Laserfiche WebLink
F <br />R <br />E <br />S <br />T <br />O <br />P <br />I <br />S <br />S <br />T <br />E <br />M <br />F <br />R <br />E <br />S <br />T <br />O <br />P <br />S <br />Y <br />S <br />T <br />E <br />M <br />THROUGH -PENETRATION DETAIL <br />SYSTEM No. E-A-1015 <br />F RATI NC�S - 2 HR <br />1. FLOOR ASSEMBLY - THE FIRE -RATED UNPROTECTED CONCRETE AND STEEL FLOOR <br />ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER <br />SPECIFIED THE INDIVIDUAL D900 SERIES DESIGNS IN THE U.L. FIRE RESISTANCE <br />DIRECTORY AND AS SUMMARIZED BELOW: <br />A. CONCRETE - MIN 2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT <br />(100-150 PCF) CONCRETE. <br />B. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON -COMPOSITE MAX <br />3 IN. DEEP GALV FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING <br />DESIGN. MAX DIAM OF OPENING IS 6 IN. <br />2. THROUGH PENETRATIONS - CNE METALLIC PIPE, CONDUIT OR TUBING INSTALLED <br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM, <br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH <br />OPENINGS SHAL_ B MIN 0 IN. (POINT CONTACTS) TO MAX 1-7/8 IN. PIPE, CONDUIT OR <br />TUBING TO BE R DDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. <br />THE FOLLOWING -YPES AND SIZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY <br />BE USED: <br />A. STEEL PIPE <br />B. IRON PIPE <br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC <br />TUBING OR STEEL CONDUIT. <br />D. COPPER TUBING <br />E. COPPER PIPE <br />3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: <br />PACKING MATERIAL - MIN 1-1/2 IN. THICKNESS OF MIN 4 PCF DENSITY MINERAL <br />WOOL BAIT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. <br />PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS <br />REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL (ITEM 38). <br />FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1/2 IN. THICKNESS OF FILL <br />MATERIAL APPI ED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. AT <br />POINT CONTACT _OCATION BETWEEN PENETRANT AND CONCRETE, A MIN 1/2 IN. <br />DIAM BEAD OF LL MATERIAL SHALL BE APPLIED AT THE CONCRETE/PENETRANT <br />INTERFACE ON -0P SURFACE OF FLOOR. <br />FIRESTOP SYSTEM INC. - 4800 DW <br />*BEARING THE J_ CLASSIFICATION MARKING <br />THROUGH -PENETRATION DETAIL <br />S''STEM No. W-J-104g <br />Y RATINGS - 2 HR <br />SECTION A -A <br />1. WALL ASSEMB_" - MIN 6-1/8 IN. THICK NORMAL WEIGHT OR LIGHTWEIGT <br />(100-150 PC[-) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY U.L. <br />CLASSIFIED CCNCRETE BLOCKS*. MAX DIAM OF OPENING IS 14-1/8 IN. <br />SEE CONCRE-E BLOCKS (CAZT) CATERCORY IN THE FIRE RESISTANCE DIRECTORY <br />FOR NAME O- MANUFACTURER. <br />2. THROUGH PENETRATIONS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED <br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. <br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF <br />OPENINGS SH-.LL BE MIN 3/8 IN. TO MAX 1 IN. PIPE, CONDUIT OR TUBING TO BE <br />RIGIDLY SUPPDRTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING <br />TYPES AND S ZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY BE USED: <br />A. STEEL P,---- <br />B, IRON PIPE <br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC <br />TUBING R STEEL CONDUIT. <br />D. COPPER -.BING <br />E. COPPER - °E <br />3. FILL, VOID OR AVITY MATERIAL* - SEALANT - MIN 1-1/4 IN. THICKNESS <br />OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF <br />OF WALL. <br />FIRESTOP SYS-EM INC. - 4800 DW <br />*BEARING THE UL CLASSIF CATION MARKING <br />FIRE ALARM NOTES: <br />SEQUENCE OF OPERATION: <br />1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS: <br />A. MANUAL PULL STATION: <br />1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE ALARM AT THE FACP. <br />3) ILLUMINATE THE ALARM RED LED, <br />4) SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES) <br />IN THE BUILDING. <br />B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER - <br />FLOW SWITCH SHALL CAUSE THE FOLLOWING: <br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION. <br />2) A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER -FLOW ALARM <br />SHALL NO BE ABLE TO BE SILENCED. <br />C. SMOKE DETECTORS FOR E'-EVATOR RECALL: <br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION. <br />2) REFER TO ELEVATOR RECALL SEQUENCE OF OPERATION. <br />D. SMOKE DUCT DETECTORS : <br />1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP, <br />3) ILLUMINATE THE SUPERVISORY LED. <br />4 SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT. <br />E. FLOW BELL : <br />1) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF FLOW SWITCH ONLY, <br />2) FLOW BELL SHALL SOUND AS LONG AS THE WATER IS FLOWING. <br />3) FLOW BELL SHALL NO BE CAPLABLE OF BEING SILENCED FROM THE FACP. <br />F. ACTIVATION OF ANY SUPERVISORY CIRCUIT OR TAMPER SWITCH SHALL CAUSE THE <br />FOLLOWING ACTIONS AND INDICATIONS: <br />1) IDENTIFY THE INDIVIDUAL CIRCUIT OR DEVICE ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP. <br />3) ILLUMINATE THE SUPERVISORY LED. <br />G. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE <br />FOLLOWING ACTIONS AND INDICATIONS: <br />1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP. <br />3) ILLUMINATE THE TROUBLE LED, <br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE DISPLAYED ON <br />THE MAIN FIRE ALARM PANEL AS WELL AS ON ALL REMOTE ANNUNCIATOR PANELS, <br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE TRANSMITTED TO <br />A LISTED CENTRAL STATION. <br />CENTRAL STATION / TRANSMISSION OF SIGNALS / MONITORING <br />- ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE <br />CENTRAL STATION. <br />- THE MEANS OF TRANSMISSION IS WIRELESS DIALER. <br />- ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS: <br />A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION, <br />SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW: <br />DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION <br />(FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS <br />OR BUILDING NUMBER. <br />- THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE <br />THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD. <br />CODES & PLAN NOTES <br />- ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED. <br />- COORDINATE WITH SPRINKLER CONTRACTOR EXACT LOCATION OF ALL <br />TAMPER AND FLOW SWITCHES. <br />- INSTALL STROBE BOX FOR FUTURE ADA USE IN ALL 1ST FLOOR APARTMENT'S <br />BATHROOMS. <br />- CONFIRM LOCATION OF POWER SUPPLIES IN BLDGS PRIOR TO ROUGH IN. <br />- REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR <br />RETURN SIDE), COORDINATE WITH -MECHANICAL CONTRACTOR THE ACTUAL <br />LOCATIONS OF THE AHUs. <br />- ALL STROBES WILL BE SET @ 75cd UNLESS NOTED. <br />- CEILING HEIGHT IS 10ft UNLESS NOTED. <br />- UNDERGROUND WIRE USED AS SLC FOR COMMUNICATION BETWEEN BUILDINGS <br />IS SUITABLE FOR WET LOCATIONS / DIRECT BURAL <br />- ANY PROPOSED INTERCONNECTION OF PANELS WILL BE A "NON -LATCHING" <br />CONFIGURATION PANEL RESET FROM 1 LOCATION. <br />- FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE. <br />- SMOKE DETECTORS FOR SMOKE COMPARTMENTS WILL BE PROVIDED <br />AS PER NFPA-72 17.7.5.6.5.1 (A) <br />- COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF SMOKE DAMPERS <br />- SINGLE STATION 120 AC SMOKE DETECTOR AND C/O DETECTORS PROVIDED BY <br />ELECTRICAL CONTRACTOR ON SEPARATE PERMIT. <br />- ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT <br />PERMIT ######### FBC 107.2 <br />- INSTALLATION SHALL BE IN ACCORDANCE WITH 2O20 FFPC 7TH ED., NFPA 72 2016 ED. <br />NFPA 1 2018 ED., NFPA 101 2018 ED. AND NFPA 13 2016 ED. <br />24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE. IF BUILDING IS OCCUPIED <br />DURING THIS TEST, FIREWATCH WILL BE REQUIRED. <br />- ALL AUDIBLE DEVICES LOCATED INSIDE SLEEPING AREAS MEET NFPA-72 (2016) <br />18.4.5.3 FOR LOW FREQUENCY REQUIREMENTS <br />- ALL NEW SYSTEMS SHALL INCLUDE A DOCUMENT CABINET. <br />** 24/5 STANDBY TEST REQUIRED IF ANY PART OF THE BLDG IS OCCUPIED <br />BY TENANTS DURING THIS TEST, A FIRE WATCH IS REQUIRED FROM <br />7AM-7PM. <br />ELECTRICAL MOUNTING BOX <br />FOR THE CEILING MOUNTED <br />NOTIFICATION DEVICES. <br />"CADDY" T-GRID BOX HANGER ACOUSTICAL TILE CEILING <br />SUPPORT, OR EQUAL. "CADDY" GRID SJPPORT FRAMING. <br />REFERENCE NO. CE-C 30-302(3). <br />CEILING GRID ELECTRICAL BACK -BOX ATTACHMENT <br />FIRE ALARM DEVICE LEGEND <br />SYMBOL <br />DEVICE DESCRIPTION <br />FACP <br />0 <br />FIRE ALARM CONTROL PANEL <br />U) <br />ZFO <br />L REMOTE ANNUNCIATOR PANE <br />Ri <br />U <br />FCPS <br />0 <br />POWER SUPPLY EXPANDER <br />_j <br />J <br />w <br />0 FMTC <br />FIRE ALARM TERMINAL CABINET <br />Z <br />Vic <br />o <br />REMOTE MICROPHONE PANEL <br />MD <br />AUDIO PANEL <br />DIALER <br />0 <br />FIRE ALARM DIALER <br />SYMBOL <br />DEVICE DESCRIPTION <br />HORN/STROBE WALL MOUNT <br />Wp <br />HORN/STROBE OUTDOOR <br />CM <br />HORN/STROBE CEILING MOUNT <br />9< LF <br />LOW FREQUENCY FREQUENCY <br />O <br />151< <br />SPEAKER/STROBE WALL MOUNT <br />VWp <br />SPEAKER/STROBE OUTDOOR <br />CM <br />SPEAKER/STROBE CEILING MOUNT <br />O Z <br />�s <br />SPEAKER <br />STROBE <br />Wp <br />STROBE OUTDOOR <br />CM <br />STROBE CEILING MOUNT <br />104 <br />LOW FREQUENCY HORNS <br />SMOKE SOUNDER BASE <br />SPRINKLER BELL <br />SYMBOL <br />DEVICE DESCRIPTION <br />F❑ <br />PULL STATION <br />PULL