<br />THROUGH -PENETRATION DETAIL
<br />SYSTEM No. E-A-1015
<br />F RATI NC�S - 2 HR
<br />1. FLOOR ASSEMBLY - THE FIRE -RATED UNPROTECTED CONCRETE AND STEEL FLOOR
<br />ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER
<br />SPECIFIED THE INDIVIDUAL D900 SERIES DESIGNS IN THE U.L. FIRE RESISTANCE
<br />DIRECTORY AND AS SUMMARIZED BELOW:
<br />A. CONCRETE - MIN 2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT
<br />(100-150 PCF) CONCRETE.
<br />B. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON -COMPOSITE MAX
<br />3 IN. DEEP GALV FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING
<br />DESIGN. MAX DIAM OF OPENING IS 6 IN.
<br />2. THROUGH PENETRATIONS - CNE METALLIC PIPE, CONDUIT OR TUBING INSTALLED
<br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM,
<br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH
<br />OPENINGS SHAL_ B MIN 0 IN. (POINT CONTACTS) TO MAX 1-7/8 IN. PIPE, CONDUIT OR
<br />TUBING TO BE R DDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY.
<br />THE FOLLOWING -YPES AND SIZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY
<br />BE USED:
<br />A. STEEL PIPE
<br />B. IRON PIPE
<br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
<br />TUBING OR STEEL CONDUIT.
<br />D. COPPER TUBING
<br />E. COPPER PIPE
<br />3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />PACKING MATERIAL - MIN 1-1/2 IN. THICKNESS OF MIN 4 PCF DENSITY MINERAL
<br />WOOL BAIT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM.
<br />PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS
<br />REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL (ITEM 38).
<br />FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1/2 IN. THICKNESS OF FILL
<br />MATERIAL APPI ED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. AT
<br />POINT CONTACT _OCATION BETWEEN PENETRANT AND CONCRETE, A MIN 1/2 IN.
<br />DIAM BEAD OF LL MATERIAL SHALL BE APPLIED AT THE CONCRETE/PENETRANT
<br />INTERFACE ON -0P SURFACE OF FLOOR.
<br />FIRESTOP SYSTEM INC. - 4800 DW
<br />*BEARING THE J_ CLASSIFICATION MARKING
<br />THROUGH -PENETRATION DETAIL
<br />S''STEM No. W-J-104g
<br />Y RATINGS - 2 HR
<br />SECTION A -A
<br />1. WALL ASSEMB_" - MIN 6-1/8 IN. THICK NORMAL WEIGHT OR LIGHTWEIGT
<br />(100-150 PC[-) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY U.L.
<br />CLASSIFIED CCNCRETE BLOCKS*. MAX DIAM OF OPENING IS 14-1/8 IN.
<br />SEE CONCRE-E BLOCKS (CAZT) CATERCORY IN THE FIRE RESISTANCE DIRECTORY
<br />FOR NAME O- MANUFACTURER.
<br />2. THROUGH PENETRATIONS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED
<br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM.
<br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF
<br />OPENINGS SH-.LL BE MIN 3/8 IN. TO MAX 1 IN. PIPE, CONDUIT OR TUBING TO BE
<br />RIGIDLY SUPPDRTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING
<br />TYPES AND S ZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
<br />A. STEEL P,----
<br />B, IRON PIPE
<br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
<br />TUBING R STEEL CONDUIT.
<br />D. COPPER -.BING
<br />E. COPPER - °E
<br />3. FILL, VOID OR AVITY MATERIAL* - SEALANT - MIN 1-1/4 IN. THICKNESS
<br />OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF
<br />OF WALL.
<br />FIRESTOP SYS-EM INC. - 4800 DW
<br />*BEARING THE UL CLASSIF CATION MARKING
<br />FIRE ALARM NOTES:
<br />SEQUENCE OF OPERATION:
<br />1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS:
<br />A. MANUAL PULL STATION:
<br />1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE ALARM AT THE FACP.
