Laserfiche WebLink
r <br />� a <br />TAPE EDGE OF HEAD <br />WALL FLASHING <br />STUCCO ON FRAME - 7/8" <br />3-GOAT SAND FINISH STUCCO <br />ON SELF FURRING LATH ON 2- <br />LAYERS OF WATER RESISTIVE <br />BARRIER COMPLYING WITH <br />ASTM E2556, TYPE 1 (TYP) <br />WALL SHEATHING PER PLAN — <br />SHINGLE WATER <br />RESISTIVE BARRIER <br />OVER WEEP SCREED -- <br />WEEP SCREED <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL- <br />18 GA HEAD WALL FLASHING <br />TO EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />SHINGLE ROOF PER SPECS -- <br />ROOF UNDERLAYMENT TO <br />TURN UP WALL MIN 8 <br />ROOF SHEATHING <br />PER PLAN <br />----------- <br />NOTE: <br />ALL LATH AND LATH <br />ATTACHMENTS TO BE OUT OF <br />CORROSION -RESISTANT MATERIAL <br />3"=1'-0" <br />TAPE EDGE OF HEAD <br />WALL FLASHING <br />STUCCO ON FRAME - 7/8" 3-COAT SAND <br />FINISH STUCCO ON SELF FURRING LATH ON <br />2- LAYERS OF WATER RESISTIVE BARRIER <br />COMPLYING WITH ASTM E2556, TYPE 1 (TYP <br />WALL SHEATHING PER PLAN--_--__ <br />SHINGLE WATER RESISTIVE <br />BARRIER OVER WEEP SCREED <br />WEEP SCREED <br />HEAD WALL TRIM FLASHING TO <br />EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL---- <br />CONT BUTYL TAPE SEALANT PER <br />MANUFACTURER INSTALLATION <br />INSTRUCTIONS <br />'Z' CLOSURE <br />STANDING SEAM METAL <br />ROOF PER SPECS — <br />ROOF UNDERLAYMENT TO <br />TURN UP WALL MIN 8" <br />ROOF SHEATHING <br />PER PLAN <br />3"= 1'-0" <br />z <br />00 <br />HEAD WALL <br />MEN=lm\ <br />STUCCO ON FRAME - 7/8" 3-COAT SAND <br />FINISH STUCCO ON SELF FURRING LATH ON <br />2.• LAYERS OF WATER RESISTIVE BARRIER <br />COMPLYING WITH ASTM E2556, TYPE 1 (TYP <br />_JI:IIJk[H,=1:UjL <br />SHINGLE WATER <br />RESISTIVE BARRIER <br />OVER WEEP SCREED <br />TAPE EDGE OF COUNTER <br />FLASHING <br />WEEP SCREED <br />COUNTER FLASHING <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL <br />SHINGLE PER SPECS <br />STEP FLASHING TO <br />EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />ROOF UNDERLAYMENT TO <br />TURN UP WALL MIN 8"-----\\\ <br />ROOF SHEATHING <br />PER PLAN <br />NOTE: <br />ALL LATH AND LATH <br />ATTACHMENTS TO BE OUT OF <br />CORROSION -RESISTANT MATERIAL <br />STUCCO ON FRAME - 7/8" 3-COAT SAND <br />FINISH STUCCO ON SELF FURRING LATH ON <br />2- LAYERS OF WATER RESISTIVE BARRIER <br />COMPLYING WITH ASTM E2556, TYPE 1 (TYP <br />TAPE EDGE OF RAKE <br />WALL FLASHING <br />WALL SHEATHING PER PLAN-------___ <br />SHINGLE WATER RESISTIVE <br />BARRIER OVER WEEP SCREED- <br />dY4F= 11&'1*0 : I W <br />RAKE WALL STEP FLASHING TO <br />EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />FIELD BEND PANEL UP 1 1/2" <br />CONT BUTYL TAPE SEALANT PER <br />MANUFACTURER INSTALLATION <br />INSTRUCTIONS <br />STANDING SEAM METAL <br />ROOF PER SPECS <br />ROOF UNDERLAYMENT TO \ <br />TURN UP WALL MIN 8"-� <br />y' <br />ROOF SHEATHING <br />PER PLAN <br />NOTE: <br />ALL LATH AND LATH <br />ATTACHMENTS TO BE <br />CONT SELF ADHERED <br />OUT OF CORROSION <br />-RESISTANT MATERIAL <br />FLASHING TURN 3" UP WALL <br />HEAD WALL <br />TAPE EDGE OF HEAD <br />WALL FLASHING <br />FIBER CEMENT SIDING <br />PER ELEVATIONS <br />AV WALL SHEATHING PER PLAN - <br />SHINGLE WATER <br />RESISTIVE BARRIER <br />OVER FLASHING--- <br />STARTER STRIP—--, <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL- <br />18 GA HEAD WALL FLASHING <br />TO EXTEND MIN 8" BEYOND <br />Ar UNDERLAYMENT <br />SHINGLE ROOF PER SPECS - <br />ROOF UNDERLAYMENT TO <br />z TURN UP WALL MIN 8" <br />ROOF SHEATHING <br />00 <br />PER PLAN <br />RAKE WALL <br />WP12 - ROOF <br />3 -1 -0 , <br />TAPE EDGE OF HEAD <br />WALL FLASHING <br />FIBER CEMENT SIDING <br />PER ELEVATIONS <br />WALL SHEATHING PER <br />SHINGLE WATER <br />RESISTIVE BARRIER <br />OVER FLASHING MIN <br />00 <br />STARTER STRIP <br />HEAD WALL TRIM FLASHING <br />TO EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL-- <br />CONT BUTYL TAPE SEALANT PER <br />MANUFACTURER INSTALLATION <br />INSTRUCTIONS <br />00 <br />'Z' CLOSURE <br />ROOF STANDING ETA <br />PER SPECS <br />ROOF UNDERLAYMENT TO <br />TURN UP WALL MIN 8" <br />ROOF SHEATHING <br />PER PLAN <br />RAKE WALL <br />WP14 - <br />3"=1 '-0" <br />�t <br />z <br />00 <br />HEAD WALL <br />HEAD WALL <br />FIBER CEMENT SIDING <br />P'ER ELEVATIONS --- <br />WALL SHEATHING PER PLAN <br />SHINGLE WATER <br />RESISTIVE BARRIER <br />OVER FLASHING--` <br />TAPE EDGE OF COUNTER <br />FLASHING <br />STARTER STRIP <br />COUNTER FLASHING---. <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL <br />SHINGLE PER SPECS-----,, <br />STEP FLASHING TO <br />EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />ROOF UNDERLAYMENT TO <br />TURN UP WALL MIN 8" <br />ROOF SHEATHING <br />PER PLAN <br />FIBER CEMENT SIDING <br />PER ELEVATIONS <br />TAPE EDGE OF RAKE <br />WALL FLASHING <br />WALL SHEATHING PER PLAN — <br />SHINGLE WATER <br />RESISTIVE BARRIER <br />OVER FLASHING MIN <br />STARTER STRIP <br />RAKE WALL STEP FLASHING TO <br />EXTEND MIN 8" BEYOND <br />UNDERLAYMENT <br />FIELD BEND PANEL UP 1 1/2 <br />CONT BUTYL TAPE SEALAN' <br />MANUFACTURER INSTALLA- <br />INSTRUCTIONS <br />'Z' CLOSURE <br />STANDING SEAM METAL <br />ROOF PER SPECS -- <br />ROOF UNDERLAYMENT TO <br />TURN UP WALL MIN 8"------- <br />ROOF SHEATHING <br />PER PLAN <br />CONT SELF ADHERED <br />FLASHING TURN 3" UP WALL <br />FLASHING REQUIREMENTS j <br />R730.1 GENERAL. EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A 0 <br />WEATHER -RESISTANT EXTERIOR WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE <br />SHALL INCLUDE FLASHING AS DESCRIBED IN SECTION R703.4. > U <br />O O +� <br />R703.1 .1 WATER RESISTANCE. THE EXTERIOR WALL ENVELOPE SHALL BE DIMENSIONED i Q. O <br />AND CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION OF WATER Q O L <br />WITHIN THE WALL ASSEMBLY BY PROVIDING A WATER-RESISTANT BARRIER BEHIND THE CCf <br />EXTERIOR CLADDING AS REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO � U <br />ft THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR CLADDING. co <br />R703.2 WATER RESISTIVE BARRIER. ONE LAYER OF NO.15 ASPHALT FELT, FREE FROM c: LO O <br />HOLES, COMPLY WITH ASTM D226 FOR TYPE 1 FELT OR OTHER APPROVED 0 cl C O <br />WATER -RESISTIVE BARRIER SHALL BE APPLIED OVER STUDS OR SHEATHING OF ALL O Li- <br />cu <br />EXTERIOR WALLS NO. 15 ASPHALT FELT SHALL BE APPLIED HORIZONTALLY, WITH THE O `� <br />UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS THAN 2 INCHES. WHERE .� O O <br />w JOINTS OCCUR, FELT SHALL BE LAPPED NOT LESS THAN 6 INCHES. OTHER APPROVED U) <br />MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE WATER -RESISTIVE cu 02 c Q <br />BARRIER MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE NO.15 ASPHALT FELT -0 <br />\ OR OTHER APPROVED WATER -RESISTIVE BARRIER MATERIAL SHALL BE CONTINUOUS <br />TO THE TOP OF WALLS AND TERMINATED AT PENETRATIONS AND BUILDING <br />APPENDAGES IN A MANNER TO MEET THE REQUIREMENTS OF THE EXTERIOR WALL <br />ENVELOPE AS DESCRIBED IN SECTION R703.1. <br />R703.7.3 WATER -RESISTIVE BARRIERS WATER -RESISTIVE BARRIERS SHALL BE <br />INSTALLED AS REQUIRED IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD -BASED <br />SHEATHING, SHALL INCLUDE A WATER -RESISTIVE VAPOR -PERMEABLE BARRIER WITH A <br />PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE <br />AF-z INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH THAT EACH LAYER <br />PROVIDES A SEPARATE CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN <br />00 ACCORDANCE WITH SECTION R703.4) INTENDED TO DRAIN TO THE WATER -RESISTIVE <br />�r BARRIER IS DIRECTED BETWEEN THE LAYERS. <br />`' EXCEPTION: WHERE THE WATER -RESISTIVE BARRIER THAT IS APPLIED OVER <br />WOOD -BASED SHEATHING HAS A WATER RESISTANCE EQUAL TO OR GREATER <br />THAN THAT OF 60-MINUTE GRADE D PAPER AND IS SEPARATED FROM THE STUCCO <br />BY AN INTERVENING SUBSTANTIALLY NON -WATER -ABSORBING LAYER OR <br />DESIGNED DRAINAGE SPACE. <br />R703.4 FLASHING. APPROVED METAL FLASHING, VINYL FLASHING, SELF -ADHERED <br />MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING SHALL BE APPLIED <br />SHINGLE -FASHION OR IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. <br />METAL FLASHING SHALL BE CORROSION RESISTANT. FLUID -APPLIED MEMBRANES USED <br />AS FLASHING SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S <br />RAKE WALL INSTRUCTIONS, ALL FLASHING SHALL BE APPLIED IN A MANNER TO PREVENT THE <br />ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE <br />BUILING STRUCTURAL FRAMING <br />W P 13 SE FDA HERED MEMBRANES U EDOAS FLASHING SHALL COMPLY WITH MMA 711. ALL <br />EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT THE JUNCTURE WITH THE <br />BUILDING WALL WITH A SEALANT COMPLYING WITH AAMA 800 OR ASTM C920 CLASS 25 <br />GRADE NS OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, <br />ASTMC1281, MMA 812, OR OTHER APPROVED STANDARD AS APPROPRIATE FOR THE <br />TYPE OF SEALANT. FLUID -APPLIED MEMBRANES USED AS FLASHING IN EXTERIOR <br />WALLS SHALL COMPLY WITH AAMA 714. THE FLASHING SHALL EXTEND TO THE SURFACE <br />OF THE EXTERIOR WALL FINISH. APPROVED FLASHINGS SHALL BE INSTALLED AT THE <br />FOLLOWING LOCATIONS: <br />1. 1. EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT EXTERIOR WINDOW <br />AND DOOR OPENINGS SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL <br />FINISH OR TO THE WATER -RESISTIVE BARRIER COMPLYING WITH SECTION 703.2 <br />FOR SUBSEQUENT DRAINAGE. MECHANICALLY ATTACHED FLEXIBLE FLASHINGS <br />SHALL COMPLY WITH MMA 712. FLASHING AT EXTERIOR WINDOW AND DOOR <br />OPENINGS SHALL BE INSTALLED IN ACCORDANCE WITH ONE OR MORE OF THE <br />FOLLOWING: <br />00 1.1 THE FENESTRATION MANUFACTURER'S INSTALLATION AND FLASHING <br />INSTRUCTIONS, OR FOR APPLICATIONS NOT ADDRESSED IN THE <br />FENESTRATION MANUFACTURER'S INSTRUCTIONS, IN ACCORDANCE WITH <br />THE FLASHING MANUFACTURER'S INSTRUCTIONS. WHERE FLASHING <br />INSTRUCTIONS OR DETAILS ARE NOT PROVIDED, PLAN FLASHING SHALL BE <br />INSTALLED AT THE SILL OF EXTERIOR WINDOW AND DOOR OPENINGS. PAN <br />FLASHING SHALL BE SEALED OR SLOPED IN SUCH A MANNER AS TO DIRECT <br />WATER TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER <br />RESISTIVE BARRIER FOR SUBSEQUENT DRAINAGE. OPENINGS USING PAN <br />FLASHING SHALL INCORPORATE FLASHING OR PROTECTION AT THE HEAD <br />AND SIDES. <br />1.2 IN ACCORDANCE WITH THE FLASHING DESIGN OR METHOD OF A <br />r o0 REGISTERED DESIGN PROFESSIONAL. <br />1.3 IN ACCORDANCE WITH THE OTHER APPROVED METHODS. <br />1.4 IN ACCORDANCE WITH FMA/AAMA 100, FMA/AAMA 200, FMA/WDMA <br />250, FMA/AAMA/WDMA 300 OR FMA/AAMA/WDMA 400. <br />2.2 AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY <br />CONSTRUCTION WITH FRAME OR STUCCO WALLS, WITH <br />PROJECTING LIPS ON BOTH SIDES UNDER STUCCO COPINGS. <br />3.3 UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL <br />COPINGS AND SILLS. <br />4.4 CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM. <br />5.5 WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TO A <br />WALL OR FLOOR ASSEMBLY OF WOOD -FRAME CONSTRUCTION. <br />6.6 AT WALL AND ROOF INTERSECTIONS. <br />RAKE WALL 7.7 AT BUILT-IN GUTTERS. <br />THESE DETAILS ARE GENERIC AND MEANT TO SHOW GENERAL <br />WP 15 FLASHING AND WATERPROOFING METHODS TO BE USED. <br />�d <br />co <br />}� <br />W <br />O <br />O <br />O <br />0 <br />=3 <br />JUN 2 i <br />L <br />o <br />cn <br />V <br />(D <br />cn <br />m <br />Virtual Review Assist. lnc. <br />Mans Review completed <br />for��mplland approved ance with the 2020 <br />-4-0 <br />co <br />w <br />FBC 7th Edition <br />by Debra Aisne Mohr PX2300 <br />¢ <br />z <br />z <br />J <br />SHEET <br />NO. <br />WR 2.0 <br />I -- _—Fii i —1 <br />1 TF <br />