STATION OUTDOOR <br />8 <br />SMOKE PHOTO DETECTOR <br />B ION <br />SMOKE ION DETECTOR <br />O <br />8 co <br />SMOKE C/O DETECTOR <br />Q <br />® <br />HEAT DETECTOR <br />I? <br />zli- <br />DUCT DETECTOR SUPPLY SIDE <br />DUCT DETECTOR RETURN SIDE <br />©RZ <br />FLOW SWITCH <br />® <br />BEAM DETECTOR <br />M❑ <br />MONITOR MODULE <br />< <br />MINI -HORN <br />®wP <br />HEAT DETECTOR WEATHER PROOF <br />a_j <br />SYMBOL <br />DEVICE DESCRIPTION <br />ffiE <br />TAMPER SWITCH <br />ir <br />® <br />RELAY <br />EOL <br />END OF LINE RESISTOR <br />O <br />U <br />suRa <br />SURGE SUPRESSOR <br />■❑ <br />DOOR HOLDER <br />U <br />HSI <br />REMOTE TEST SWITCH <br />> <br />❑ <br />CONTROL MODULE <br />d <br />❑ <br />LOCK BOX (PROVIDED BY OTHERS) <br />U) <br />CEILING MOUNTED <br />SMOKE/HEAT <br />DETECTOR <br />24" MIN HANDICAP <br />BEDROOM STROBE <br />MORE THAN TWO APPLIANCES <br />IN THE SAME ROOM OR ADJACENT <br />SPACE WITHIN THE FIELD OF VIEW <br />SHALL FLASH IN SYNCHRONIZATION. <br />80" MIN <br />96" MAX <br />NFPA 72 2016 <br />(ADAAG) <br />BO" ABOVE HIGHEST FLOOR <br />LEVEL OR 6" BELOW CEILING <br />TO THE BOTTOM OF THE <br />STROBE. WHICHEVER IS LOWER. <br />FINISHED <br />FLOOR <br />3' (MIN) <br />PER NFPA 72 <br />A/C SUPPLY DIFFUSER <br />AUDIO/VISUAL <br />�c VISUAL -ONLY CEILING MOUNTED NOTIFICATION <br />DEVICES DEVICE (TO BE WHITE), <br />SEE PLAN FOR LOCATION. <br />ACCEPTABLE HERE/ <br />DO NOT INSTALL <br />IN THIS AREA <br />WALL MOUNTED <br />HEAT DETECTOR - <br />TO THE BOTTOM. <br />WALL MOUNTED <br />5'-0 SMOKE DETECTOR - <br />MAX FROM EXIT DOOR TO THE TOP. <br />MANUAL I <br />PULL <br />STATION <br />6„ <br />MAGNETIC <br />DOORO <br />HOLDER <br />48" (ADA) <br />TO THE WORKING MECHANISM <br />48" ALSO MEETS THE <br />REQUIREMENTS OF NFPA 72 2016 <br />4" <br />C <br />►' <br />4' <br />12" (MAX) <br />REMOTE <br />/-ANNUNCIATOR <br />IMPORTANT NOTE NOTE <br />NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE CHECK WITH MANUFACTURE'S INSTALLATION SHEET <br />THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF <br />DEVICES APPLY, AND WHICH DO NOT. BACK BOXES, AND WIRING REQUIREMENTS. <br />FIRE ALARM DEVICE MOUNTING GUIDE <br />TYPICAL SPRINKLER CLOSET WITH FIRE ALARM PANEL 17 INSTALLATION NOTES: <br />INSTALLATION DIAGRAM. <br />Q <br />2 <br />MAIN TAMPERS AND WATERFLOWS <br />Breaker Box <br />1. <br />120vac Lme n 1/2 or 3/4 EMT conduit, PVc or Flex <br />supplied by electrical contractor, <br />2. <br />120vac surge protector, suppled by Fire Alarm contractor, <br />3, <br />Installed by Electrical Contractor on Electrical breaker Panel. <br />Splice Box, Installed and Supplied By Electrical Contractor, <br />4. <br />FACP, Supplied and Installed by Fire Alarm Contractor. <br />b=: <br />5. <br />6. <br />FOPS, Supplied and Installed by Fire Alarm Contractor. <br />3/4" EMT Conduit ar Flex Supplied By Electrical Contractor. <br />p0000 <br />7. <br />PVC Box 6x6x4, Supplied and Installed by Electrical Contractor, <br />® ! m <br />8. <br />3/4" PVC Conduit for Underground Connection Front/To other <br />Fire Alarm Closets. <br />FACP m <br />2 <br />9. <br />WaterRow Sensor. <br />10. <br />Water Tamper. <br />11. <br />Surge Protector, Supplied and Installed BY Fire Alarm Contractor. <br />12. <br />3/4" EMT Conduit or Flex Supplied By Electrical Contractor. <br />1 3 11 <br />13. <br />4 Square PVC Splice Box, Supplied and Installed by Fire Alarm <br />J z <br />FCPS <br />14. <br />Contractor. <br />1/2" or 3/4" PVC Conduit or Seal tight Flex Supplied By <br />Electrical Contractor. <br />15. <br />3/4" PVC Conduit for Underground Connection To Outside Tampers. <br />m <br />16. <br />Single gang Box attached to Water Tamper, Supplied and <br />installed By E13ctrical Contractor. <br />17. <br />4 Square Box with Rised P-Ring For Smoke Detector, Supplied <br />By Electrical Contractor. <br />18. <br />Breaker Lock, Supplied By Electrical Contactor. <br />ME <br />EXTERIOR MAIN TAMPERS, BACKFLOWS, ETC. <br />ELEC-RICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING ALL THE <br />NECESSARY HARDWARE (BOXES, CONNECTORS, CONDUITS, Etc.) AS WELL AS <br />nA Ai ik-TAI i AI Anrn iAi 7Ai nTnAnTrr <br />-t <br />� � B 2 <br />JL <br />71 <br />--a,� --.' L f' <br />I <br />A41 <br />I <br />i <br />I � G <br />N <br />SITE PLAN <br />THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND <br />SEALED BY SAMUEL P. DEAN, P.E. ON [11.282022] USING <br />A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF <br />THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND <br />SEALED AND THE SHA-1 AUTHENTICATION CODE MUST <br />BE VERIFIED ON ANY ELECTRONIC COPIES. <br />■ I' <br />U2 e. rP,, r-, <br />mom <br />Fire Alarm & C mmunicati ns <br />Cust mer Service is ur Greatest Techn I gy. <br />ME <br />SUPERIOR FIRE ALARM 8c <br />COMMUNICATIONS <br />6201 JOHNS ROAD <br />SUITE 9 <br />TAMPA, EL 33634 <br />813- 81 8- 4444 <br />CERTIFIED ALARM SYSTEM <br />CON TR ACT OR 1 <br />LICENSE EE 20001162 <br />0 <br />�- <br />E <br />4-A <br />L <br />N <br />U <br />Q <br />2� <br />Z_ <br />J z <br />a <br />0 <br />F- <br />OCO <br />U <br />U) uUJ <br />Uj <br />oN-' <br />XQ <br />Ov <br />WoZ <br />0 Q <br />LL <br />U <br />J <br />_jz <br />Q <br />IxvW <br />W <br />CO <br />L <br />s <br />N <br />4- <br />O <br />DO <br />CAD DATE: <br />9/9/2022 <br />N0. ISSUE/REVISION <br />DATE <br />Digitally signed <br />,,%0IEL. P 04 � .. <br />5P <br />by Samuel P. <br />`�,,�\GENSF <br />No 83915 <br />Dean <br />STATE OF 44,: <br />Date: <br />-•°�F° �OR1�PC_> <br />2022.11.28 <br />oNA� �,° <br />09:13:58-05'00' <br />SAMUEL P. DEAN P.E. <br />CONSULTING ENGINEER <br />REGISTRATION NUMBER 93915 <br />CA # 29694 <br />1503-A WEST B SCH BLVD. <br />TAMPA FLORIDA 33612 <br />PHONE: (813) 961-3075 <br />FAX: (813) 961-1031 <br />email: spec-@oeltengineering.com <br />1 CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF <br />ALL OF THE STRUCTURAL ELEMENTS AND SYSTEMS FOR THIS <br />STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE <br />WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL <br />OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE <br />TOTAL RESPONSIBILITY OF OTHERS. <br />SFIEET: <br />FIRE ALARM <br />FA- I of 3 <br />