<br />3) ILLUMINATE THE ALARM RED LED,
<br />4) SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES)
<br />IN THE BUILDING.
<br />B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER -
<br />FLOW SWITCH SHALL CAUSE THE FOLLOWING:
<br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION.
<br />2) A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER -FLOW ALARM
<br />SHALL NO BE ABLE TO BE SILENCED.
<br />C. SMOKE DETECTORS FOR E'-EVATOR RECALL:
<br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION.
<br />2) REFER TO ELEVATOR RECALL SEQUENCE OF OPERATION.
<br />D. SMOKE DUCT DETECTORS :
<br />1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP,
<br />3) ILLUMINATE THE SUPERVISORY LED.
<br />4 SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT.
<br />E. FLOW BELL :
<br />1) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF FLOW SWITCH ONLY,
<br />2) FLOW BELL SHALL SOUND AS LONG AS THE WATER IS FLOWING.
<br />3) FLOW BELL SHALL NO BE CAPLABLE OF BEING SILENCED FROM THE FACP.
<br />F. ACTIVATION OF ANY SUPERVISORY CIRCUIT OR TAMPER SWITCH SHALL CAUSE THE
<br />FOLLOWING ACTIONS AND INDICATIONS:
<br />1) IDENTIFY THE INDIVIDUAL CIRCUIT OR DEVICE ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP.
<br />3) ILLUMINATE THE SUPERVISORY LED.
<br />G. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE
<br />FOLLOWING ACTIONS AND INDICATIONS:
<br />1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP.
<br />3) ILLUMINATE THE TROUBLE LED,
<br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE DISPLAYED ON
<br />THE MAIN FIRE ALARM PANEL AS WELL AS ON ALL REMOTE ANNUNCIATOR PANELS,
<br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE TRANSMITTED TO
<br />A LISTED CENTRAL STATION.
<br />CENTRAL STATION / TRANSMISSION OF SIGNALS / MONITORING
<br />- ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE
<br />CENTRAL STATION.
<br />- THE MEANS OF TRANSMISSION IS WIRELESS DIALER.
<br />- ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS:
<br />A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION,
<br />SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW:
<br />DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION
<br />(FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS
<br />OR BUILDING NUMBER.
<br />- THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE
<br />THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD.
<br />CODES & PLAN NOTES
<br />- ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED.
<br />- COORDINATE WITH SPRINKLER CONTRACTOR EXACT LOCATION OF ALL
<br />TAMPER AND FLOW SWITCHES.
<br />- INSTALL STROBE BOX FOR FUTURE ADA USE IN ALL 1ST FLOOR APARTMENT'S
<br />BATHROOMS.
<br />- CONFIRM LOCATION OF POWER SUPPLIES IN BLDGS PRIOR TO ROUGH IN.
<br />- REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR
<br />RETURN SIDE), COORDINATE WITH -MECHANICAL CONTRACTOR THE ACTUAL
<br />LOCATIONS OF THE AHUs.
<br />- ALL STROBES WILL BE SET @ 75cd UNLESS NOTED.
<br />- CEILING HEIGHT IS 10ft UNLESS NOTED.
<br />- UNDERGROUND WIRE USED AS SLC FOR COMMUNICATION BETWEEN BUILDINGS
<br />IS SUITABLE FOR WET LOCATIONS / DIRECT BURAL
<br />- ANY PROPOSED INTERCONNECTION OF PANELS WILL BE A "NON -LATCHING"
<br />CONFIGURATION PANEL RESET FROM 1 LOCATION.
<br />- FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE.
<br />- SMOKE DETECTORS FOR SMOKE COMPARTMENTS WILL BE PROVIDED
<br />AS PER NFPA-72 17.7.5.6.5.1 (A)
<br />- COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF SMOKE DAMPERS
<br />- SINGLE STATION 120 AC SMOKE DETECTOR AND C/O DETECTORS PROVIDED BY
<br />ELECTRICAL CONTRACTOR ON SEPARATE PERMIT.
<br />- ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT
<br />PERMIT ######### FBC 107.2
<br />- INSTALLATION SHALL BE IN ACCORDANCE WITH 2O20 FFPC 7TH ED., NFPA 72 2016 ED.
<br />NFPA 1 2018 ED., NFPA 101 2018 ED. AND NFPA 13 2016 ED.
<br />24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE. IF BUILDING IS OCCUPIED
<br />DURING THIS TEST, FIREWATCH WILL BE REQUIRED.
<br />- ALL AUDIBLE DEVICES LOCATED INSIDE SLEEPING AREAS MEET NFPA-72 (2016)
<br />18.4.5.3 FOR LOW FREQUENCY REQUIREMENTS
<br />- ALL NEW SYSTEMS SHALL INCLUDE A DOCUMENT CABINET.
<br />** 24/5 STANDBY TEST REQUIRED IF ANY PART OF THE BLDG IS OCCUPIED
<br />BY TENANTS DURING THIS TEST, A FIRE WATCH IS REQUIRED FROM
<br />7AM-7PM.
<br />ELECTRICAL MOUNTING BOX
<br />FOR THE CEILING MOUNTED
<br />NOTIFICATION DEVICES.
<br />"CADDY" T-GRID BOX HANGER ACOUSTICAL TILE CEILING
<br />SUPPORT, OR EQUAL. "CADDY" GRID SJPPORT FRAMING.
<br />REFERENCE NO. CE-C 30-302(3).
<br />CEILING GRID ELECTRICAL BACK -BOX ATTACHMENT
<br />FIRE ALARM DEVICE LEGEND
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />FACP
<br />0
<br />FIRE ALARM CONTROL PANEL
<br />U)
<br />ZFO
<br />L REMOTE ANNUNCIATOR PANE
<br />Ri
<br />U
<br />FCPS
<br />0
<br />POWER SUPPLY EXPANDER
<br />_j
<br />J
<br />w
<br />0 FMTC
<br />FIRE ALARM TERMINAL CABINET
<br />Z
<br />Vic
<br />o
<br />REMOTE MICROPHONE PANEL
<br />MD
<br />AUDIO PANEL
<br />DIALER
<br />0
<br />FIRE ALARM DIALER
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />HORN/STROBE WALL MOUNT
<br />Wp
<br />HORN/STROBE OUTDOOR
<br />CM
<br />HORN/STROBE CEILING MOUNT
<br />9< LF
<br />LOW FREQUENCY FREQUENCY
<br />O
<br />151<
<br />SPEAKER/STROBE WALL MOUNT
<br />VWp
<br />SPEAKER/STROBE OUTDOOR
<br />CM
<br />SPEAKER/STROBE CEILING MOUNT
<br />O Z
<br />�s
<br />SPEAKER
<br />STROBE
<br />Wp
<br />STROBE OUTDOOR
<br />CM
<br />STROBE CEILING MOUNT
<br />104
<br />LOW FREQUENCY HORNS
<br />SMOKE SOUNDER BASE
<br />SPRINKLER BELL
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />F❑
<br />PULL STATION
<br />PULL STATION OUTDOOR
<br />8
<br />SMOKE PHOTO DETECTOR
<br />B ION
<br />SMOKE ION DETECTOR
<br />O
<br />8 co
<br />SMOKE C/O DETECTOR
<br />Q
<br />®
<br />HEAT DETECTOR
<br />I?
<br />zli-
<br />DUCT DETECTOR SUPPLY SIDE
<br />DUCT DETECTOR RETURN SIDE
<br />©RZ
<br />FLOW SWITCH
<br />®
<br />BEAM DETECTOR
<br />M❑
<br />MONITOR MODULE
<br /><
<br />MINI -HORN
<br />®wP
<br />HEAT DETECTOR WEATHER PROOF
<br />a_j
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />ffiE
<br />TAMPER SWITCH
<br />ir
<br />®
<br />RELAY
<br />EOL
<br />END OF LINE RESISTOR
<br />O
<br />U
<br />suRa
<br />SURGE SUPRESSOR
<br />■❑
<br />DOOR HOLDER
<br />U
<br />HSI
<br />REMOTE TEST SWITCH
<br />>
<br />❑
<br />CONTROL MODULE
<br />d
<br />❑
<br />LOCK BOX (PROVIDED BY OTHERS)
<br />U)
<br />CEILING MOUNTED
<br />SMOKE/HEAT
<br />DETECTOR
<br />24" MIN HANDICAP
<br />BEDROOM STROBE
<br />MORE THAN TWO APPLIANCES
<br />IN THE SAME ROOM OR ADJACENT
<br />SPACE WITHIN THE FIELD OF VIEW
<br />SHALL FLASH IN SYNCHRONIZATION.
