Laserfiche WebLink
t <br />I <br />ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FEPF- <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I� <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />� 4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />lO <br />EXHAUST FAN <br />141),EXHAUST <br />FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />�[P] <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�[JBD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />© 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />]M <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />Q\� <br />a <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J <br />OPT. CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />150Af200A INDOOR <br />n <br />200 amp <br />150 amp <br />UNDERGROUND IDis <br />SERVICE BY POWER CO.—�� <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEMA1 <br />1so AMP/ <br />200 AMP <br />lights & Outlets <br />appliances and GFI <br />rWH <br />Range <br />HVAC <br />200=410 in 2" Conduit <br />Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />Ili- 1.5" VTR <br />-I <br />I <br />I <br />I <br />� I <br />/ I <br /><\ I I <br />I <br />I I I I <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />DEDICATED <br />RECEPTACLE <br />FOR MICROWAVE <br />RANGE HOOD <br />PER SPECS <br />2 X <br />I 1 <br />I <br />K TC <br />I <br />GFII r <br />II 3 <br />II � <br />FOR DISPOSAL <br />OPTIONAL LIGHTING <br />SCALE: Y4"=1'-0" <br />I `R' 7 T 'll' <br />S.D <br />I j \ <br />------------ <br />I ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />G LIGHT PRE -WIRE <br />BEDROOM 2 ' <br />I I I <br />I I I <br />I I I <br />I -----------I <br />I I <br />I I <br />I <br />I I <br />I I <br />I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />t I <br />I I <br />I I <br />L---------------------------------------� <br />PER SPECS <br />ELECTRICAL PLANS <br />SCALE: Y4"=1'-0" <br />SWITCH FOR <br />DISPOSAL IN <br />CABINET <br />r_===_i <br />ALT <br />I I AC PAD I I <br />Il 11 <br />WP <br />)__GFI <br />DISC. <br />eW3 <br />!V <br />O <br />O <br />o <br />n O <br />m <br />h d <br />ev C= <br />Q <br />3= �x <br />c <br />i .� Q <br />a>r r4cc <br />d <br />i; Cr ._T ? <br />N O-� <br />= E <br />r0 0 <br />a C7 <br />C7 <br />CV <br />0 <br />cj <br />CID <br />CV <br />r��� <br />t.: <br />...ilt: <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residental 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />0 <br />W <br />Q <br />vE <br />o cc+3 8 <br />N <br />00 <br />yy0 <br />� <br />fi4 <br />'C <br />r� s♦ � LL <br />Cm J LL <br />LU <br />mLL Ll d <br />V <br />2 <br />13 <br />11 <br />maC a 4 <br />1: <br />0 <br />Win2O�l°' <br />LL Z <br />m w <br />`n N Z d J <br />ZN <br />O U U <br />W <br />1:1� <br />o g <br />z C. <br />a <br />J— <br />Cl t1') <br />N <br />N(Ij <br />er <br />^ O <br />':'Z(p <br />O <br />V <br />a--+ <br />t'>3 <br />w W <br />� <br />U <br />W <br />O <br />Ln <br />N <br />W <br />� � <br />U_ <br />r <br />� to <br />U <br />w W <br />Ila <br />C 0 <br />`z <br />m <br />o <br />�Z <br />Z <br />cn <br />Z <br />a <br />g <br />LL <br />aowte <br />20 <br />>m <br />z® <br />w <br />H <br />go <br />� <br />Wo <br />� U <br />Z¢r <br />SE <br />0¢ <br />WZ <br />d <br />_ t <br />WZ <br />g <br />�� <br />C13 <br />a z <br />.a <br />m O <br />Fz <br />Z <br />m <br />hm <br />¢w <br />z <br />3 <br />$� <br />Z <br />go <br />33 <br />WLL <br />aZ <br />WN <br />2 <br />~ <br />o <br />�' <br />w� <br />Z¢ <br />>0 <br />a <br />o- <br />Uri <br />�O <br />Ln <br />M <br />i <br />T <br />co <br />CN <br />N <br />o <br />� <br />N <br />U) m <br />N <br />+-' <br />O <br />_ <br />N <br />0) <br />' <br />a N <br />m <br />O <br />r <br />Q <br />c <br />r <br />ci <br />M <br />w <br />S^ <br />N <br />d <br />Z <br />Z <br />E N <br />N <br />c <br />s <br />a o <br />JOB <br />NO : <br />23-04652 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />