ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with LIL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in LIL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/LIL 2034, standard for single and multiple station CO alarms or <br />LIL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11.In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />6. <br />�?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />FO <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />�D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />DI3 <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />a <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TV <br />TELEVISION (OPTIONAL) <br />TV 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />FPn <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />J <br />ROUGH -IN FOR OPT. CEILING FAN <br />a <br />CEILING MOUNTED LIGHT FIXTURE WI ROUGH -IN FOR <br />r J <br />OPT. CEILING FAN <br />W <br />(1I) PHONE LINE, (1) DATA PORT <br />150A/200A <br />INDOOR <br />PANEL <br />CENTER <br />#14 to lights & outlets <br />NEMA t <br />#12 to appliances and GFI <br />150 AMP! <br />200 AMP 01 <br />#10 to WH <br />#6 to Range <br />10 <br />#6 to HVAC <br />METER <br />MAOIN <br />150=2/0 <br />200=4/0 <br />IF <br />in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND Disconnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING #4 GROUNDING WIRE <br />TERMINATION PER j WITH CODE APPROVED <br />NEC 17,250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />1.5" VTR <br />I <br />III <br />I <br />I <br />,Ili 3" VTR <br />I � � <br />r T, I <br /><� I I <br />V, %/TR <br />3 <br />SWITCH <br />PLUMBING RISER_ <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />1 <br />DR M <br />O I\ <br />I <br />,jA <br />AL n <br />I <br />I <br />Q1 <br />I <br />I <br />J <br />/Idr <br />UFII Fo X <br />7, <br />I E <br />CV <br />I � GFI <br />/ <br />I <br />I <br />CIFI <br />IDW I <br />KITCHE <br />DEDICATED <br />RECEPTACLE FOR <br />CROWAVE RANGE <br />HOOD PER SPECS <br />SPEC 3 & 4 KITCHEN <br />SCALE: %4'=1'-0" <br />WID A/C PAD <br />GuuFI DISC. <br />LANAI WP _ <br />*12 GFI N 0O K <br />GI ROUGH -IN FOR <br />IOPT. CLG. FAN/ <br />LIGHT PRE -WIRE -- , <br />/ SWITCH F <br />FAMILY DISPO: <br />I PENDANT <br />I ROUGH -IN FOR AS PER <br />OPT. CLG. FAN/ SPECS <br />' LIGHT PRE -WIRE M <br />rn <br />� G � <br />FOYER <br />/ <br />I <br />I <br />.ENTRY <br />DB & GFI TO GFI <br />BE ALIGNED — — — — — — — <br />VERTICALL <br />Mr� <br />I _ J <br />GFI <br />/KITCHE <br />REF <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />_ — dFl HOOD PER SPECS <br />F <br />DINING <br />PENDANTAS <br />PER SPECS <br />` <br />III' <br />S� <br />• <br />iAND <br />SWITCH <br />:ABOVE <br />sonannannnnnnii�awnin <br />nwwwww <br />LL <br />wwwwt <br />ut I @) 44-- V V �p� ` lal-I (CV 44" kw <br />A.F.F. 1T A.F.F. lT <br />W.H. L <br />J <br />/ Z LU <br />O <br />/ Qa <br />I U J <br />Q <br />OJ � <br />-- - <br />--------r--- GARAGE f----- — —W J <br />1 >w <br />GARAGE <br />o � LIGHT AS <br />PER SPECS <br />GARAGE <br />r---------------DOOF--------------- <br />I GFI <br />IRRIGATION <br />GFI @ 44" <br />A.F.F. <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />X IY <br />w w <br />�o <br />Lu Z J <br />�O� <br />m <br />uj <br />�UI=- <br />>OJ� <br />CID <br />COACH LIGHTS COACH LIGHTS <br />OR PREWIRE AS OR PREWIRE AS <br />PER SPECS / PER SPECS <br />FIRST FLOOR ELECTRICAL PLAN — ELEV—A <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I I <br />I I <br />I I I <br />I I I <br />I I I <br />L----------I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L---------------------------------------I <br />SECOND FLOOR ELECTRICAL PLAN <br />ELEV—A <br />�9 <br />W <br />>✓' to G� 9�.1 <br />-g t <br />"- <br />Cn to <br />0,4 <br />W :a4$ <br />a cs s <br />,pt <br />M <br />N <br />0 <br />N <br />0 <br />W3 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building <br />Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />N <br />E <br />/W <br />V W C <br />0 co <br />N CO <br />H r-tea <br />10 <br />M V 3 <br />J <br />W <br />LL W <br />J LL LL <br />d <br />V (5 c <br />Z <br />13n <br />Lu <br />a <br />-C 6 O <br />t—c� <br />co <br />�$ O <br />W C/) <br />m w <br />LL z N NZ <br />LL <br />Q J <br />-0U <br />Z <br />v <br />mom W <br />El0 <br />cMt <br />O <br />� o Q <br />J <br />d. N <br />Ul z <br />Ca o <br />LL <br />C/3 <br />a <br />U <br />0 o <br />' ... <br />''V^) <br />L <br />s..,.., <br />r— J E <br />U o N <br />t <br />e <br />ALId o <br />J <br />M <br />M <br />i <br />z <br />Z <br />Z <br />Q <br />c6E <br />zo <br />oo<� <br />Zo <br />E= U <br />wz <br />oa <br />10 <br />10o <br />oa <br />o <br />0a <br />Z <br />Z—� <br />iL <br />W Oo <br />K� <br /><o <br />mo <br />o, <br />Zc <br />M —' <br />Q� <br />�w <br />ZZ <br />oU� <br />O< <br />g00 <br />U5 <br />0¢ <br />< <br />dz <br />�w <br />m <br />i0 <br />F <br />o <br />w� <br />;o <br />M <br />N 0§ <br />� <br />- <br />0 <br />2 O <br />i <br />>M <br />0 <br />m <br />m <br />C9 <br />N Q- <br />LO <br />.-. <br />°o <br />N <br />(/\ 5 J <br />in <br />�--� 0 <br />Ln <br />co N <br />m <br />O <br />LO <br />N <br />Q O N <br />r- <br />E <br />CD Lj <br />CD <br />o <br />Z <br />Z <br />E T <br />c <br />cc a <br />U -j Q p <br />JOB <br />NO: 23-04904 <br />SCALE : AS NOTED <br />SHEET NO. <br />3 <br />