND APPROVED BEFORE REQUESTING THE FRAMING INSPECTION IN <br />ACCORDANCE WITH 2O17 FLORIDA BUILDING CODE (6TH ADDITION). <br />59• CONTRACTOR TO VERIFY STRUCTURAL INTEGRITY OF EXIST. WALLS, BEAMS, <br />COLUMNS, ETC. BEFORE REMOVAL OR DEMOLISHING. AN INSPECTION BY A <br />STRUCTURAL ENGINEER MAYBE REQUIRED BEFORE COMMENCEMENT OF <br />CONSTRUCTION. <br />60. ALL EXISTING STRUCTURAL MEMBERS SUCH AS WALLS, BEAMS, COLUMNS, <br />ROOF, FOUNDATION, ETC. TO BE VERIFIED BY STRUCTURAL ENGINEER PRIOR <br />TO CONSTRUCTION. <br />SOIL TREATMENT FOR TERMITES <br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TREATMENT PROVIDER & NEED <br />FOR RE -INSPECTION & TREATMENT CONTRACT RENEWAL SHALL BE <br />PROVIDED. SIGN SHALL BE POSTED NEAR WATER HEATER, OR ELECTRICAL <br />PANEL. <br />2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0" <br />AWAY FROM THE BUILDING SIDE WALLS. <br />3. IRRIGATION/ SPRINKLER SYSTEM INCLUDING ALL RISERS 8c SPRAY HEADS <br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS. <br />4. TO PROVIDE FOR INSPECTION OF TERMITE INFESTATION, SEPARATION <br />BETWEEN WALL COVERING 8c FINAL EARTH GRADE SHALL NOT BE LESS <br />THAN 6 INCHES. EXCEPTION: PAINT OR CEMENTITIOUS FINISH < THAN 5/8" <br />THICK APPLIED DIRECTLY TO FOUNDATION WALL <br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND <br />BACKFILL IS COMPLETE. <br />6. SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE TREATED <br />INCLUDING SPACED BOXED OR FORMED. <br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF <br />TRAPS, ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. <br />PERMANENT FORMS MUST BE OF A SIZE 8c DEPTH THAT WILL ELIMINATE <br />THE DISTURBANCE OF SOIL AFTER THE INITIAL TREATMENT. <br />8. A 10-MIL. MINIMUM VAPOR RETARDER MUST BE INSTALLED TO PROTECT <br />AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE VAPOR <br />RETARDER PLACEMENT, RETREATMENT IS REQUIRED. <br />9. CONCRETE OVERPOUR & MORTAR ALONG FOUNDATION PERIMETER MUST <br />BE REMOVED BEFORE EXTERIOR TREATMENT. <br />10. APPLY SOIL TREATMENT UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 1'-0" OF STRUCTURE SIDEWALLS. <br />11- AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER <br />CONSTRUCTION IS COMPLETE INCLUDING LANDSCAPING 8c IRRIGATION. ANY <br />SOIL DISTURBED AFTER THE VERTICAL BARRIER IS APPLIED SHALL BE <br />RETREATED. <br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE -CONSTRUCTION TREATMENT. <br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO BUILDING <br />DEPARTMENT BY A LICENSED PEST CONTROL COMPANY BEFORE A 0.0. WILL <br />BE ISSUED. CERTIFICATE OF COMPLIANCE SHALL STATE "THE BUILDING HAS <br />RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF <br />SUBTERRANEAN TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE <br />RULES & LAWS OF THE FLORIDA DEPARTMENT OF AGRICULTURE & <br />CONSUMER SERVICES." <br />14- AFTER WORK IS COMPLETED, LOOSE WOOD & FILL MUST BE REMOVED <br />FROM BELOW & WITHIN 1'-0" OF BUILDING. INCLUDING ALL GRADE STAKES, <br />TUB TRAP BOXES, FORMS, SHORING, OR OTHER CELLULOSE CONTAINING <br />MATERIAL. <br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE <br />BURIED WITHIN '5'-0" OF ANY BUILDING OR PROPOSED BUILDING. <br />PROPOSED INTERIOR BUILD -OUT AT: <br />5915 Gall Blvd, <br />Zephyrhills, FL 33542 <br />OWNER NAME: ZEPHYR LLC <br />OWNER ADDRESS: 7162 READING RD STE 730 <br />CINCINNATI, OH 45237-3845 <br />PROFESSIONAL SERVICES BY: GLOBAL CONSULTING ENGINEERS, INC. <br />Dead Jot <br />sullo o GasStation0 ul G x gaIV 1P <br />Rd 0, <br />Rd North Ave <br />North Ave <br />0, <br />' K & K Glass, I <br />s r �w Laundry USA <br />w 011ie's Bargain OtItlet <br />i iscount tcr. <br />Pet Supplies IVI rion Smith Florist <br />Pius Z phyrhills Delivery <br />Sunrise Eatery s4 � <br />T €� <br />Sl ell's Killer Bakery <br />SITE-LOCA110LA <br />Hart cl� 9 Tai�e��_J <br />Adkins 0 Pet Hospital T - <br />Wellspring Tree Lane Village ,.. <br />�. itd LlVit� Mobile Horne - <br />All <br />� <br />,, AbOUt , <br />Salon Day Spa R.. <br />4 sc, <br />y, <br />I5th Ave . <br />ALL WORK SHALL COMPLY WITH PREVAILING <br />CODES FLORIDA BUILDING CODE, <br />NATIONAL ELECTRIC CODE, <br />DRAWING ABBREVIATIONS <br />AND THE CITY OF ZEPHYRHILLS <br />A.B. <br />ANCHOR BOLT <br />DET. <br />DETAIL <br />GYP. <br />GYPSUM <br />PSI <br />PER SQUARE INCH <br />ORDINANCES <br />A. C. <br />AIR CONDITIONING <br />DIA. <br />DIAMETER <br />HGT. <br />HEIGHT <br />REF. <br />REFERENCE <br />ACOUST. <br />ACOUSTICAL <br />DIM. <br />DIMENSION <br />HDWE. <br />HARDWARE <br />REINF. <br />REINFORCED <br />ADD'N. <br />ADDITION <br />DN. <br />DOWN <br />HM. <br />HOLLOW METAL <br />R/C <br />REINFORCED CONCRETE <br />ADMIN. <br />ADMINISTRATION <br />DRYW <br />DRYWALL <br />INFO <br />INFORMATION <br />A.F.F. <br />ABOVE FINISHED FLOOR <br />DS. <br />DOWNSPOUT <br />INSUL. <br />INSULATION <br />RM. <br />ROOM <br />DWGS. <br />DRAWINGS <br />JT. <br />JOINT <br />SCHED. <br />SCHEDULE <br />ALT. <br />ALTERNATE <br />EA. <br />EACH <br />LAM. <br />LAMINATED <br />SC. <br />SOLID CORE <br />n(� <br />ALUM. <br />ALUMINUM <br />EIFS <br />EXTERIOR INSULATING <br />LAV. <br />LAVATORY <br />SECT. <br />SECTION(S) <br />i"11 /i <br />ANCH. <br />ANCHOR <br />FINISH SYSTEM <br />MACH. <br />MACHINE <br />SH. <br />SHEET <br />*AV`)A "Ti: <br />ACT. <br />ACOUSTICAL CEILING TILE <br />ELECT. <br />ELECTRICAL <br />MANUF. <br />MANUFACTURER <br />SIM. <br />SIMILAR <br />tX1;°V--s ZCMYINrHIL <br />ELEV. <br />ELEVATION <br />MATL. <br />MATERIAL <br />SS. <br />STAINLESS STEEL <br />o11 AWV,,; OMCIAL <br />® <br />AT <br />EQ. <br />EQUAL <br />MAX. <br />MAXIMUM <br />STL. <br />STEEL <br />BLK. <br />BLOCK <br />EWC. <br />ELECTRIC WATER COOLER <br />MECH. <br />MECHANICAL <br />STD. <br />STANDARD <br />BD. <br />BOARD <br />MIN. <br />MINIMUM <br />STRUCT. <br />STRUCTURAL <br />BM. <br />BEAM <br />EXIST, <br />EXISTING <br />M.O. <br />MASONRY OPENING <br />TELE. <br />TELEPHONE <br />BOTT. <br />BOTTOM <br />EXT. <br />EXTERIOR <br />M.R. <br />MOISTURE RESISTANT <br />TH. <br />THICK(ENED) <br />BRG. <br />BEARING <br />EXP. <br />EXPANSION <br />MET. <br />METAL <br />TYP. <br />TYPICAL <br />B.U.R. <br />BUILT UP ROOF <br />F&I <br />FURNISH AND INSTALL <br />NIC. <br />NOT IN CONTRACT <br />T.O.W. <br />TOP OF WALL <br />C.J. <br />CONTROL JOINT <br />FIBERGL. <br />FIBERGLASS <br />NO. <br />NUMBER <br />T.O.S. <br />TOP OF STEEL <br />CLG. <br />CEILING <br />F.D. <br />FLOOR DRAIN <br />NTS. <br />NOT TO SCALE <br />UL <br />UNDERWRITERS <br />CLR. <br />CLEAR <br />F.E. <br />FIRE EXTING. <br />O.C. <br />ON CENTER <br />LABORATORIES <br />CMU. <br />CONCRETE MASONRY UNIT <br />FIN. <br />FINISH <br />O.D. <br />OUTSIDE DIAMETER <br />UNO <br />UNLESS NOTED <br />FLASH'G. <br />FLASHING <br />OFF. <br />OFFICE <br />OTHERWISE <br />COL. <br />COLUMN <br />FL. <br />FLOOR <br />OPG. <br />OPENING <br />VCT <br />VINYL COMPOSITION <br />CONC. <br />CONCRETE <br />FTG. <br />FOOTING <br />OPP. <br />OPPOSITE <br />TILE <br />CONT. <br />CONTINUOUS <br />FURN. <br />FURNISH <br />PART. <br />PARTITION <br />VERT. <br />VERTICAL <br />CONSTR. <br />CONSTRUCTION <br />GA. <br />GAUGE <br />PAV'T. <br />PAVEMENT <br />W/ <br />WITH <br />C.T. <br />CERAMIC TILE <br />GALV. <br />GALVANIZED <br />P.T. <br />PRESSURE TREATED <br />W.W.F. <br />WELDED WIRE FABRIC <br />COORD. <br />COORDINATE <br />GWB <br />GYPSUM WALL BOARD <br />PTD. <br />PAINTED CHLORIDE <br />W. <br />WIDTH <br />DBL. <br />DOUBLE <br />PVC <br />POLY VINYL <br />WD. <br />WOOD <br />SCOPE OF WORK &PERMIT REFERENCE: <br />NEW INTERIOR BUILDOUT IN AN EXISTING 1,072 SF <br />RETAIL SPACE IN EXISTING SHELL SPACE. <br />TENANT CONTRACTOR NOTE <br />TENANT/ GENERAL CONTRACTOR MUST AQUIRE LAND <br />LORD'S APPROVAL OF THE PROPOSED DESIGN/ <br />WORK IN WRITING BEFORE THE START OF ANY WORK. <br />LEGAL DESCRIPTION <br />SITE: PARCEL ID: 10-26-21-0020-00000-0100 <br />PINE GROVE PB 2 PG 15 COM SW COR LOT 10 FOR POB TH NO2DG 02' 12"W 172.00 FT TH N88DG 28' WE 623.71 FT TH S02DG <br />02' WE 47.00 FT TH S88DG 28' 05"W 93.00 FT TH S02DG 02' 10"E 60.00 FT TH N88DG 28' 05"E 93.00 FT TH S02DG 02' 12"E <br />65.00 FT TH S88DG 28' 05"W 630.08 FT TO POB LESS THAT POR DESC IN OR 9679 PG 2653 LYING WITHIN OR 4341 PG 1041 <br />CODE INFORMATION <br />FLORIDA BUILDING CODE, 2020 (7TH EDITION) <br />ALL WORK SHALL CONFORM TO THE FOLLOWING CODES <br />AS WELL AS <br />ALL LOCAL ORDINANCES AUTHORITIES HAVING LOCAL JURISDICTION: <br />FLORIDA EXISTING BUILDING CODE 2020 <br />EDITION <br />FLORIDA ENERGY CONSERVATION CODE 2020 <br />EDITION <br />FLORIDA MECHANICAL CODE 2020 <br />EDITION <br />FLORIDA CODE FUEL GAS 2020 <br />EDITION <br />FLORIDA PLUMBING CODE 2020 <br />EDITION <br />FLORIDA FIRE PREVENTION CODE 2020 <br />EDITION <br />NFPA 1 UNIFORM FIRE CODE 2018 <br />EDITION <br />NFPA 101 LIFE SAFTY CODE 2018 <br />EDITION <br />NFPA 70-17 NAT'L ELECTRICAL CODE 2017 <br />EDITION <br />NFPA 72-18 NAT'L FIRE ALARM CODE 2018 <br />EDITION <br />FLORIDA ACCESSIBILITY CODE 2020 <br />EDITION <br />(COMBINES FL. AMERICANS W\ DISABILITIES ACT & FED. <br />ADA LAW) <br />BUILDING DATA <br />BUILDING LOCATION RIVERVIEW/ HILLSBOROUGH COUNTY <br />EXISTING ZONING OOSD <br />PROPERTY USE MERCANTILE (GENERAL RETAIL) <br />EXISTING OCCUPANCY VACANT SHELL <br />PROPOSED OCCUPANCY "M" MERCANTILE (RETAIL <br />STORE) <br />LAND AREA 2.13 ACRES <br />EXISTING SHELLBUILDING AREA 14,024 S.F. <br />PROPOSED BUILDOUT AREA 1,072 S.F. <br />MAXIMUM AREA ALLOWED 12,500 S.F. <br />EXISTING BUILDING HEIGH 16'-0" <br />MAXIMUM HEIGHT ALLOWED 35' <br />TYPE OF CONSTRUCTION TYPE VB <br />UNSPRINKLED UNPROTECTED, <br />FIRE ALARM NO <br />MEANS OF EGRESS/ MAX OCCUPANT LOAD: <br />FBC - BUILDING, CHAPTER 10 FLOOR AREA PER OCCUPANT <br />TABLE 1004.1.2: <br />TOTAL OCCUPANT LOAD = 1072 / 60 SF PER PERSON <br />=18 PERSONS <br />PARKING REQUIREMENTS. <br />PARKING REQUIREMENT: 5 SPACES PER 1,000 SF <br />1,072 / 1000 * 5 = 6 SPACES REQUIRED <br />270 SHARED SPACES PROVIDED <br />WIND DESIGN CRITERIA: (ASCE7-10) <br />BASIC WIND SPEED: 140 MPH (3 SEC. GUST) <br />WIND EXPOSURE: "C" <br />BUILDING RISK CATEGORY II <br />ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT, <br />P = qh [(GCp) - (GCpi)] <br />GCpi = +/- 0.18 <br />CORNER DISTANCE = 8.0 FT <br />COMPONENTS AND CLADDING WIND PRESSURES = SEE TABLES <br />NET WIND UPLIFT = -0.6DL + WL <br />GRAVITY DESIGN LOADS: <br />ROOF LIVE LOAD: 20 PSF <br />ASSUMED ROOF DEAD LOAD: 20 PSF (37 PSF AT TOWERS). <br />ASSUMED DESIGN SOIL BRG PRESSURE: 2,000 PSF (GC VERIFY) <br />COMPACT TO 95% OF THE MODIFIED PROCTOR DRY DENSITY <br />SITE NOTES <br />1. CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND CAREFULLY COMPARE <br />SUCH FIELD MEASUREMENTS AND CONDITIONS AND OTHER INFORMATION <br />KNOWN TO THE CONTRACTOR WITH THE DRAWINGS BEFORE COMMENCING <br />WORK ACTIVITIES. ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED <br />BY OR MADE KNOWN TO THE CONTRACTOR SHALL BE PROMPTLY <br />REPORTED TO THE ENGINEER. CONTRACTOR'S COMMENCEMENT OF WORK <br />SHALL CONSTITUTE T U E ACCEPTANCE OF EXISTING CONDITIONS. <br />2. CONTRACTOR SHALL REMOVE ALL DEBRIS, TREES, VEGETATION AND <br />ORGANIC MATTER IN ORDER TO PREPARE THE SITE FOR DEVELOPMENT. <br />3. CONTRACTOR SHALL CONNECT ALL POTABLE WATER LINES FIRE LINES <br />AND SEWER LINES TO EXISTING WATER, FIRE AND SEWER LATERALS. <br />4. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS BEARING THEIR REVIEW <br />STAMP. TO THE ENGINEER FOR REVIEW OF ALL PRE -MANUFACTURED <br />COMPONENTS PRIOR TO FABRICATION &/OR PURCHASE. ALLOW 10 <br />BUSINESS DAYS FOR REVIEW. <br />HANDICAP ACCESSIBILITY NOTES <br />THE DESIGN OF SPACES DEPICTED IN THESE DRAWINGS COMPLIES <br />WITH THE ACCESSIBILITY REQUIREMENTS OF THE 2020 FLORIDA <br />BUILDING CODE 6TH EDITION. <br />BUILDING SHALL INCLUDE AN ACCESSIBLE ROUTE FOR THE PUBLIC <br />FROM ACCESSIBLE PARKING SPACES TO ENTRY DOORS AND INTO <br />THE BUILDING. ALL PUBLIC AREAS ARE ACCESSIBLE AND HAVE NO <br />LEVEL CHANGES GREATER THAN j " EXCEPT AS PROVIDED BY RAMP. <br />SHEET INDEX <br />1 - <br />CS.1 <br />COVER SHEET. <br />2 - <br />G1.1 <br />PROPOSED FLOOR PLAN & DETAILS. <br />3 - <br />G1.2 <br />LIFE SAFETY & REFLECTED CEILING PLANS. <br />4 - <br />G1.3 <br />ENLARGED RESTROOMS PLANS AND DETAILS. <br />5 - <br />G1.4 <br />SCHEDULES AND DETAILS. <br />6 - <br />P-1 <br />PLUMBING PLAN DETAILS. <br />7 - <br />P-2 <br />PLUMBING RISER DIAGRAMS. <br />8 - <br />M-1 <br />MECHANICAL PLAN. <br />9 - <br />E-1 <br />ELECTRICAL POWER & LIGHTING PLANS. <br />10- <br />E-2 <br />ELECTRICAL NOTES AND SPECS. <br />11- <br />E-3 <br />ELECTRICAL SPECIFICATIONS <br />BEFORE PERMITTING OR START OF CONSTRUCTION: <br />1. TENANT TO ACQUIRE LANDLORD WRITTEN APPROVAL OF ALL PROPOSED ALTERATIONS. <br />2. CONTRACTOR TO VERIFY ALL EXISTING DIMENSIONS AND ELEVATIONS. <br />3. CONTRACTOR TO COORDINATE ROUGH WINDOW/ DOOR OPENINGS SIZE W/ MFR SPECS <br />ISSUED FOR: REVIEW <br />11.12.2021 <br />z <br />O <br />o' <br />U <br />U) <br />w <br />0 <br />xw>_w_0zM <br />O <br />Ln <br />-� <br />co <br />q <br />� <br />� <br />O <br />� <br />W <br />� <br />� <br />a <br />N <br />W <br />� <br />O <br />(� <br />W <br />� <br />z <br />L;j > <br />a <br />z <br />0 <br />0 <br />J <br />Lo <br />U <br />U <br />z <br />Q_ <br />U) <br />Lp::� <br />�O <br />� U <br />co <br />0z <br />m�I <br />O <br />�{ <br />a® <br />F' O <br />z <br />W <br />�l <br />co <br />rr <br />CrD <br />w <br />a� <br />0 <br />H <br />(f <br />a <br />E- <br />�� <br />6 <br />w <br />✓(\ i1�1 <br />m <br />O <br />fs-� <br />Ld <br />ai <br />T <br />Q <br />o <br />62 <br />Gw,ffFi7 COA. NO.29116 <br />MAZEN <br />PE. <br />MAR,if, <br />(FL. P I# 691 6) <br />o Q <br />w <br />cn <br />W <br />cn <br />v O <br />w <br />-' w <br />,F <br />�- <br />0w <br />SHEET <br />7z <br />L <br />