Laserfiche WebLink
ROOF DIAPHRAGM NAILING SCHEDULE <br />RIDGE LINE <br />w 15/32" CDX <br />Co <br />PLYWOOD OR <br />7/16" OSB <br />RIDGE LINE <br />140 MPH (ult) 3 SECOND GUST EXPOSURE "C" WIND ZONE 140 MPH (ult) 3 SECOND GUST EXPOSURE "C" WIND ZONE <br />8d RING SHANK NAILS @ 6" O.C. & 8d RING SHANK NAILS @ 6" O.C. EDGES & <br />+ + + + + 4" O.C. @ GABLE END WALL OR GABLE TRUSS 8d RING SHANK NAILS @ 6" O.C. INTERMEDIATE <br />0.113 INCH NOMINAL SHANK DIAMETER 0.113 INCH NOMINAL SHANK DIAMETER <br />RING DIAMETER OF 0.012 OVER SHANK DIAMETER RING DIAMETER OF 0.012 OVER SHANK DIAMETER <br />16 TO 20 RINGS PER INCH 16 TO 20 RINGS PER INCH <br />0.280 INCH FULL ROUND HEAD DIAMETER 0.280 INCH FULL ROUND HEAD DIAMETER <br />2 INCH NAIL LENGTH 2 INCH NAIL LENGTH <br />NOTE: * FOR 8d RING SHANK NAILS 0.113x 2x 3/8" RING SHANK COIL GUN NAILS MAY BE USED <br />1) SEE STRUCTURAL NOTES FOR SHEATHING SPECIFICATIONS AND WIND SPEED. <br />2) END JOINTS OF THE ROOF SHEATHING SHALL BE STAGGERED AND OCCUR OVER FRAMING MEMBER. <br />3) SCHEDULE ASSUMES SHEATHING IS FASTENED DIRECTLY TO SOUTHERN YELLOW PINE OR DOUGLAS FIR OR BETTER. IF ROOF FRAMING CONSISTS <br />OF A LESSER GRADE OF LUMBER, CONTRACTOR MUST CONTACT ENGINEER OF RECORD FOR ALTERNATE NAILING PATTERN. <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />+ + + + <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />o <br />+ + <br />+ + <br />+ + + + + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+CD <br />+ + <br />+ + <br />+ + + + <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + + + + + + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />+ <br />+ + <br />+ + <br />+ + <br />+ + <br />+ + <br />+++ <br />+ <br />+ <br />+ <br />+ + <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />+++ <br />+++ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + + <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />+ + <br />+ <br />+ <br />+ <br />+ <br />/++ <br />+ <br />o <br />+ + <br />+ + <br />+ + + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />T <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + + + <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />++ <br />+ <br />++++++++ <br />+ <br />Backer and Filler Block Dimensions <br />BCI®Joist <br />Backer Block <br />Series <br />Thickness <br />Filler Block Thickness <br />3/4" orp <br />5000s 1.8/1.7 <br />nel <br />wood panels <br />Two 3/4" wood panels or 2 x <br />P — <br />1-1/8" or two 1/2" <br />6000s 1.8/1.7 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 1/2" <br />6500s 1.8/1.7 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 112" <br />602.0 <br />wood panels <br />2x _ + 5/8" or 3/4" wood panel <br />902.0 <br />2x _ lumber <br />Double 2 x — lumber <br />FILL CELL <br />w <br />CONT. #5 > STD. 900 <br />I HOOK <br />BAR <br />STD. 90' HOOK <br />BOND BEAM <br />r, <br />SIMPSON MGT <br />w/(22)10d <br />NAILS TYP. GIRDER TRUSS <br />CONT. #5 <br />BAR 2X TOP PLATE <br />5/8"D <br />#5 CONT. THRU <br />BOLT <br />FROM BOLT <br />FOUNDATION <br />TO HIGHEST <br />____1 BOND BEAM <br />BOND BEAM STEP <br />SCALE: N.T.S. <br />2nd FLOOR <br />INTERIOR/EXT WALL SEE <br />PLAN FOR MORE INFO <br />CONT. BASE PLATE <br />BEARING COLUMN <br />PLYWOOD FLOOR <br />SEE PLAN FOR REQ'D <br />COLUMN AND f/ SHEATHING PER PLAN <br />CONNECTION <br />\ TJI TO BE CUT TO ALLOW <br />f� FOR BLOCKING/TJI <br />MASONRY WALL OR <br />INTERIOR BRG. WALL <br />TJI PER PLAN <br />OTHERWISE SOLID <br />BLOCKING TO MATCH <br />' Solid block all posts from # OF 2nd FLOOR <br />above to bearing below. STUDS <br />SECTION @ INT. BRIG. WALL <br />DOUBLE JOIST <br />CONSTRUCTION <br />(Not required if both loaded equally from above) <br />N.T.S. <br />{ <br />1/8" min. } Small gap 2" min. <br />Filler blocking <br />1/8" gap <br />+ i <br />� <br />2" max. 4" max. Web Stiffener Fastener Schedule <br />- ---- --- <br />i Joist Lolntermediate <br />Series Dept h l d <br />9 1/2 2_8d <br />®__ <br />BCI 5000s 11 7/8' 2-8d 3-8d <br />— <br />14 2-8d 5-$d - <br />Clinch nails - - -- <br />9-1/2" 2-8d � 2-8d � <br />when BCI 6000s®'11-7/8"I 2-8d 3-8d <br />\\ <br />possible �- BC16500s_ 14" 2-8d_8d <br />1) <br />Support back of web during nailing to prevent damage to <br />16" 2-8d 6-8d <br />11 7/8 2-8d 3-8d <br />web -flange connection. <br />- I- 14 2-8d 5-8d <br />BCI - <br />2) <br />Block solid between joists for full length of span. <br />' <br />Tight fit 16' 2-8d 6-8d <br />3) <br />Leave 1/8" gap between top of filler blocking and bottom of top flange. <br />11-7/8" 3-16d <br />2x4/Plywood/OSB web stiffener 2" min. 14"_ 5-16d�5-16d <br />4) <br />Place joists together and nail from each side with 2 rows of 10d nails <br />BCI 90s® j- - <br />_: CONTRACTOR TO PROVIDE 2x TO FILL THE HEIGHT at 12" o.c., clinched when required when Indicated or max. 16" 6-16d 6-16d <br />2x possible. Stagger rows from opposite - Hangers with side nailing. <br />OF THE JOIST ASA REQUIRED LEAVING Yj' GAP @TOP sides by 6". - Hangers with sides not containing WEB STIFFENER <br />top flange of joist. <br />DOUBLE JOIST CONNECTION - Birdsmouth cuts. N.T.S. <br />- Under 2nd floor column w/ loads <br />N.T.S. <br />SQUASH BLOCKS AT INTERIOR <br />BEARING <br />Vertical load transfer =1900 plf max along load bearing wall. <br />Load bearing wall must stack <br />"Non -stacking walls over squash=20 blocks and <br />require additional wall or beam below.* <br />consideration. Check <br />local building <br />code for appropriate 1116 <br />details in One 10d box <br />areas=20 of high or=20 sinker <br />" lateral load. nail each side <br />10 -0 at bearing. <br />TANK -LESS W/H <br />CORNER OF <br />HOME H C G <br />GARAGE SIDE O O O <br />5'-0" <br />STUB -OUT FOR O o o ;n <br />GAS METER _ U <br />0 0 <br />• MEASUREMENTS ARE FROM FINISHED FLOOR <br />• ROUGH -IN GAS TO RIGHT (ALWAYS) - 12" OFF -CENTER <br />• ROUGH -IN ELECTRIC TO LEFT (ALWAYS) - 12" OFF -CENTER <br />GAS CONNECTION DETAIL <br />"ONLY APPLIES TO HILLSBOROUGH AND PASCO COUNTY" <br />RAFTER SPAN TABLE <br />MEMBER SIZE AND SPACING <br />MAXIMUM LENGTH <br />MEMBER CONNECTIONS* <br />2" X 4" @ 16" O.C. <br />T-5" <br />(2)16d TOENAILS <br />2" X 6" @ 16" O.C. <br />10'-8" <br />(2)16d TOENAILS <br />2" X 8" @ 16" O.C. <br />13'-9" <br />(3)16d TOENAILS <br />2" X 10" @ 16" O.C. <br />16-5" <br />1 SIMPSON HTS20 OR 3 16d TOENAILS <br />2" X 12" @ 16" O.C. <br />19'-3" <br />(1) SIMPSON HTS20 OR (4)16d TOENAILS <br />2" X 4" @ 24" O.C. <br />6'-1" <br />(2)16d TOENAILS <br />2" X 6" @ 24" O.C. <br />8'-6" <br />(2)16d TOENAILS <br />2" X 8" @ 24" O.C. <br />11'-0" <br />(2)16d TOENAILS <br />2" X 10" @ 24" O.C. <br />13'-0" <br />(3)16d TOENAILS <br />2" X 12" @ 24" O.C. <br />164" <br />(1) SIMPSON HTS20 OR (3)16d TOENAILS <br />* TOENAIL CONNECTIONS DESIGNED FOR SHEAR ONLY (i.e. RAFTER TO RIDGEBEAM). <br />** SOUTHERN YELLOW PINE, 55 PSF LOADING <br />Squash block / <br />(2x4 minimum) I <br />Bearing wall, Versa -Lam LVL or <br />Glulam Beam <br />NO HOLES (EXCEPT <br />KNOCKOUTS) ALLOWED <br />IN BEARING ZONES —) <br />DO NOT cut, notch <br />or drill flanges <br />Boise Joist Blocking <br />Use 3" (10d) nails at 6" o.c. <br />Load bearing walls 7 / <br />(I <br />Provide adequate bearing <br />for each lapped joist. <br />odnails SECTION @ INT. BRIG. WALL <br />N.T.S. <br />MINIMUM SPACING = 2x GREATEST <br />D DIMENSION OF LARGEST HOLE <br />(see table below) (KNOCKOUT EXEMPTS) D <br />(see table below) <br />higher than 15001b. <br />BLOCKING PANEL, INTERIOR <br />Vertical load transfer =1900 plf max. along bearing wall <br />Required on interior walls : for vertical load transfer Plumbing <br />when load bearing - for lateral support when joists <br />meet over wall, or wall stacks directly over wall or <br />beam below Load bearing wall must stack over <br />blocking and wall or beam below.* <br />Joist <br />�When joists meet over wall, provide <br />1 3/4" minimum bearing for each. I -Joist can be offset <br />Use 10dx3" nails at 6"o.c. for all joist <br />blocking panel *Non -stacking walls <br />require additional consideration. — <br />ZO <O <br />6" A ROUND HOLE MAY 6" 6" DO NOT CUT HOLES <br />BE CUT ANYWHERE IN CANTILEVER LARGER THAN 1Y2" <br />THE WEB. PROVIDE AT ROUND IN <br />LEAST 3" OF CLEARANCE CANTILEVERS. <br />FROM OTHER HOLES <br />MINIMUM DISTANCE FROM SUPPORT, LISTED BELOW, IS REQUIRED FOR ALL HOLED GREATER THAN 1Yz" <br />NOTES: <br />1. JOISTS MUST BE PROPERLY DESIGNED TO MEET BUILDING CODE REQUIREMENTS. <br />2. TABLE IS FOR UNIFORMLY LOADED MAXIMUM LOADS OF 40 PSL(LIVE) AND 15 PSF (DEAD) ON SIMPLE SPAN APPLICATIONS ONLY. <br />3. REFER TO JOIST SPECIFIER GUIDE FOR INSTALLATION