Laserfiche WebLink
FOLD UP WEATHER <br />RESISTIVE BARRIER & WEATHER RESISTIVE AFLASHING REQUIREMENTS <br />TEMPORARILY SECURE BARRIER WINDOW UNIT <br />DOOR ROUGH OPENING <br />WEATHER SLOPE <br />RESISITIVE R703.1 General. Exterior walls shall provide the building with a weather -resistant exterior wall envelope. The exterior wall envelope shall <br />BARRIER 0.3 In : 12.0 In <br />WOOD FRAME CONSTR. include flashing as described in Section R703.4. A water -resistive barrier is described as a material behind an exterior wall covering that is <br />TAPE EXTERIOR SELF -ADHERED FLASHING 3/4"-1" BEAD OF CONSTR. (0.6 Cm : 30.cm) <br />a SHEATHING BY LAPPING DOWN ADHESIVE TO BE APPLIED UNDER SELF -ADHERED FLASHING intended to resist liquid water that has penetrated behind the exterior covering from further intruding into the exterior wall assembly. An <br />OVER RIM JOIST AND UP THRESHOLD OF DOOR AND exterior wall covering is described as a material or assembly of materials applied on the exterior side of exterior walls for the purpose of <br />WALL BY 6 IN. RETURN UP JAMB 6". USE LIQUID EXTERIOR providing a weather -resistive barrier, insulation, or for aesthetics, including but not limited to, veneers, siding, exterior insulation and finish <br />tnsseae�eowleoow� NAIL BRAND OR EQUAL WEATHER p g 9 g+ <br />2 _ PROOF CAULKING CEMT. FIN. systems, architectural trim and embellishments such as cornices, soffits, and fascias. <br />O WEATHER lJ SELF -ADHERED FLASHING BUILDING PAPER <br />RESISITIVE <br />s BARRIER SEAL TOPS OF JOISTS WIRE LATH <br />UNDER DECKING 1 R703.2 Water -resistive barrier. One layer of No. 15 asphalt felt, free from holes and breaks, complying with ASTM D226 for Type 1 felt or <br />(SEE DETAIL WP07) SUBFLOOR other approved water -resistive barrier shall be applied over studs or sheathing of all exterior walls. Such felt or material shall be applied <br />SELF -ADHERED FLASHING horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm). Where joints occur, felt shall be lapped not less <br />HEAD FLASHING TIE-IN INSTRUXTIONS: than 6 inches (152 mm). The felt or other approved material shall be continuous to the top of walls and terminated at penetrations and <br />1. Cut, fold up &temporarily secure weather RIM JOIST building appendages in a manner to meet the requirements of the exterior wall envelope as described in Section R703.1. <br />THESE DETAILS ARE GENERIC AND resistive barrier above header to allow for <br />flashing installation <br />MEANT TO SHOW GENERAL FLASHING 2. Self -adhered flashing plus head flashing under R703.7.3 Water -resistive barriers shall be installed as required in Section R703.2 and, where applied over wood -based sheathing, shall <br />AND WATERPROOFING METHODS TO weather resistive barrier 1 1 include a water -resistive vapor -permeable barrier with a performance at least equivalent to two layers of Grade D paper. The individual <br />BE USED. 3. Fold weather resistive barrier back over head 2 2 ^ layers shall be installed independently such that each layer provides a separate continuous plane and any flashing (installed in accordance <br />flashing and seal with tape v with Section R703.4) intended to drain to the water -resistive barrier is directed between the layers. <br />3/8" CEMENT <br />PLASTER <br />12 MIL DRYLOK <br />CMU - MASONRY BLOCK <br />EXTREME <br />WINDOW <br />FASTENER <br />1) SEALANT AT <br />4) SEALANT JOINT <br />WINDOW BUCK TO <br />OUTSIDE EDGE OF <br />'' MASONRY <br />WINDOW BUCK <br />c <br />2) SEALANT JOINT <br />5) SEALANT FROM <br />INSIDE EDGE OF <br />WINDOW FRAME <br />WINDOW BUCK <br />ACROSS WINDOW BUCK <br />AND EXTEND TO <br />WINDOW FRAME <br />MASONRY <br />ATTACHED <br />PER CODE <br />6) TOOLED SEALANT <br />REQUIREMENTS <br />BEAD BRIDGING <br />CLADDING AND WINDOW <br />FRAME <br />3) SEALANT WINDOW FRAME TO <br />WINDOW BUCK ALL THE WAY <br />AROUND, INCLUDING SILL. <br />SCS 06_05 CMU INSTALLATION 6 POINT BUCK AND <br />FENESTRATION INSTALLATION AND INTERFACE <br />JAMB, SILL AND HEAD DETAIL <br />APPROVED SHEATHING <br />APPROVED HOUSEWRAP <br />STRUCTALATH TWIN TRACK 2.5 <br />3/4" CEMENT PLASTER <br />12 MIL (min) DRYLOK EXTREME <br />APPROVED FLASHING TAPE <br />"V" SEALANT SOCKET WITH <br />TOOLED APPROVED SEALANT <br />S <br />DO NO- <br />BOTTO <br />FLANGE <br />SELF -ADHERED FLASHING Scale: NTS <br />FLANGED WINDOW <br />FLASHING INSTALLATION AFTER WEATHER RESISTIVE BARRIER <br />SELF -ADHERED FLASHING <br />HALF ROUND WINDOW <br />1 1P'IV1111 - 1 L/ l 111N1 <br />SCS 06 02 WINDOW FIN INTERFACE WITH <br />SELF -ADHERED FLASHING <br />EXTRUDED SHOULDER <br />DECK JOIST <br />SELF -ADHERED FLASHING <br />2xFRAMEWALL-----_ <br />PRODUCTS DETAILS <br />TILE FINISH---_ <br />TWO LAYERS OF FELT OR ONE LAYER OF HOUSE WRAP AND <br />ONE LAYER OF FELT ARE REQUIRED BEHIND STUCCO. FBC <br />1/2" DUROCK�-_ <br />R703.2.1 AND FBCR 703.7.3 <br />Detail Instructions <br />Refer to the number marked as ## in each detail that corresponds to the <br />numbered items in the list of instructions below: <br />1. Install self -adhered flashing in order as shown by numbers <br />8" CMU <br />2. Install flashing and weather resistive barrier to form water shedding <br />laps <br />e <br />4" OR 8" CMU <br />3. Self -adhered flashing can be substituted for building paper <br />(PER SEAT DEPTH) <br />4. Split the release paper using the ripcord (Split release on demand, <br />FILL WITH GROUT <br />embedded in the adhesive layer) - for ease of installation and to <br />_ <br />minimize scoring cuts <br />a <br />5. Remove all release paper per standard installation instructions and <br />adhere to substrate using a square piece of flashing material (6" x 6" <br />Minimum) <br />SLOPED MUD BED <br />6. Fold as shown by arrows <br />° <br />7. Angle of corner may vary, adjust folding of the flashing accordingly to <br />4 <br />fit tight to corner <br />VINYL SHOWER PAN a <br />8. Mechanically fasten as necessary <br />SLOPE <br />d ° u <br />4 <br />a <br />SELF -ADHERED FLASHING <br />EXTERIOR DOOR WITH DECK - SECTION A <br />EXTERIOR SHEATHING <br />3/4"-1" BEAD OF CONSTR. <br />ADHESIVE TO BE APPLIED UNDER <br />THRESHOLD OF DOOR AND RETURN <br />UP JAMB 6". USE LIQUID NAIL BRAND <br />OR EQUAL WEATHER PROOF CAULKING <br />SECTION -A (SEE DETAIL WP02) <br />\SHING <br />SELF -ADHERED FLASHING <br />1 0 <br />2 SEAL TOPS OF JOISTS <br />UNDER DECKING <br />(SEE DETAIL WP07) <br />SELF -ADHERED FLASHING <br />EXTERIOR DOOR WITH DECK <br />E <br />AM <br />SELF-ADHER <br />W <br />1'4" PER PLAN <br />1'-0" PER PLAN <br />in <br />SHOWER SEAT <br />SELF -ADHERED FLASHING <br />OUTSIDE CORNER <br />Z <br />Exception: Where the water -resistive barrier that is applied over wood -based sheathing has a water resistance equal to or greater <br />1 <br />SELF -ADHERED FLASHING <br />CEMT. FINISH SILL/ POTSHELF/ CHIMNEY SHOULDER 1 <br />than that of 60-minute Grade D paper and is separated from the stucco by an intervening, substantially nonwater-absorbing layer or <br />designed drainage space. <br />R703.4 Flashing. Approved corrosion -resistant flashing shall be applied shingle -fashion in a manner to prevent entry of water into the wall <br />g pP g pp 9 p rY <br />MECHANICALLY FASTEN IF RUBBERIZED RUBBERIZED ASPHALT <br />NEEDED IN CORNERS ADHESIVE <br />INSTALL RED <br />FLASHING JAMB &HHEAD <br />THROUGH SELF -ADHERED ASPHALT ADHESIVE <br />cavity penetration of water to the building structural framing components. Self -adhered membranes used as flashing shall comply with <br />cavi or en g g p g p y <br />FLASHING, SEE <br />FLASHING SELF -ADHERED FLASHING---,,,,,AAMA <br />711. All exterior fenestration products shall be sealed at the juncture with the building wall with a sealant complying with AAMA 800 or <br />FLANGED WINDOW <br />(SEE DETAIL WP01) <br />ASTM C920 Class 25 Grade NS or greater for proper joint expansion and contraction, ASTM C1281, AAMA 812, or other approved standard <br />SCORED <br />as appropriate for the type of sealant. Fluid -applied membranes used as flashing in exterior walls shall comply with AAMA 714. The flashing <br />RELEASE PAPER <br />shall extend to the surface of the exterior wall finish. Approved corrosion resistant flashings shall be installed at the following locations: <br />SELF -ADHERED FLASHING, <br />��o (BEFORE FOLDING, SCORE <br />1. Exterior window and door openings. Flashing at exterior window and door openings shall extend to the surface of the exterior wall <br />EXTEND A MINIMUM 6" <br />PAPER TO <br />RELEASEDH SVEASSHOWN) <br />finish or to the water -resistive barrier complying with Section 703.2 for subsequent drainage. Mechanically attached flexible flashings <br />VERTICALLY FROM <br />BOTTOM OF <br />shall comply with AAMA 712, Flashing at exterior window and door openings shall be installed in accordance with one or more of the <br />THRESHOLD <br />following: <br />1.1 The fenestration manufacturer's installation and flashing instructions, or for applications not addressed in the fenestration <br />manufacturer's instructions, in accordance with the flashing manufacturer's instructions. Where flashing instructions or <br />> <br />details are not provided, pan flashing shall be installed at the sill of exterior window and door openings. Pan flashing shall be <br />sealed or sloped in such a manner as to direct water to the surface of the exterior wall finish or to the water resistive barrier <br />2 <br />for subsequent drainage. Openings using pan flashing shall incorporate flashing or protection at the head and sides. <br />5 <br />1.2. In accordance with the flashing design or method of a registered design professional. <br />4 <br />1.3. In accordance with other approved methods. <br />1 <br />6 <br />1.4 In accordance with FMA/AAMA 100, FMA/ AAMA 200, FMA/WDMA 250, FMA/AAMA/ WDMA 300 or FMA/AAMA/WDMA <br />400. <br />2 <br />7 <br />2. At the intersection of chimneys or other masonry construction with frame or stucco walls, with projecting lips on both sides under <br />stucco copings. <br />' <br />SELF -ADHERED FLASHING <br />1 <br />3. Under and at the ends of masonry, wood or metal copings and sills. <br />INSIDE CORNER • <br />4. Continuously above all projecting wood trim. <br />5. Where exterior porches, decks or stairs attach to a wall or floor assembly of wood -frame construction. <br />�Ground� <br />6. At wall and roof intersections. <br />7. At built-in clutters. <br />=LF-ADHERED FLASHING <br />ITCH <br />HERED FLASHING <br />1 <br />2 <br />4 <br />5 <br />g g <br />uJ Lu PLASTER STOP <br />_ CONTINUOUS BACKER-� <br />0 W ROD & SEALANT <br />w Lu <br />= W <br />Q Lu <br />W <br />� ° A <br />U) <br />a <br />e <br />FOUNDATION WEEP SCREED <br />STRIP OF SAF <br />DRAINAGE PLANE WRB <br />BOND BREAK WRB <br />SF LATH <br />WRAP DP WRB ONTO <br />THE VERTICAL <br />SURFACE TO TOP OF <br />FLANGE AS AN AIR <br />BARRIER <br />3-1/2" INCH FLANGE <br />Ha <br />THIS GAP IS A RESULT OF <br />NATURAL SHRINKAGE. <br />DO NOT SEAL. <br />DRIP SCREED PLASTIC <br />ACCESSORY <br />SOFFIT/CANTILEVER <br />Water Resistant Barrier <br />Lath <br />Sheathing <br />Stucco <br />LEGEND <br />SELF ADHERED FLASHING (SAF) o <br />DRAINAGE PLANE (DP) WEATHER RESISTANT <br />BARRIER (WRB) - <br />BOND BREAK WEATHER RESISTANT BARRIER - <br />SELF FURRING (SF) LATH <br />PLASTER ACCESSORY <br />SHEATHING,'OSB', PLYWOOD, DENSGLASS <br />kSTER STOP A <br />NTINUOUS BACKER ROD <br />EALANT <br />MENTITIOUS FINISH <br />STRUCTURAL FRAMING <br />STRUCTURAL SHEATHING <br />STRIP OF SAF <br />DRAINAGE PLANE WRB <br />BOND BREAK WRB <br />SF LATH <br />FHESE DETAILS ARE GENERIC AND MEANT TO SHOW GENERAL <br />FLASHING AND WATERPROOFING METHODS TO BE USED. <br />Cement Plaster <br />in accordance <br />with ASTMC926 <br />over wood 2nd <br />floor <br />Cement <br />Plaster <br />over block <br />1 st floor <br />7/8" Cement Plaster <br />in accordance with <br />ASTMC926 <br />- Felt backed metal <br />lathe in accordance <br />with ASTMC1063 <br />Building Paper <br />-7/16" O.S.B. <br />sheathing <br />Metal <br />Flashing <br />Weep Screed <br />Installed As Per <br />Manufact. Specs. <br />Maintain <br />Bottom of <br />Weep Screed <br />1 1/2" to 2" <br />Above Roof <br />Sheathing <br />Note: <br />The building paper and metal lath must be <br />installed over the top of the weep screed. <br />WEEP SCREED DETAIL <br />SCALE: NOT TO SCALE <br />7/8" Cement Plaster <br />in accordance with <br />ASTMC926 <br />Felt backed metal <br />lathe in accordance <br />with ASTMC1063 <br />Building Paper <br />7/16" O.S.B. <br />sheathing <br />.Stampede or similar <br />cauk bottom <br />joint only <br />Weep Screed <br />Installed As Per <br />Manufact. Specs. <br />1/2" Cementitious <br />Decorative Finish <br />All inside and <br />outside corner will <br />need to be miter <br />cut and caulked all <br />butt joints need to <br />becaulked using <br />Stampede or sim. <br />caulk for all <br />0 <br />N <br />O <br />N <br />N <br />0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained <br />within these <br />drawings comply with the 2017 <br />Florida Building Code - <br />Residential 6th Edition. Engineer's signature and <br />seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />•i <br />00 E <br />V <br />'t 8 <br />O <br />o1_p <br />CIO <br />N *k <br />N <br />0 <br />N J <br />u- -J u; <br />U) `C <br />M MLu <br />u- <br />LL a <br />y <br />�4 <br />ej <br />NLJL� <br />W N <br />a a Lu <br />Z <br />m c 0" <br />2 O <br />O H <br />o <br />O O <br />Z <br />LLW <br />5 <br />N Z <br />jQ a <br />U 0 J <br />Z <br />M <br />O U <br />❑ll❑ <br />N <br />N M <br />'o o <br />z <br />z o <br />Q <br />J - <br />a. <br />cn <br />N <br />M <br />z <br />(1) <br />(-D o <br />a--+ <br />w <br />� <br />V <br />OLU <br />S <br />�y N <br />X <br />co <br />v <br />w <br />J E <br />t B <br />fv <br />v N <br />Q <br />m <br />N <br />I� <br />o <br />w <br />M <br />M <br />z <br />o <br />Z <br />UL J <br />i? E <br />O <br />E U <br />� ¢ <br />o o <br />wz <br />Y <br />za <br />oa <br />(O <br />C <br />O <br />UO <br />t- <br />XU <br />a <br />�U <br />O� <br />N�o <br />Qo <br />WW <br />-- TT <br />ci cr <br />C <br />z <br />U <br />" <br />m2 <br />o <br />of <br />ZI <br />w J <br />m <br />¢ <br />Q W <br />�Z <br />y <br />>> <br />rw <br />o <br />O <br />U <br />�jj <br />Q <br />d <br />�W <br />ci 3 <br />�0 <br />oZ <br />F� <br />3 <br />A <br />� <br />�W <br />g <br />CO <br />V <br />1. <br />Z< <br />a <br />OU3 <br />2N <br />0 <br />= <br />> d' <br />m <br />W <br />m <br />Ln <br />O <br />� <br />W Co <br />= <br />� <br />r <br />O N <br />N <br />LO <br />r <br />+Lo <br />N <br />r <br />000 <br />N <br />o <br />E <br />m <br />'E <br />:3 <br />Z <br />E O <br />m <br />d <br />E <br />U J <br />Q <br />J <br />JOB <br />NO: <br />20-8071 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />W P <br />