GENERAL NOTES:
<br />THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2020 FLORIDA BUILDING CODE
<br />ZTH EDITION AND THE 2020 FLORIDA BUILDING CODE - RESIDENTIAL ZTH EDITION.
<br />T.L. HAN50N A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING
<br />COMPANY: HAS APPLIED "RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN OF THIS STRUCTURE.
<br />THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE
<br />FOLLOWING SUPERIMPOSED LOADS:
<br />SLAB:
<br />LIVE LOAD - 50 P.S.F.
<br />DEAD LOAD - 10 P.S.F,
<br />ROOF:
<br />LIVE LOAD (TRUSS TOP CHORD) - 20 P.S.F.
<br />DEAD LOAD (TRUSS TOP CHORD) - 10 P.S.F. (15 P•S,F. WHEN TILE ROOFING IS INSTALLED)
<br />DEAD LOAD (TRUSS BOTTOM CHORD) - 10 P.S.F.
<br />ASSUMED TRUSS SELF WEIGHT (DEAD LOAD) - 1 P.S,F,
<br />WIND:
<br />BUILDING IS DESIGNED TO CONFORM TO ASCE 1-16, CHAPTERS 26 THRU 31: PER 2020 FLORIDA
<br />BUILDING CODE, RESIDENTIAL 1TH EDITION -SECTION R301,2.1.1, AND 2020 FLORIDA BUILDING CODE
<br />1TH EDITION SECTION 160E
<br />COMPONENT 4 CLADDING WIND LOADS
<br />WIND DESIGN ASSUMPTIONS:
<br />BUILDING EXPOSURE - B
<br />BUILDING RISK CATEGORY - II
<br />MEAN ROOF HEIGHT 30' OR LESS
<br />HEIGHT 4 EXPOSURE ADJUSTMENT
<br />COEFFICIENT - 1,0
<br />ENCLOSED BUILDING
<br />INTERNAL PRESSURE COEFFICIENT • +/- 0,15
<br />WIND SPEED SHOWN AT THE BOTTOM RIGHT
<br />CORNER OF THIS SHEET
<br />ALL STRUCTURAL ELEMENTS, EXTERIOR
<br />WALLS AND INTERIOR WALLS SHALL BE
<br />TYPE V CONSTRUCTION PER FBC 602.5
<br />ALL OTHER
<br />BUILDING
<br />ROOF OVERHANG
<br />COMPONENT
<br />ZONE
<br />LOADS
<br />LOADS
<br />1
<br />N/A
<br />+32,3/-35.3
<br />2
<br />65.1
<br />+32,3/-56.2
<br />3
<br />-110,6
<br />+32.3/-89,0
<br />4
<br />N/A
<br />+35,3/-38,2
<br />5
<br />N/A
<br />+35,3/-41.2
<br />SOIL BEARING 4 COMPACTION:
<br />THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S,F.
<br />(MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL
<br />ON THE SITE IS PROPERLY PREPARED 4 COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F.
<br />FOUNDATION LOADING.
<br />T.L. HANSON: A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL
<br />ENGINEERING COMPANY: DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE
<br />NOR PERFORMING ANY SOIL TESTING.
<br />T.L. HANSON SHALL NOT BE RESPONISIBLE FOR THE SITE SOILS ABILITY TO SUPPORT
<br />THE BUILDING LOADS.
<br />FOUNDATIONS 4 SLAB -ON -GRADE:
<br />BUILDING SITE SHALL BE SCRAPED TO REMOVE ALL ORGANIC MATERIALS WITHIN THE BUILDING AREA.
<br />ANY ADDITIONAL FILL PLACED ON THE BUILDING PAC) AREA, SHALL BE COMPACTED
<br />SUCH THAT IT CAN ADEQUATELY SUPPORT A 2,000 P.S.F. FOUNDATION LOADING,
<br />SLAB SHALL BE PLACED OVER A 6 MIL VAPOR BARRIER ON CLEAN, ADEQUATELY
<br />COMPACTED AND TERMITE POISONED SOIL,
<br />CONCRETE UTILIZED IN THE FOUNDATIONS AND SLABS SHALL HAVE A MINIMUM 28 DAY
<br />COMPRESSIVE STRENGTH OF 2,500 P.S,I,
<br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE
<br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25"
<br />FOR 05 REBAR, 30" FOR "6 REBAR 4 35" FOR "1 REBAR.
