ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13, Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14, Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FfF <br />DUPLEX OUTLET ABOVE COUNTER <br />w.P. WEATHERPROOF DUPLEX OUTLET <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />G.F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />K* 220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />24 FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED LIGHT FIXTURE <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />P.C. <br />TRACK LIGHT <br />—� FLUORESCENT LIGHT FIXTURE <br />Q EXHAUST FAN <br />,Qr EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />P� PUSH BUTTON SWITCH (OPTIONAL) <br />F0 PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />© TELEVISION (OPTIONAL) <br />® 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />ELECTRIC METER <br />owl_ ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C`/rJ <br />ROUGH -IN FOR OPT. CEILING FAN <br />G J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />17 <br />G J OPT. CEILING FAN <br />GD (1) PHONE LINE, (1) DATA PORT <br />L TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />LAV <br />LAV <br />I <br />I <br />ti W/C <br />Ll <br />SHOWER <br />` \nd F FAR <br />STUDOR <br />VENTQ I , DBL SINK <br />L TI W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31878 <br />LOAD WATTS -- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA 1 <br />200 AMP <br />ETER MA N <br />1 ISO-200 AMP I IT /—Serial Cable <br />NEM <br />3R <br />Power Co. Feed ---, IJ <br />i>— #4 Solid COPPER Ground <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least V apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 -17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT i <br />WP <br />GFI <br />An <br />DINING <br />KITCHEN0000 <br />I <br />--- GFI d --- <br />SWITCH FOR - <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,,>ROUGH -IN\ <br />FOR OPT. <br /><-�fi-,FAN/LIGHT <br />� 1 <br />r� <br />I <br />I <br />1 / <br />DB <br />NTRY WP <br />IGHT AS 0 FI@ <br />0 <br />ER SPECS <br />DB &GFI TO I <br />BE ALIGNED I <br />VERTICALLY <br />I <br />w <br />jo= <br />� LLo <br />� BUJ <br />0m <br />0 <br />C.M <br />1 UPSTAIRS F <br />@ 44" <br />,\ \ ` <br />W.H. <br />A.F.F. <br />' \ O <br />I <br />I GARAG E <br />I I <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I <br />J <br />I <br />I <br />Ip Z <br />I <br />IQ _ <br />I <br />I0 Q <br />I <br />I1M W <br />11> <br />I <br />W <br />1 <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL —UNIT—C 1624 <br />SCALE: Y4"=1'-0" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />r— — — — — — <br />2ND ELECTRICAL - UNIT-C 1624 <br />SCALE: Y4"=1'-0" <br />N <br />No <br />0 <br />co <br />o <br />as <br />"ZIP <br />s <br />`ate o <br />N cc O ►- <br />.y06/O � <br />3 a' as <br />ux 'ate <br />c E <br />o <br />Cv <br />a <br />N <br />0 <br />N <br />N <br />0 <br />LE vvko ,,41J* <br />%0 G• <br />No PE 75 <br />cc <br />:"�• STATE <br />OF <br />a <br />irrJ t'1 • <br />• <br />i� �, <br />%%% <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />a� <br />a cN <br />c8�� <br />t1 <br />64 <br />Q <br />0 <br />N J <br />7 <br />(n . r _ LL W <br />W <br />a <br />rNi c W ° a <br />d <br />0 <br />JLLLL z <br />Z <br />Z <br />t mo 01 o <br />W <br />'o2�`r J m <br />W <br />¢ <br />Z <br />co W <br />LO N Z UU S <br />Cl)Q <br />U U)LL F- <br />N <br />o U ❑❑❑ <br />Z <br />W <br />Ur <br />Z N � <br />z � <br />a <br />U) <br />—� <br />A4_j <br />C <br />w <br />� <br />U <br />0 <br />S <br />c <br />�N <br />® <br />v <br />W J <br />�— E <br />s $ <br />x� <br />t1d <br />c� o <br />Q Y <br />N <br />14 <br />Mo <br />cJ <br />O <br />Z <br />Z <br />< <br />a <br />`zo <br />>� <br />Za <br />Q <br />p <br />m " <br />W' <br />'Zoa <br />I— <br />2g <br />-' <br />0o <br />& a <br />ZER <br />CID <br />'0 <br />Z <br />o <br />a <br />ai <br />Wa <br />OV <br />mo <br />ZLL <br />Z <br />m J <br />mm <br />aw <br />5 <br />N <br />¢w <br />O� <br />ZI <br />Z <br />Qo <br />W <br />a <br />°LL <br />a <br />�w <br />� <br />SIC <br />o <br />J <br />w� <br />; <br />c) <br />Z< <br />COS <br />03 <br />o� <br />> 00 <br />N <br />F— <br />0 <br />' <br />L <br />(ID 00 <br />r <br />00 <br />LM <br />C <br />T <br />550 <br />U) m <br />OHO <br />0 <br />Ln <br />cM <br />L O <br />Cfl <br />fV <br />Ln <br />c=o <br />ui <br />m <br />w <br />04 <br />iri O <br />o <br />Z <br />Z <br />E r <br />r <br />m <br />a <br />c0 � <br />¢ o <br />JOB <br />NO: 23-13115-13120 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />