Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />200A INDOOR PANEL <br />MAIN <br />O <br />200 amp <br />150 amp <br />POWER CO. FEED <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEC 14, 250.94 <br />NEMA 1 <br />2oo AMP <br />#14 copper to lights 8 outlets <br />#12 copper to 20 amp ckts <br />#10-2 copper to WH <br />#10-3 copper to Dryer <br />or 4/0 SER Alu <br />4 Bare Cu Ground <br />WITH CODE APPROVED <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />GENERAL ELECTRICAL NOTES: Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70 - 2014, LOCAL CODES AND THE LOCAL POWER CO. <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general) <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 42" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2014 NEC. <br />T Provide Tamper Resistant Receptacles as required by the 2014 NEC, 406.11 <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2017 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' of the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlets shall not be required on a wall directly behind a range or sink to fulfill the <br />requirement for an outlet every 24". The width of the sink or range is not to be included in the spacing <br />of the outlets unless the distance from the sink or range is greater the 12" for straight counter tops and <br />18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FF <br />DUPLEX OUTLET ABOVE COUNTER <br />� wP <br />WEATHERPROOF DUPLEX OUTLET <br />vGFI <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />6. <br />P4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />LED <br />LED CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />PC <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q <br />EXHAUST FAN <br />;O� <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />kD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CO <br />CARBON MONOXIDE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />©2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />�]M <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />C� J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />Ci T J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />W <br />I <br />WP DISC. <br />GFI H. <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />GFI <br />\ -- —_ --- ` I o <br />ROUGH -IN FOR <br />\ RANGE _ LIR IGHT PRE -WIR <br />E <br />RE I / <br />\ PENDANT AS / �- I / <br />PER SPECS \ 2 I O <br />U. . S IT H ROUGH -IN FOR y � /� <br />/ I OPT. CLG. FAN!\` ROUGH -IN FOR <br />_ _ _ INK ! DIS I IGHT PRE -WIRE G I OPT. CLG. FAN/ <br />tt)4—\ ' \\ GF1I 1L_ _�I ❑o _. GF �II � <br />/ PRE -WIRE <br />�AFE D.GFI BED OOM3` BEbROO <br />''.. BEDROOM 2\\,\ <br />S.D. <br />OPT' <br />I \ F <br />M REF. I 4E <br />U.C. OUTLET C.M <br />LM <br />U.C. OUTLET — — — — — — — — — — — — — — — LS.D. S.D. <br />f3 OF— <br />FOR DW=______ <br />ROUGH -IN FOR <br />OPT. CLG. FAN/ \ WP <br />LIGHT PRE -WIRE GFI <br />12 <br />_-- ENTRY <br />� FA R M \ \ I <br />CH <br />3 NEC=—=MM—Mr.J <br />4M7 �TA <br />GFI @ 44" <br />A.F.F. <br />— — —------------ <br />� <br />I I 71 \ \ I I <br />OPT, o T IA1 1 I I I <br />C.M D. I I I <br />I 1 I I <br />I 11 I <br />S.D. \ \ \ �o VP ----------- <br />GFI @ 44' I I I <br />ROUGH -IN FOR I A.F.F. I I <br />OPT. CLG. FAN/ I GFI FOR I I I <br />\ LIGHT PRE -WIRE ( GAR. DOOM I <br />GFI I I I <br />2 CAR GARAGE <br />G V \ <br />I I I I <br />OWNER'S SUITE W.I.C. � <br />I I/A I I I I <br />I I 1 I <br />I I I I I <br />O20 <br />I II <br />--- j D <br />VERIFY LOCATION <br />j I <br />PFIl — — — —J ELECTRICAL PANEL L_IRRIGATION <br />GFI ---- (� ----- r� AGFI @ 44" A.F.F. <br />RECEPT. '—' <br />FOR ALARM VERIFY METER H.B. <br />SYSTEM LOCATION WITH <br />BUILDER <br />MAIN FLOOR ELECTRICAL PLAN_ <br />DD V <br />z_M <br />0 <br />z <br />E3Q <br />Z <br />w <br />�o <br />�V — <br />O w <br />c <br />t/) ZD <br />m <br />t-- <br />o <br />f- <br />U <br />to 0 <br />m N <br />LUp <br />N fM <br />_ai <br />O o N <br />C) <br />10-10 <br />�"00 <br />ono <br />Q rn <br />0 <br />off. <br />Yc <br />O M ONO <br />H goN o O <br />Z Lu <br />�. 53 <br />LU 8 <br />_ <br />W V LL o a <br />v <br />Z U) <br />c4o <br />LLZ o�C14 o <br />U)� � <br />Z <br />W N <br />OO U O <br />El 171 <br />WWW.FDSENG.COM <br />rn <br />0 <br />CV <br />0 <br />00 <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 Florida Building Code - <br />Residential 6th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />L AR <br />4600 W. Cypress St, Suite 200 1 Tampa, FL 33607 <br />www.LennarTampa.com <br />oz <br />0 <br />wuj <br />¢£ <br />f <br />Zw <br />J <br />� <br />Z0c <br />t <br />y 0wZ <br />a p m <br />two <br />U <br />on <br />L <br />zO <br />Lf U <br />Z <br />a <br />LL <br />w <br />J <br />N3 <br />LU <br />0 <br />-0cc <br />_ <br />z <br />a <br />J w <br />O <br />O�Z <br />0 <br />o <br />z <br />UoM <br />N <br />g a 0 <br />zap¢ <br />Q <br />°o '-0 <br />Z <br />Z <br />w0Zo <br />� Cy Q <br />LU�+/ <br />J <br />'T^ <br />r-I <br />W <br />W <br />OUZO <br />< U <br />a¢ <br />O <br />kO <br />Q <br />Z <br />Z <br />�¢z <br />Z S <br />L!i <br />g <br />0 <br />¢Z <br />o <br />= <br />n <br />r—I <br />a <br />V) <br />o <br />SCALE : AS NOTED <br />DATE : 07/08/2019 <br />TECH: FM <br />VERSION NO. 4n0 <br />SHEET NO. <br />4.0 <br />