ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general). In a Flood Zone, all electrical equipment to be at or above DFE. <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 44" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC. <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2014 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FqT <br />DUPLEX OUTLET ABOVE COUNTER <br />[@.WP <br />WEATHERPROOF DUPLEX OUTLET <br />GFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />P4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />POWER CO. <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEC 14, 250.94 <br />200A INDOOR PANEL <br />CENTER <br />10 N14 copper to lights & outlets <br />NEMA 1 <br />200 AMP <br />01 #12 copper to 20 amp clue <br />#10.2 copper to WH <br />lk10-3 copper to Dryer <br />METER <br />MO/0 <br />or <br />4/0 SER Alu <br />200 amp <br />150 amp <br />Bare Cu Ground <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram (updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />WP GFI DISC. <br />H. <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />Unnn oeo eoE:nc <br />ip <br />EXHAUST FAN <br />—db _Q <br />I <br />W.H. VERIFY LOCATION <br />GFA I <br />-----J <br />ELECTRICAL PANEL <br />"W"EXHAUST <br />FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />III <br />1111111111111111j111111111111 <br />1111111'" <br />111 <br />17=11 <br />111111 <br />RECEPT. <br />CH <br />CHIMES (OPTIONAL) <br />FOR ALARM VERIFY METER <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />SYSTEM LOCATION WITH <br />BUILDER <br />�D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />©2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />0 <br />THERMOSTAT <br />ELECTRIC METER <br />NMI <br />ELECTRIC PANEL <br />—� <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />G J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G T J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />ELECTRICAL PLAN - ELEV-B1 <br />SCALE:1/4"=V-0" <br />0 <br />CV <br />0 <br />CV <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained <br />within these <br />drawings comply with the 2017 <br />Florida Building Code - <br />Residential 6th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />N <br />W <br />, <br />O "T V <br />O O <br />p <br />00 <br />��(0 <br />N j <br />N Rt <br />o <br />v <br />Cc,O ) <br />r C <br />M N r- 0) <br />t J <br />1 N <br />* ao LL <br />C <br />N <br />.�COM <br />7LL� <br />J W <br />a <br />♦» <br />Q <br />Z< <br />u1 M <br />rt Co i- <br />-&_,o <br />LL <br />W to <br />' ir <br />a a <br />m00 <br />toa)o <br />W <br />EO1Qt <br />Boa <br />ILZ <br />N ° <br />N Q M Z <br />a oLn <br />Z <br />U H J <br />❑❑❑ <br />W <br />M c�- <br />Z N O <br />� O <br />O QQN <br />Z � Q <br />Q M <br />� N <br />t/1 <br />M <br />Z <br />a--+ <br />f� <br />•0 <br />g <br />u, g <br />o Q <br />w <br />c� <br />E <br />E <br />�N <br />0 <br />C 00 <br />m <br />Rig�— <br />T E <br />O <br />C o y <br />c 4) <br />® <br />0 <br />Q o <br />sm <br />o <br />� <br />w <br />M <br />CM <br />mz <br />o S <br />Z <br />Q <br />J <br />zo <br />Q <br />E <br />o0 <br />w <br />z® <br />O a <br />I_ <br />x0 <br />0o <br />0 <br />o <br />N M <br />ao <br />wo <br /><o <br />�Q <br />wW <br />(� <br />c) c <br />- <br />0r <br />�m <br />m� <br />oO <br />1 <br />>z <br />J <br />¢ro <br />"z <br />rn <br />o� <br />�z <br />U <br />d <br />H <br />a <br />Aw <br />U <br /><o <br />oz <br />tik <br />=3 <br />�O <br />o <br />co <br />v <br />w� <br />z< <br />d <br />°3 <br />0 <br />2N <br />= <br />L <br />B <br />n, <br />W <br />� <br />0 <br />\ <br />./ <br />Q <br />Q <br />> <br />QL <br />o <br />^ <br />c <br />T <br />0 <br />J <br />T <br />:, <br />LO <br />.L Q <br />O � <br />r <br />(0 <br />CD <br />ai <br />z <br />w <br />T <br />` <br />M <br />o <br />Z <br />E <br />E <br />c <br />d <br />U _j <br />Q 0 <br />� <br />JOB <br />NO: <br />20-2742 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />I I1 <br />