AND OTHER INFO. <br />4. SELECT A TABLE ROW BASED ON JOIST DEPTH AND THE ACTUAL JOIST SPAN ROUNDED UP TO THE NEAREST TABLE SPAN. SCAN ACROSS <br />THE ROW TO THE COLUMN HEADED BY THE APPROPRIATE ROUND HOLE DIAMETER OR RECTANGULAR HOLE SIDE. USE THE LONGEST SIDE OF <br />A RECTANGULAR HOLE. THE TABLE VALUES IS THE CLOSEST THAT THE CENTERLINE OF THE NEAREST SUPPORT. <br />5. THE ENTIRE WEB MAY BE CUT OUT. DO NOT CUT THE FLANGES. HOLES APPLY TO EITHER SINGLE OR MULTIPLE JOISTS IN REPETITIVE <br />MEMBER CONDITIONS. <br />6. FOR MULTIPLE HOLES, THE AMOUNT OF UNCUT WEB BETWEEN HOLES MUST EQUAL AT LEAST TWICE THE DIAMETER (OR LONGEST SIDE) OF <br />THE LARGEST HOLE. <br />7. %" ROUND KNOCKOUTS IN THE WEB MAY BE REMOVED BY USING A SHORT PIECE OF METAL PIPE AND HAMMER. <br />8. HOLES MAY BE POSITIONED VERTICALLY ANYWHERE IN THE WEB. THE JOIST MAY BE SET WITH THE %" KNOCKOUT HOLES TURNED WITHER <br />UP OR DOWN. <br />9. THIS TABLE WAS DESIGNED TO APPLY TO THE DESIGN TO APPLY TO THE DESIGN CONDITIONS COVERED BY TABLES ELSEWHERE IN HIS <br />PUBLICATION. USE THE BC CALC SOFTWARE TO CHECK OTHER HOLE SIZES OR HOLES UNDER OTHER DESIGN CONDITIONS. IT MAY BE <br />POSSIBLE TO EXCEED THE LIMITATIONS OF THIS TABLE BY ANALYZING A SPECIFIC APPLICATION WITH THE BC CALC SOFTWARE. <br />HOLE CUTTING CHART <br />N.T.S. <br />up to 3" to avoid <br />vertical plumbing <br />3" max <br />JOISTS OFFSET <br />N.T.S <br />Jc <br />I.0 <br />SIMPS( <br />w/(22) <br />NAILS 1 <br />TYPICAL SIMPSON MGT TO <br />BUILT-UP COLUMN DETAIL <br />TYPICAL SIMPSON LUS/HUS/HUC <br />INSTALLATION <br />MIN. EMBEDMENT <br />SCHEDULEFOR <br />AND QUANTITY <br />)F FASTENERS <br />TYPICAL SIMPSON HETA20 / <br />HETAL20 INSTALLATION <br />A/C CHASE 4" PVC <br />SLEEVE THRU STEM <br />WALL <br />Backer block (12" wide min.) <br />Nail with 10-10d nails. <br />Install tight to top flange. SLEEVE THRU STEM ° <br />SEE PLAN FOR---'°. a . • ° <br />FOUNDATION INFO ° <br />*A <br />,�I <br />STEM FOUNDATION <br />\�V/ "ICI Filler block. <br />Nall with <br />10-10d nails. <br />Backer block required where top <br />mount hanger load exceeds 250 lbs. <br />Install tight to top flange. <br />1/4"-2" gap <br />KBacker Block <br />"Top Mount" "Face Mount" <br />Backer block shall be tight Backer block shall be tight <br />to bottom of top flange with to top of bottom flange with <br />1/4"-2" gap at top of bottom 1/4"-2" gap at bottom of top <br />flange. flange. <br />eb stiffner as <br />Web stiffeners are not required when top required if hanger <br />flange is laterally supported by joist hanger. doesn't meet <br />height <br />- -- requirements <br />-0 6 X Joist <br />c " p/ / depth <br />I -JOISTS BUCKETS <br />N.T.S. <br />GRADE <br />a <br />r--REINF. SEE PLAN <br />(2) #5 REBAR <br />A/C CHASE 4" PVC <br />SLEEVE THRU FOOTING <br />MONO FOUNDATION <br />TYP. FND. PENETRATIONS <br />SCALE: N.T.S. <br />SIMPSON HETA20 / HETAL20 <br />INSTALLATION @ MID SPAN <br />NOTE: <br />UPLIFT VALUE <br />IS BASED ON <br />S.P.F. <br />LOCATION OF <br />SECOND H10A <br />SIMPSON H10A (WHEN <br />w/ (18)10d x 1 1/2" ° REQUIRED) <br />NAILS <br />UPLIFT =1015# <br />TYPICAL SIMPSON H10A <br />INSTALLATION <br />TYPICAL SIMPSON MTS <br />/ HTS INSTALLATION <br />TOP (2) #5's x 4'-0" <br />CENETERED @ PIPE <br />PENETRATION <br />WE"i"1111�► <br />PLUMBING LINE <br />PVC OR SCH40 SLEEVE <br />�— SEE FND. PLN. <br />SIZE & REINF. <br />12" BELOW PIPE VERTICAL THRU FND. <br />GRADE <br />. ._�-,,11 <br />PVC OR SCH40 SLEEVE <br />TOP (2) #5's x 4' 0" <br />CENETERED @PIPE <br />PENETRATION PLUMBING LINE <br />a ° .d <br />a ° <br />co Z • • <br />° <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE PERPENDICULAR TO FND. <br />TOP (2) #5's x 4'-0" PVC OR SCH40 SLEEVE <br />CENETERED @ PIPE <br />PENETRATION PLUMBING LINE <br />d a' d ° <br />a a. °� °< G <br />a — <br />— — Q <br />< jiTl I <br />• <br />SEE FND. PLN. <br />SIZE & REINF. <br />I <br />CO <br />Fj <br />C1J <br />( J � o <br />' � <br />`•. F 1- <br />.......... <br />�... <br />SS�01a <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 <br />Florida Building Code - <br />Residential 6th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />9 <br />W <br />Q <br />d E m rb <br />8 N (p ap <br />00 6 N it <br />5 <br />G <br />- <br />Pc #�� <br />-9 w <br />M <br />w <br />rnF- '0 LLJ a <br />U. <br />Q <br />y"MM W N <br />"" LL ° it <br />0�o <br />tY m 0 <br />Lwoa <br />W <br />C4w <br />Z <br />LL <br />r°2O_jO' <br />o nQ <br />coN O <br />+ Z N Z <br />0O0 --r <br />V M V <br />Z N <br />�Q <br />z <br />� <br />Q <br />a <br />Ln <br />N <br />M <br />z <br />c� o <br />C1 <br />LL <br />4-1 <br />f- <br />N <br />W N <br />� a <br />V <br />Ow <br />V) <br />C� 4 <br />w <br />EE <br />8 <br />! <br />h 1'h <br />S L:16 <br />c N z <br />- <br />414-1 <br />o <br />w <br />M <br />M <br />¢ <br />o <br />z <br />J <br />U_ <br />E <br />m <br />� o <br />c <br />" <br />Z, <br />Q <br />o <br />E v <br />E <br />oz <br />uo <br />Fto <br />o E <br />.0o <br />p< <br />ao <br />° <br />�Z <br />z <br />NW� <br />. n7 <br />Cl)7 <br />U <br />2 <br />0 <br />2 <br /><Z <br />z <br />J <br />- <br />aI <br />QW <br />sz <br />CO <br />a 3 <br />Q <br />SM° <br />aZ <br />ww <br />W <br />U� <br />�k <br />Milli!cfl <br />o <br />w <br />X0 <br />>° <br />a <br />eY <br />za <br />03 <br />�M <br />0 <br />= <br />E <br />>� <br />cc <br />W <br />\ <br />m <br />� <br />' <br />T <br />^ <br />C^ <br />O <br />V <br />W m <br />c <br />T <br />Np <br />TLO <br />T_ <br />I o <br />� (3) <br />r <br />T' <br />N <br />6 <br />Z <br />m <br />Z <br />E <br />N <br />a <br />E <br />U <br />hi <br />Q p <br />JOB <br />NO : <br />20-6579 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />SN 1 <br />