ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and fisted in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI LIL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />PE5W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />piiip <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />j <br />WALL SWITCH <br />j3 <br />THREE-WAY SWITCH <br />24 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />Q <br />EXHAUST FAN <br />�O <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />IEBP <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />IM <br />ELECTRIC METER <br />_Ia <br />ELECTRIC PANEL <br />JJ <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />�A IL� <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />T J <br />OPT. CEILING FAN <br />C$ <br />(1) PHONE LINE, (1) DATA PORT <br />150AI200A INDOOR <br />PANELCENTER <br />NEMA 1 <br />150 AMP/ <br />200 AMP <br />n <br />200 amp <br />150 amp <br />copper to lights & outlets <br />copper to 20 amp ckts <br />2 copper to WH <br />3 copper to Dryer <br />or 4/0 SER Alu <br />UNDERGROUND DisconnL#4GROUNDING <br />POWER CO. FEED <br />INTERSYSTEM Bare Cu Ground <br />BONDING o WIRE <br />TERMINATION PER 71 WITH CODE APPROVE <br />NEC 14, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2014 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-17, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER CO. <br />11 <br />I <br />I 1`2 VTR <br />u I <br />I I <br />IA I <br />W I <br />3 <br />0 <br />wi ACNE ANS N <br />A. <br />/ I <br />I <br />I I I n <br />3 4It <br />I <br />c/o To M <br />qIN <br />NOTE: PLUMBING RISER IS SCHEMATIC TO SCALE: NTS <br />BE VERIFIED WITH PLUMBER <br />ENTRY <br />VERIFY METER LOCATION <br />WITH BUILDER <br />ELECTRICAL PLAN - ELEV-Al <br />SCALE: %4'=1'-0" <br />'t <br />N <br />0 <br />N <br />N <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building <br />Code - <br />Residential 7th Edition. Engineer's <br />signature and seal is only for <br />the structural engineering portions of the drawing <br />pages bearing <br />Engineer's signature and seal. <br />H <br />CCD <br />W <br />E <br />M3 <br />00 <br />N� <br />LQN <br />N <br />9 2 <br />J <br />E J LL <br />0 <br />'D <br />:5 00 N <br />rprr-'2 <br />* it-W <br />-Jw a <br />4 <br />C <br />N � <br />uJ� 3 <br />a <br />' vi YYn <br />a s <br />Z <br />13 <br />W <br />lt <br />0o <br />C <br />j '�N(U <br />L O J <br />Wing6'"' <br />Z <br />co N <br />N M Z <br />J n K <br />N <br />v_j <br />ZpV <br />co <br />W <br />❑00 <br />Hal <br />N M <br />o g <br />z N <br />z o � <br />r <br />V) <br />, M <br />W <br />V O <br />LLl <br />U <br />4 <br />L o <br />IN <br />N <br />wWINm <br />3 <br />I <br />L <br />= c5 N <br />II <br />U 0 <br />to 0 <br />¢ <br />0 <br />of <br />co <br />coS <br />z2 <br />Z <br />Q <br />U <br /><® <br />14 <br />E J <br />WO <br />on <br />R <br />o <br />U <br />Zd <br />C:) <br />i <br />a <br />ao <br />ao <br />O Z <br />a <br />wz <br />o <br />to <br />G <br />� <br />.0 <br />U <br />m� <br />O <br />Z <br />oz <br />Z <br />J <br />m <br />Q W <br />� <br />rn <br />. I <br />ao <br />o¢ <br />E <br />rn w <br />W <br /><o <br />LL <br />� <br />o <br />az <br />w <br />=3 <br />>O <br />Mi <br />�V <br />z¢ <br />d <br />0 <br />C O <br />;n <br />>� <br />rn <br />m <br />0 <br />0 <br />0 <br />O <br />\� <br />�' <br />Q <br />X <br />> <br />0 <br />CLO <br />V <br />!OR <br />V <br />f" <br />coo <br />�..� <br />E <br />r <br />co p <br />r <br />.J� <br />� <br />r <br />E <br />CV <br />M <br />o <br />z <br />ca <br />Z <br />� <br />E 0 <br />y <br />0 <br />E <br />U J <br />Q 0 <br />J <br />JOB <br />NO: <br />21-2031 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />I <br />i�.. !T 1.-_ I. fteit �__m r. N'MRt. a . <br />