<br />PLANS ARE ENGINEERED FOR A MAXIMUM STEMWALL HEIGHT OF 4 COURSES (AFTER
<br />FINAL SITE GRADING). THE CONTRACTOR OR BUILDING OWNER SHALL DETERMINE THE
<br />EXACT STEMWALL HEIGHT BASED UPON SITE CONDITIONS PRIOR TO POURING THE FOUNDATION
<br />AND CONTACT ARKAY ENGINEERING WHEN MORE THAN 4 COURSES ARE REQUIRED.
<br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON THE
<br />SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND
<br />A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY THE REQUIRED BUILDING SETBACKS.
<br />MASONRY WALLS:
<br />CONCRETE MASONRY UNITS SHALL BE HOLLOW UNIT MASONRY IN ACCORDANCE WITH ASTM C-50
<br />AND SHALL HAVE A MINIMUM F'M OF 1,500 P.S,I,
<br />MORTAR SHALL CONFORM TO ASTM C-210 AND SHALL BE EITHER TYPE M OR S,
<br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE
<br />WITH ASTM A-615, LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25"
<br />FOR 05 REBAR, 30" FOR "6 REBAR 4 35" FOR 01 REBAR.
<br />GROUT FOR THE POURED CELLS AND LINTELS SHALL HAVE A MAXIMUM COURSE AGGREGATE SIZE
<br />OF 3/8", PLACED AT AN 8 TO It INCH SLUMP AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH
<br />OF 2,500 P.S.I. (WHEN TESTED PER ASTM C-1019),
<br />PROVIDE CLEAN -OUT OPENINGS (12 80, IN,) IN CELLS CONTAINING SPLICED REINFORCEMENT, WHEN
<br />THE GROUT POUR EXCEEDS 5 FEET IN HEIGHT,
<br />TIMBER MATERIALS:
<br />ALL TIMBER MATERIALS SHALL BE AS FOLLOWS:
<br />ALL PLUMBING, ELECTRICAL AND MECHANICAL ROUGH -INS MUST BE COMPLETE, INSPECTED AND APPROVED
<br />PRIOR TO REQUESTING THE FRAMING INSPECTION.
<br />ALL LUMBER IN CONTACT WITH MASONRY WILL BE PRESSURE TREATED
<br />MATERIALS
<br />INTERIOR STUD WALLS TO BE OF 2 X 4 02 SPRUCE OR BETTER WITH SINGLE 2 X 4 P.T.
<br />PINE BOTTOM PLATE AND SINGLE 2 X 4 °2 SPRUCE TOP PLATE WITH STUDS SPACED
<br />MAXIMUM 24" OC. WALLS TO HAVE 1/2" GYPSUM BOARD EACH SIDE, WITH WALLS AT
<br />GARAGE TO HAVE MINIMUM R-II INSULATION
<br />DRAFTSTOPPING:
<br />IN SINGLE FAMILY DWELLINGS, DRAFTSTOPPING SHALL BE PROVIDED (PARALLEL TO THE MAIN
<br />FRAMIMG MEMBERS) IN FLOOR/CEILING ASSEMBLIES SEPARATING USEABLE SPACES. DRAFTSTOPPING
<br />SHALL BE CONSTUCTED SUCH THAT THE FLOOR/CEILING ASSEMBLY IS BROKEN UP INTO TWO OR
<br />MORE APPROXIMATE AREAS WITH NO AREA GREATER THAN 1000 SQ, FT.
<br />ATTIC ACCESS:
<br />ATTIC ACCESS SHALL BE PROVIDED TO ATTIC AREAS EXCEEDING 30 SQ, FT. AND HAVING MINIMUM
<br />30 INCHES OF VERTICAL HEIGHT, ROUGH -FRAMED OPENING NOT TO BE LESS THAN 22 X 30 INCHES.
<br />WHEN MECHANICAL EQUIPMENT IS LOCATED IN THE ATTIC, IT SHALL BE INSTALLED IN ACCORDANCE
<br />WITH THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION 1-11305,13
<br />PRODUCT CATEGORY
<br />STRUCTURAL COMPONET
<br />STRUCTURAL COMPONET
<br />STRUCTURAL COMPONET
<br />STRUCTURAL COMPONET
<br />STRUCTURAL COMPONET
<br />STRUCTURAL COMPONET
<br />STRUCTURAL COMPONET
<br />ROOFING
<br />ROOFING
<br />WINDOWS
<br />EXTERIOR DOORS
<br />SOFFIT 4 FASCIA TRIM
<br />EXTERIOR DOORS
<br />SOIL TERMITE TREATMENT:
<br />TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES
<br />APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR
<br />USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION.
<br />A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED
<br />PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE
<br />SHALL STATE
<br />"THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
<br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA
<br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES."
<br />IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION,
<br />DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE
<br />OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE
<br />BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR. THE SYSTEM
<br />MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL.
<br />INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION,
<br />BACKFILLING 4 COMPACTION ARE COMPLETE
<br />ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED
<br />(INCLUDING ANY BOXED OR FORMED AREAS) -
<br />BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE
<br />WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN
<br />ADEQUATE SIZE 4 DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE
<br />INITIAL TREATMENT.
<br />A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL
<br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT
<br />SHALL BE REQUIRED
<br />ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER
<br />MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT
<br />EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE
<br />WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS
<br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS
<br />COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE
<br />VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED.
<br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE
<br />BUILDING SIDEWALLS (PER FBC R318).
<br />AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW
<br />AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES
<br />FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS,
<br />THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE
<br />CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION
<br />WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION
<br />FOR FUTURE TERMITE INFESTATIONS
<br />TRUSSES:
<br />IF THE CONTRACTOR, TRUSS MANUFACTURER OR ANY OTHER DESIGN PROFESSIONALS REVISE THE
<br />TRUSS SYSTEM LAYOUT FROM THOSE SHOWN ON THESE PLANS T. L, HANSON 4 ASSOCIATES IS
<br />REQUIRED TO REVIEW ALL FINAL CONSTRUCTION DOCUMENTS FOR COMPLIANCE WITH THE DESIGN
<br />INTENT PRIOR TO COMMENCEMENT OF THE PROJECT,
<br />EXTERIOR WINDOWS E DOOR ASSEMBLIES:
<br />ALL EXTERIOR WINDOW 4 GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH ANSI/AMMA/NWWDA
<br />101/182 STANDARDS AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING THE MANUFACTURER,
<br />PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT TESTING ENTITY.
<br />ALL MULLIONS AND ADJACENT DOOR/WINDOW ASSEMBLIES SHALL BE TESTED OR ENGINEERED TO
<br />TRANSFER 1.5 TIMES THE DESIGN LOADS TO THE ROUGH OPENING SUBSTRATE,
<br />INSTALL ALL WINDOW 4 DOOR ASSEMBLIES PER THE MANUFACTURERS ANCHORING RECOMMENDATIONS
<br />TO ACHEIVE THE DESIGN PRESSURES SPECIFIED,
<br />ELECTRICAL, PLUMBING 4 MECHANICAL:
<br />IN ACCORDANCE WITH CHAPTER 411.003(2)(1) OF THE FLORIDA ADMINISTRATIVE CODE: ELECTRICAL,
<br />PLUMBING AND MECHANICAL SYSTEMS SHALL BE DESIGNED BY THE RESPECTIVE CONTRACTORS TO
<br />MEET ALL APPLICABLE CODES. THE ELECTRICAL, PLUMBING AND MECHANICAL SYSTEMS DRAWN HEREON
<br />ARE BASED UPON A DESIGN PROVIDED BY THE OWNER TO ADDRESS HIS/HER REQUIREMENTS.
<br />ALL ELECTRICAL OUTLETS IN BATHROOMS, KITCHEN, GARAGE AND AT
<br />EXTERIOR LOCATIONS SHALL BE WIRED INTO A GROUND -FAULT INTERRUPTER "GFI" CIRCUIT.
<br />ALL ELECTRICAL OUTLETS IN HABITABLE SPACES SHALL BE WIRED INTO AN ARC -FAULT INTERRUPTER
<br />SAFETY GLAZING:
<br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF
<br />GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R306:
<br />(1) GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR
<br />ASSEMBLIES.
<br />(2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM
<br />ROOMS, BATHTUBS, AND SHOWERS, GLAZING IN ANY PORTION OF A BUILDING WALL
<br />ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS
<br />THAN 60 INCHES ABOVE THE DRAIN INLET.
<br />(3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE
<br />THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A
<br />CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE
<br />FINISHED FLOOR OR WALKING SURFACE.
<br />(4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS
<br />DESCRIBED IN ITEMS (2) AND (3) ABOVE. THAT MEETS ALL OF THE FOLLOWING
<br />CONDITIONS:
<br />A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 50, FT,
<br />B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR.
<br />C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR.
<br />D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE
<br />PLANE OF THE GLAZING,
<br />REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS
<br />THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING.
<br />APPROVED PRODUCT LIST
<br />SUB CATEGORY
<br />MANUFACTURER
<br />HUCEE
<br />SIMPSON
<br />ABUSE
<br />SIMPSON
<br />HIOA
<br />SIMPSON
<br />HETA20
<br />SIMPSON
<br />MBHA HANGERS
<br />5IMP50N
<br />MSTA24
<br />SIMPSON
<br />LINTEL HEADER CAST CRETE CORP
<br />STATE OF FL,
<br />APPROVAL "
<br />FL 10531
<br />FL 10860
<br />FL 1045E
<br />FL 114'13
<br />FL 13c304
<br />FL 13812
<br />FL 158,1
<br />ASPHALT
<br />GAF SINGLES ALL
<br />FL 10124,1
<br />UNDERLAYMENT
<br />GAF
<br />FL 10626,1
<br />SINGLE HUNG
<br />NON IMPACT
<br />PLYGEM 1500
<br />FL 16103,1
<br />SLIDING GLASS
<br />PLYGEM 4-I80
<br />FL 14634,4
<br />SOFFIT AMERICAN
<br />CONSTRUCTION METALS
<br />FL 12019,1
<br />SINGLE SWINGING
<br />PLAST PRO
<br />FL 15221,1
<br />FL 15221,E
<br />NEW WALL HEIGHT
<br />8, O,, THIS SIDE OF HOUSE —
<br />—TOP OF OPENINGS —
<br />HARDI LAP SIDING
<br />EXISTING WALL HEIGHT
<br />THIS SIDE OF HOUSE 8. 011
<br />... .. ... ... .. ... .. ... .. ... .. ... .. ... .. ... ... .. ... .. ... .. ... .. .. ... .. .. ... .. ... .. ... I TOP OF OPENINGS n 6 8
<br />U• DECORATIVE CEMENTITIOUS FINISH
<br />Lu
<br />01
<br />0 - —FINISH --=--=--- --=------=-----=---=--;---=------=----------------------------•--------------------- ------------------------------- - FINISH FLOOR — -
<br />OWNER OR CONTRACTOR TO VERIFY
<br />ROOF PITCH PRIOR TO MANUFACTURING
<br />OF ROOF TRUSSES, DO NOT GO BY
<br />DRAWiNG5
<br />FRONT ELEVATION 1/411 = 11 OII
<br />AREA VENTILATION REQUIRED - UPPER t LOWER VENTED PROVIDED
<br />1594 S,F, ATTIC AREA / 300 = 5,32 S,F, X 144 - 168 S,I,
<br />168 S,I, / 2 = 384 S,I, UPPER AND LOWER VENTILATION REQUIRED
<br />UPPER VENTILATION PROVIDED
<br />3 OFF RIDGE VENTS AT 138 SI,/EA - 414 > 384 $1,
<br />LOWER VENTILATION PROVIDED
<br />200 FT, SOFFIT VENTS l MIN AT 6,42 SI,/FT = 12134 > 384 Si,
<br />HARDI LAP SIDING
<br />DECORATIVE CEMENTITIOUS FINISH
<br />--------------
<br />RIGHT ELEVATION 1/411 _ 11 OII
<br />OFF RIDGE VENT
<br />LAP S
<br />REAR ELEVATION 1/411 _ V OII
<br />HARDI LAP SIDING
<br />1' 4"
<br />STUCCO TO MASONRY INSTALLATION:
<br />APPLY 2 COATS OF PLASTER DIRECT TO
<br />SURFACE TO ACHIEVE A MINIMUM 5/8" THICKNESS
<br />INSTALL CASING BEAD. CORNER BEAD AND ALL
<br />EXPANSION JOINTS TO FACE OF BLOCK WALL WITH
<br />3/8" MASONRY STUB NAILS, 1/2" T NAILS SPACED
<br />MAXIMUM 16" OC OR APPLY A I"XI"X 3/4" THICK
<br />SECTION OF LIQUID NAIL TO FACE OF WALL
<br />MAXIMUM I6" OC
<br />STUCCO TO FRAMING INSTALLATION:
<br />INSTALL 1/2" PLYWOOD SHEATHING NAILED TO GABLE END
<br />WITH 8D NAILS 6" OC TO ALL WOOD MEMBERS OF TRUSS.
