ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2"AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11.In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />I� <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />FEFW.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I-® <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />13 <br />THREE-WAY SWITCH <br />14 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT -TO BE SURFACE MOUNTED ON J-BOX <br />1-0 <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />lO <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />�D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />®2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />�]M <br />ELECTRIC METER <br />NMI <br />ELECTRIC PANEL <br />—MR-i <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G T J <br />OPT. CEILING FAN <br />69 <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I I <br />I I <br />I I <br />I I <br />LAV <br />� I <br />ti TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />t <br />I <br />I <br />OPT. <br />LAV <br />I LAV <br />J— <br />W/C <br />SHOWER <br />\rid F FLR <br />STUDOR <br />VENTTI , DBL SINK <br />'N W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />120.0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHERA WATTS <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />100 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />1 5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Riser Diagram <br />4 UNIT BUILDING <br />(2) 1532 UNITS & (2) 1624 UNITS <br />800 AMP <br />0 <br />TERMINAL BOX <br />O <br />TENANT PANEL w/ 150 <br />150 AMP <br />150 AMP <br />AMP INSIDE MAIN <br />0 <br />0 <br />150 AMP <br />150 AMP <br />0 <br />0 <br />150 AMP <br />150 AMP <br />FRI <br />GROUND <br />1/0 CU. TO BUILDING STEEL <br />C.O. <br />2" PVC CONDUIT WITH 2 #2/0 AL - 1 #1/-0 AL-1 #1 AL <br />TO POWER CO. 6 REQUIRED PER BUILDING <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17 LOCAL CODES AND THE LOCAL POWER CO. <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />0 <br />OUTDOOR LIVING <br />INSTALL LIGHT �\�/'r <br />ROUGH -IN / }/ <br />FOR OPT. <br />FAN/LIGHT <br />GFI <br />in. <br />\ GFI <br />I <br />t <br />DINING <br />I <br />KITCHEN 1 1 <br />I �G1 <br />� I <br />� I <br />FI oo GEL-j <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK G <br />\ I <br />\ �C <br />II <br />I <br />\ I <br />GREAT ROOM \ <br />^� /,,^TROUGH -IN\ <br />FOR OPT. CH <br />FAN/LIGHT 1 <br />r\01 <br />To S\AYTC <br />I I / <br />' UPSTAIRS <br />FOYER <br />VTRY I, <br />GHT AS Q <br />=R SPECS <br />I <br />1 <br />I <br />GFI <br />@ 44" <br />` \ <br />\ <br />LW-H. <br />A.F.F. <br />` <br />,I <br />` p <br />/ <br />11 <br />1 <br />I <br />I GARAGE <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I <br />J <br />I <br />I <br />10 Z <br />I <br />I¢ a <br />I <br />10 Q <br />I <br />I-1 U <br />1 <br />I> - <br />Iy= U <br />I <br />I <br />I IW <br />1 <br />h of <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL — UNIT—C 1624 <br />SCALE: YV=V-0" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />NOTE: <br />-INSTALL 2" CONDUIT TO METER CAN <br />-INSTALL A MAIN 150 AMP BREAKER IN PANEL <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL —UNIT—C 1624 <br />SCALE: Y4"=1'-0" <br />V-4 <br />CV <br />C%j <br />00 <br />0- <br />d �� <br />:> Id1 <br />p „ <br />'....' c= <br />•� 'G s1G1 „>{ <br />6IJ � G" Gffi <br />C, I- <br />1. <br />No P <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />H <br />E <br />8 <br />V <br />N0 .2 S <br />am ID N <br />0 <br />en <br />a: <br />M V tk LJL <br />N J <br />LL w <br />J LL. a <br />aY <br />Z <br />—o� <br />g� 0W <br />� °' m <br />"j <br />U <br />w <br />N Z <br />0 M <br />ZN <br />o� <br />WCD <br />❑ ❑ <br />Z N o <br />z <br />CD <br />Dw <br />LL <br />cn <br />�'U <br />0 <br />8 <br />04 <br />c <br />� <br />U <br />w m <br />t <br />®� <br />_ <br />Of 0 <br />< N 0 <br />soo <br />o <br />M <br />W <br />M <br />¢ <br />zo <br />z <br />Q <br />♦a. E <br />2 <br />to <br />1 <br />- <br />N <br />QN <br />z <br />o a <br />X OU <br />� OU <br />Z <br />E <br />N <br />a�o1 <br />o <br />0` <br />a z <br />wo <br />< <br />i <br />�� <br />m 0 <br />fu <br />ox°Y <br />F O <br />a <br />Z <br />N <br />J <br />m <br />aw <br />cA <br />�, <br />� <br />¢ ° <br />o <br />oa <br />Z z <br />g ° <br />W <br />a <br />U 3 <br />wLL <br /><o <br />�w <br />N w <br />w� <br />XI5 <br />>_ <br />CD <br />CD <br />za <br />d <br />1;'13: <br />0 O <br />F <br />m <br />d- <br />N <br />^^`` <br />m <br />r <br />O <br />L <br />`V <br />M <br />O <br />N <br />U-) <br />Cr CV <br />o <br />\.i <br />' ^ Y <br />v, o <br />O <br />00 <br />m <br />N <br />O <br />LO <br />I-- <br />N <br />L.n <br />O <br />O <br />C <br />'a <br />04 <br />< r <br />Nr <br />Ln <br />O <br />T <br />T <br />N <br />.f '. <br />T <br />o <br />Z <br />E Q <br />rn <br />m <br />co <br />E <br />?3 <br />cc <br />c <br />0 <br />JOB <br />NO: 22-11668-11666 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />15 <br />