<br />80" MIN
<br />96" MAX
<br />NFPA 72 2016
<br />(ADAAG)
<br />BO" ABOVE HIGHEST FLOOR
<br />LEVEL OR 6" BELOW CEILING
<br />TO THE BOTTOM OF THE
<br />STROBE. WHICHEVER IS LOWER.
<br />FINISHED
<br />FLOOR
<br />3' (MIN)
<br />PER NFPA 72
<br />A/C SUPPLY DIFFUSER
<br />AUDIO/VISUAL
<br />�c VISUAL -ONLY CEILING MOUNTED NOTIFICATION
<br />DEVICES DEVICE (TO BE WHITE),
<br />SEE PLAN FOR LOCATION.
<br />ACCEPTABLE HERE/
<br />DO NOT INSTALL
<br />IN THIS AREA
<br />WALL MOUNTED
<br />HEAT DETECTOR -
<br />TO THE BOTTOM.
<br />WALL MOUNTED
<br />5'-0 SMOKE DETECTOR -
<br />MAX FROM EXIT DOOR TO THE TOP.
<br />MANUAL I
<br />PULL
<br />STATION
<br />6„
<br />MAGNETIC
<br />DOORO
<br />HOLDER
<br />48" (ADA)
<br />TO THE WORKING MECHANISM
<br />48" ALSO MEETS THE
<br />REQUIREMENTS OF NFPA 72 2016
<br />4"
<br />C
<br />►'
<br />4'
<br />12" (MAX)
<br />REMOTE
<br />/-ANNUNCIATOR
<br />IMPORTANT NOTE NOTE
<br />NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE CHECK WITH MANUFACTURE'S INSTALLATION SHEET
<br />THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF
<br />DEVICES APPLY, AND WHICH DO NOT. BACK BOXES, AND WIRING REQUIREMENTS.
<br />FIRE ALARM DEVICE MOUNTING GUIDE
<br />TYPICAL SPRINKLER CLOSET WITH FIRE ALARM PANEL 17 INSTALLATION NOTES:
<br />INSTALLATION DIAGRAM.
<br />Q
<br />2
<br />MAIN TAMPERS AND WATERFLOWS
<br />Breaker Box
<br />1.
<br />120vac Lme n 1/2 or 3/4 EMT conduit, PVc or Flex
<br />supplied by electrical contractor,
<br />2.
<br />120vac surge protector, suppled by Fire Alarm contractor,
<br />3,
<br />Installed by Electrical Contractor on Electrical breaker Panel.
<br />Splice Box, Installed and Supplied By Electrical Contractor,
<br />4.
<br />FACP, Supplied and Installed by Fire Alarm Contractor.
<br />b=:
<br />5.
<br />6.
<br />FOPS, Supplied and Installed by Fire Alarm Contractor.
<br />3/4" EMT Conduit ar Flex Supplied By Electrical Contractor.
<br />p0000
<br />7.
<br />PVC Box 6x6x4, Supplied and Installed by Electrical Contractor,
<br />® ! m
<br />8.
<br />3/4" PVC Conduit for Underground Connection Front/To other
<br />Fire Alarm Closets.
<br />FACP m
<br />2
<br />9.
<br />WaterRow Sensor.
<br />10.
<br />Water Tamper.
<br />11.
<br />Surge Protector, Supplied and Installed BY Fire Alarm Contractor.
<br />12.
<br />3/4" EMT Conduit or Flex Supplied By Electrical Contractor.
<br />1 3 11
<br />13.
<br />4 Square PVC Splice Box, Supplied and Installed by Fire Alarm
<br />J z
<br />FCPS
<br />14.
<br />Contractor.
<br />1/2" or 3/4" PVC Conduit or Seal tight Flex Supplied By
<br />Electrical Contractor.
<br />15.
<br />3/4" PVC Conduit for Underground Connection To Outside Tampers.
<br />m
<br />16.
<br />Single gang Box attached to Water Tamper, Supplied and
<br />installed By E13ctrical Contractor.
<br />17.
<br />4 Square Box with Rised P-Ring For Smoke Detector, Supplied
<br />By Electrical Contractor.
<br />18.
<br />Breaker Lock, Supplied By Electrical Contactor.
<br />ME
<br />EXTERIOR MAIN TAMPERS, BACKFLOWS, ETC.
<br />ELEC-RICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING ALL THE
<br />NECESSARY HARDWARE (BOXES, CONNECTORS, CONDUITS, Etc.) AS WELL AS
<br />nA Ai ik-TAI i AI Anrn iAi 7Ai nTnAnTrr
<br />-t
<br />� � B 2
<br />JL
<br />71
<br />--a,� --.' L f'
<br />I
<br />A41
<br />I
<br />i
<br />I � G
<br />N
<br />SITE PLAN
<br />THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
<br />SEALED BY SAMUEL P. DEAN, P.E. ON [11.282022] USING
<br />A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF
<br />THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
<br />SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
<br />BE VERIFIED ON ANY ELECTRONIC COPIES.
<br />■ I'
<br />U2 e. rP,, r-,
<br />mom
<br />Fire Alarm & C mmunicati ns
<br />Cust mer Service is ur Greatest Techn I gy.
<br />ME
<br />SUPERIOR FIRE ALARM 8c
<br />COMMUNICATIONS
<br />6201 JOHNS ROAD
<br />SUITE 9
<br />TAMPA, EL 33634
<br />813- 81 8- 4444
<br />CERTIFIED ALARM SYSTEM
<br />CON TR ACT OR 1
<br />LICENSE EE 20001162
<br />0
<br />�-
<br />E
<br />4-A
<br />L
<br />N
<br />U
<br />Q
<br />2�
<br />Z_
<br />J z
<br />a
<br />0
<br />F-
<br />OCO
<br />U
<br />U) uUJ
<br />Uj
<br />oN-'
<br />XQ
<br />Ov
<br />WoZ
<br />0 Q
<br />LL
<br />U
<br />J
<br />_jz
<br />Q
<br />IxvW
<br />W
<br />CO
<br />L
<br />s
<br />N
<br />4-
<br />O
<br />DO
<br />CAD DATE:
<br />9/9/2022
<br />N0. ISSUE/REVISION
<br />DATE
<br />Digitally signed
<br />,,%0IEL. P 04 � ..
<br />5P
<br />by Samuel P.
<br />`�,,�\GENSF
<br />No 83915
<br />Dean
<br />STATE OF 44,:
<br />Date:
<br />-•°�F° �OR1�PC_>
<br />2022.11.28
<br />oNA� �,°
<br />09:13:58-05'00'
<br />SAMUEL P. DEAN P.E.
<br />CONSULTING ENGINEER
<br />REGISTRATION NUMBER 93915
<br />CA # 29694
<br />1503-A WEST B SCH BLVD.
<br />TAMPA FLORIDA 33612
<br />PHONE: (813) 961-3075
<br />FAX: (813) 961-1031
<br />email: spec-@oeltengineering.com
<br />1 CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF
<br />ALL OF THE STRUCTURAL ELEMENTS AND SYSTEMS FOR THIS
<br />STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE
<br />WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL
<br />OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE
<br />TOTAL RESPONSIBILITY OF OTHERS.
<br />SFIEET:
<br />FIRE ALARM
<br />FA- I of 3