<br />COVER WITH TYVEK HOUSE WRAP. INSTALL GALV PAPER
<br />BACK WIRE LATH WITH MINIMUM 1 1/2" 16GA GALV STAPLES
<br />SPACED MAXIMUM 6" OC ON STUDS OR ALL WEBS OF THE
<br />TRUSS. ALL LAPS OF LATH TO BE A MINIMUM 1 1/2", APPLY
<br />PEEL AND STICK TAPE AT ALL JOINTS OF BLOCK TO WOOD,
<br />INSTALL FELT PAPER OVER THIS JOINT PRIOR TO INSTALLING
<br />GALV EXPANSION JOINT AT THIS LOCATION WITH MINIMUM 1 1/2"
<br />16GA STAPLES w 6" OC, APPLY 3 COATS OF PLASTER TO
<br />ACHIEVE A MINIMUM 1/8" THICKNESS AT ALL AREAS
<br />SIDING TO WOOD OR MASONRY INSTALLATION:
<br />REFER TO THE MANUFACTURE SPECIFICATIONS ON
<br />ALL EXTERIOR SIDING
<br />ale `100
<br />Ole
<br />° 'Y ® -
<br />-SONA NO�i8654
<br />P &>C I�NSITg% 2
<br />41,tr,26
<br />I HERBY CEO'�� PR L 41D SPECIFICATIONS
<br />WERE PRE PA ®1'°°° DIRECT SUPERVISION
<br />ARE IN COMPLI 1��l �> 16, SECTION 1609 OF THE
<br />FLORIDA BUILDING C `i TH EDITION AND ASCE 1-Iro
<br />FOR 139 MPH WIND ZONE RISK CATEGORY II AND THE ENTIRE
<br />2020 BUILDING CODE RESIDENTIAL 1 TH EDITION
<br />m
<br />CIA
<br />m
<br />f�
<br />z
<br />_p
<br />O
<br />LL r
<br />r
<br />In
<br />z
<br />to
<br />lu
<br />i
<br />m
<br />Q w
<br />p
<br />V
<br />w
<br />z
<br />4LL
<br />A
<br />0
<br />Q- ID
<br />in
<br />:3
<br />m
<br />in
<br />6�
<br />m
<br />0
<br />pl
<br />111
<br />LLl
<br />m co
<br />Z
<br />�
<br />lij
<br />a
<br />rWW--z
<br />LL
<br />NZ O
<br />Zm
<br />az o�
<br />Il.l
<br />A
<br />3:
<br />U
<br />�Z
<br />o d)
<br />O
<br />Jw
<br />o
<br />H
<br />d
<br />zz
<br />�7
<br />O
<br />w
<br /><t
<br />T
<br />LO
<br />� N
<br />m
<br />0
<br />0)
<br />r
<br />ll1
<br />N
<br />ll-I
<br />z
<br />0
<br />La
<br />m0
<br />Q
<br />Q
<br />VJ
<br />z
<br />lu
<br />OL
<br />O
<br />Q
<br />Q
<br />1 3
<br />4*
<br />z r �
<br />O -A
<br />(VY :
<br />O 0-
<br />z
<br />nu
<br />1�
<br />F G
<br />2 OF
<br />
|