Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14, Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />theid edge of a sink. This would include the receptacle Installed for a washing machine. Receptacle <br />outside dg p g p <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. WEATHERPROOF DUPLEX OUTLET <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />G.F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />?4. FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />O RECESSED LIGHT FIXTURE <br />P.C. LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />�D ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH I CHIMES (OPTIONAL) <br />PB PUSH BUTTON SWITCH (OPTIONAL) <br />[e] PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />a TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />TV TELEVISION (OPTIONAL) <br />❑N 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />]M ELECTRIC METER <br />_Q ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J OPT. CEILING FAN <br />W (1) PHONE LINE, (1) DATA PORT <br />150AI200A INDOOR <br />PANEL CENTER <br />MO <br />200 amp <br />150 amp <br />UNDERGROUND IlDis <br />SERVICE BY POWER CO.----_ <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />#14 to lights & outlets <br />#12 to appliances and GFI <br /># 1 0 to WH <br />#8 to Range <br />#6 to HVAC <br />150=2/0 <br />200=4/0 in 2" Conduit <br />4 Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV.03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS- <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS- <br />U.C. OUTLET <br />SWITCH FOR <br />DISPOSAL <br />SPEC 3 & 4 KITCHEN <br />; --_-LANAI---- I I <br />I I <br />I <br />�;� /^ � I I <br />I I I I <br />I 1 I AC PAD <br />I <�/ w� I WP DISC. <br />GFI GFI i I <br />I <br />• • A • • r^ _---1 <br />^�� qp <br />- <br />I, ' <br />ALT <br />I I AC PAD I VP@ <br />i <br />r - <br />OWNER'S <br />KI FS <br />�B - <br />1 DINING --WP rt \ <br />_._-I r_ <br />LIGHT AS PAR � M��_ -- � -, I a I � - I' SUITE <br />SPECS 50 OPT - - - <br />\M, <br />- 5 - -- - — <br />-_ --- -- LIGHT AS PER �! <br />lr <br />SPECS FI <br />OPT. CLG. FAN/ <br />I <br />LIGHT PRE -WIRE <br />PENDANT r----------- " / <br />LIGHT PER __ I WIC <br />SPECS RECEPT. FOR <br />% �I ALARM SYSTEM <br />�i-..',�, i GFI <br />I GREAT RM -- <br />GFII 1% I=---� Q <br />---Tole <br />- <br />- - I-------- <br />�U.C. OUTLETROUGH-IN FOR OPT. <br />?! - I I GF e J FAN/LIGHT - ------ S.D. <br />T - o <br />SWITCH FOR ' OPT. CLG. FAN/ ° — <br />DISPOSAL ' `LIGHT PRE -WIRE /OPT. CLG. FAN/ <br />GFII - - — - <br />/ -- i LIGHT PRE -WIRE <br />I � I <br />1 <br />I _. 12I <br />B <br />I <br />M <br />_._...-_ .. �. .._. . - I / 6/� <br />PROVIDE PHONE / CABLE r <br />AND OUTLET AT TECH <br />CENTER BEDROOM 4 <br />3 / S.D. <br />� � � � / . M. <br />CH I <br />-- <br />-- Ir r I Af <br />` I IT <br />I <br />S FHI 3 4--II --I -I --I --II - <br />I 11 <br />I I I ; O I I T /IS HII 1 <br />it I I I I II I I I I IT GA I i I I I I I I BI L W I <br />qp <br />/P7V <br />I 1 LL <br />-- - _@ --------- <br />GFI @ 44' <br />W.H. A.F.F. GFI \ H A\FI <br />44 A.F.F. I <br />zWqp <br />qp <br />- <br />- --` <br />JI S.D. S.D. <br />U <br />GARAGE / -- WP IDS I <br />Lt- ►- LIGHT AS I OPT. CLG. FAN/ <br />w PER SPECS GFI I LIGHT PRE -WIRE <br />W � <br />\ GARAG E <br />II / <br />OPT. CLG. FAN/ <br />GARAGE / 1 I LIGHT PRE-WIREI ` <br />GFIENTRY1 = ENTRY <br />r------------------------------� - ; ; BEDROOM 3 I BEDROOM 2 <br />I I - <br />I I I <br />IRRIGATION GFI---- <br />@44"A.F.F.-------- <br />I <br />I I <br />I I <br />- - - - - - - - - - - - - - - - - - - - - - - - - - - - - I I <br />COACH LIGHTS <br />OR PREWIRE AS <br />.` PER SPECS �. <br />n <br />VTR 3" VTR III, <br />III, �I <br />JI I <br />I I <br />I I <br />I i <br />I r� <br />3" VTR III_ <br />I � t <br />I I I I I <br />3" <br />PLUMBING RISER_ <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />ELECTRICAL PLAN <br />SCALE: %4'=1'-0" <br />ItV <br />a <br />:2. <br />� <br />'7 <br />BLit <br />o <br />Li' CL o <br />M CD <br />�.af N ]� <br />3 0 <br />d C= z <br />�a»� <br />cs -. <br />txCj <br />3 <br />� <br />COdv-0 <br />. Cj Q, <br />N C'� <br />c � <br />to v <br />M <br />N <br />0 <br />N <br />Rr <br />_t <br />µ` <br />Z <br />y <br />F." <br />6'6.4. <br />'• <br />1 <br />• <br />' �;gyp. <br />To the best of the Englneefs knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code <br />- <br />Residential 7th Edition. Engineer's signature and seal <br />is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />Q <br />v E N <br />N N 6 — r rn <br />o c 'I'll ak <br />O <br />7 <br />LL <br />N <br />Q�mov <br />ci <br />cA�r�-° L w ' <br />3 W a nw. <br />J U- L a W U <br />z p <br />Z <br />O <br />r N v 0 ❑ <br />O <br />AO <br />W <br />Z <br />IL <br />w Lu O <br />02rM z <br />w <br />Z <br />N coM Z U <br />O F <br />Z <br />< <br />Od <br />El <br />v M � <br />�/1 <br />z N M <br />0 <br />Z � N <br />z o � <br />Q <br />N <br />�3 0 <br />LU <br />C3 <br />0wa <br />m <br />�N <br />r— cn <br />U c <br />y � <br />J E <br />I <br />oo <br />QCID <br />o <br />o <br />w <br />cc <br />U <br />�o <br />Uj z <br />>� <br />Z o <br />on <br />Z <br />IC° to <br />@ <br />g <br />a <br />-0WZ <br />o <br />0< <br />d <br />Qo <br />Z <br />m J <br />oNo <br />00 <br />¢w <br />ZZ <br />W <br />cn <br />T <br />o< <br />goo <br />a <br />m F <br />m <br />az <br />=3 <br />M <br />wF <br />ao <br />v <br />10 <br />03 <br />� <br />-17 <br />> LO <br />J <br />0 <br />V <br />m <br />0 <br />o <br />(0 L o <br />N <br />^ <br />N <br />°o <br />LO <br />N <br />^ 0 <br />° <br />--I <br />N <br />V) co <br />>' <br />LO <br />p <br />LL <br />N <br />M o00 <br />0) <br />L.n <br />r <br />Q <br />L <br />r <br />E <br />N <br />j O <br />� CV <br />VI Lfi <br />o <br />Z <br />Z <br />E N <br />u <br />n <br />o <br />U <br />Q 0 <br />JOB <br />NO: <br />23-04907 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />