V <br />ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />200A INDOOR PANEL <br />CENTER <br />10 k14 copper to lights & oudets <br />NEMA t <br />200 AMP <br />10 p12 copper to 20 amp ckts <br />10 fl10-2 copper to WH <br />10 #10-3 copper to Dryer <br />METER <br />MAIN <br />0 <br />2/0 or <br />4/0 SER Alu <br />200 amp <br />150 amp <br />POWER CO. FEED----_ <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEC 14, 250.94 <br />4 Bare Cu Ground <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />GENERAL ELECTRICAL NOTES: Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general) <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 42" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2014 NEC, 406.11 <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2017 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FF <br />DUPLEX OUTLET ABOVE COUNTER <br />06 <br />WEATHERPROOF DUPLEX OUTLET <br />GFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />+PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUSTFAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />kD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />Tq 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />I� <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />G J <br />`Q\ 19 <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />(✓ T J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />U <br />C.M <br />/ Y � <br />PA IO �� j CAFE <br />OWNER'S Sl'T� ITE <br />/ ROUGH -IN FOR / <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />u C-r <br />f <br />FAMILY RM <br />ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />U.C. OUTLET <br />FOR DW <br />U.C. OUTLET <br />T_T_TZ I ___FT <br />GFI <br />GFI C- -1-------- GF <br />laD. <br />' INK / DIS <br />PENDANT AS <br />PER SPECS \ <br />� r <br />AC PAD <br />WID H.B. <br />GFI DISC. <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />RECEPT. <br />FOR ALARM <br />SYSTEM <br />VERIFY METER <br />LOCATION WITH <br />BUILDER H. <br />LJ IRRIGATION ----- -----� VERIFY LOCATION GFI @ 44" A.F.F <br />--- <br />._ <br />W H ELECTRICAL PANEL I I I <br />O I II <br />W.I.C. I I I l <br />I I I I <br />I I I <br />2 CAR GARAGE <br />I I I <br />I I I <br />GFI FOR I I <br />GAR. DOOM <br />GFI I I I <br />GFI @ 44" I I I <br />A.F.F. I I I <br />I I I 11 <br />-----------J <br />I 11 I I I I <br />I }I I I I I <br />JOPT. OPT. <br />_ I I I <br />D. <br />lip .0 <br />I I <br />-- L------------ <br />AHU GFI @ 44" <br />A.F.F. <br />�TDJCH <br />I <br />_ I <br />IENTRY <br />07 <br />------- AGA <br />3 3 <br />— — — S.D. _ S.D. <br />C.M <br />I <br />OPT. <br />RED BEDROOM 2 S.D. F' <br />BEDROOM 3/ 11, <br />\ BEDROOM 4 <br />GFI <br />OUGH-IN FOR �/ /� I i \ ROUGH -IN FOR <br />OPT. CLG. FAN/ y �\ OPT. CLG. FAN/ <br />VV <br />\ <br />LIGHT PRE -WIRE !%h `LIGHT PRE -WIRE <br />ROUGH -IN FOR I <br />OPT. CLG. FAN/ <br />/ LIGHT PRE -WIRE <br />MAIN FLOOR ELECTRICAL PLAN <br />SCALE: Y4"=1'-0" <br />\ <br />Lr— <br />rf[ �0ma <br />i n , <br />0 <br />I� <br />z N $ <br />z 0 <br />J M <br />d N <br />E3 <br />M <br />� z <br />N (D LL <br />4—J � ca <br />C6 W o <br />[� <br />E <br />o <br />r— <br />U C° <br />` E <br />m�..., <br />s r <br />U 'o N <br />c <br />¢ e <br />° <br />N N <br />0 o N Q w z <br />M d <br />�ZN <br />Z � �M� Zo0 w <br />0' <br />W y� tiz a <br />us a' cCL <br />ch <br />Z C moo¢"0 <br />-NS r� <br />H 2 9 rn m C <br />Q <br />a Q <br />W �a�c <br />ZLL <br />00 <br />rn <br />0 <br />N <br />O <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 Florida Building Code - <br />Residential 6th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />o <br />M <br />w <br />Z <br />M <br />z <br />g <br />u <br />E <br />�o <br />» <br />Z <br />ry <br />Za <br />Q O <br />w1 <br />o E <br />o <br />U <br />ra <br />r10 <br />0� <br />0 OU <br />°o< <br />N <br />wo <br />az <br />aZ <br />�� <br />® <br />d L <br />m <br />ZZ <br />O y <br />U <br />�m <br />m0 <br />� <br />O LL <br />Z <br />o <br />GW <br />N 3 <br />0 <br />g° <br />a <br />Z 3 <br />�F <br />U <br />�� <br />�� <br />X� <br />�i <br />w <br />¢2 <br />x3 <br />W 0 <br />l� <br />O <br />zl¢ <br />a x <br />10 3 <br />2O <br />0 <br />TO <br />^L` <br />W <br />M <br />O <br />LL <br />oo <br />T <br />0 <br />T <br />°— J O <br />T <br />T N <br />o) <br />r <br />ai <br />W <br />T M CV <br />M <br />o <br />Z <br />Z <br />E <br />cc <br />cca0 <br />E <br />a <br />U J Q CIS <br />0J <br />c <br />0 <br />JOB <br />NO: 19-5907 <br />SCALE : AS NOTED <br />SHEET NO. <br />4.0 <br />