ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44"AFF <br />Bathroom 39"AFF <br />Laundry Room 36"AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44"AFF <br />Range 2"AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R3114.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />1_� DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />F�F <br />K 31 --W. P. WEATHERPROOF DUPLEX OUTLET <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />K)G.F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />14 FOUR-WAY SWITCH <br />JR RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />RECESSED LIGHT FIXTURE <br />+P.C. LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUSTFAN <br />EXHAUST FAN/ILIGHT COMBINATION <br />MD ELECTRIC DOOR OPERATOR (OPTIONAL) <br />a; -_a <br />FC—H] CHIMES (OPTIONAL) <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SMOKE DETECTOR <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />pVj 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />THERMOSTAT <br />ELECTRIC METER <br />awl ELECTRIC PANEL <br />—2*-1 DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />r <br />LAV _r--, <br />1i f UB/ - <br />W/C SHOWER <br />LAV <br />3" VTR <br />OPT. <br />LAV <br />LAV <br />_L1 W/C <br />SHOWER <br />- <br />3" <br />STUDOR <br />VENTT Lrj DBLS'NK <br />W/ DISP. <br />Vael <br />PLUMBING RISER <br />SCALE:NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS - <br />UNIT -A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1 �00 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LQAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />Ist 10 KWat 100% <br />000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />P7104E <br />AIR CONDITIONER — WATTS AT 100% <br />1 <br />I <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOADWATTS -- 240VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Riser Diagram <br />4 UNIT BUILDING <br />(2) 1532 UNITS & (2) 1624 UNITS <br />800 AMP <br />0 <br />TERMINAL BOX <br />0 <br />TENANT PANEL w/ 150 <br />150 AMP <br />150 AMP <br />AMP INSIDE MAIN <br />0 <br />0 <br />150 AMP <br />150 AMP <br />0 <br />0 <br />150 AMP <br />150 AMP <br />GROUND <br />1/0 CU. TO BUILDING STEEL <br />C.O. <br />70 2" PVC CONDUIT WITH 2 �00 AL - 1 #11-0 AL-1 #1 AL <br />TO POWER CO. 6 REQUIRED PER BUILDING <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 -17 LOCAL CODES AND THE LOCAL POWER CO. <br />------------------------- <br />OUTDOOR LIVING <br />1\ A <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT' Wp <br />GFI <br />I AK <br />I <br />DINING <br />KITCHEN <br />F <br />qrl I <br />AnI 'I <br />0-0- <br />C - - GFQ <br />SWITCH FOR - <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,>ROUGH -IN\ <br />FOR OPT <br />­1'�'\"N.>FAN/LIGH`T <br />< <br />FOYER`�, <br />DB <br />�B <br />ENtRY WID 0- <br />LIGHT AS UO GFI& <br />PER SPECS <br />DB & GFI TO <br />---------- <br />BE ALIGNED <br />VERTICALLY <br />__j <br />r (�F-L — <br />rA <br />I UPSTAIRS [ <br />GFI <br />@ 44" <br />A.F.F. <br />0 <br />IGARAGE <br />I <br />GARAGE <br />LIGHT AS <br />TER SPECS <br />GARAGE <br />\=@DOOR <br />GFI <br />r--- - <br />- - - - - - - - - - - - - --- <br />LU <br />Z <br />i-E <br />Uj <br />_j <br />> UJI <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL - UNIT -A 1532 <br />SCALE: A"=V-0" <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />NOTE: <br />-INSTALL 2" CONDUIT TO METER CAN <br />-INSTALL A MAIN 150 AMP BREAKER IN PANEL <br />OWNER'S <br />BEDROOM <br />/,>ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT <br />v <br />0. BATH <br />BATH 2 <br />­11;�1.7 <br />wic <br />LL---------- <br />L____ <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />---------- <br />�/p <br />�_-L-WIC <br />Al <br />LOFT <br />/,,>ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT <br />\BEDROOM 2 <br />2ND ELECTRICAL - UNIT -A 1532 <br />SCALE: X"=V-0" <br />C17) <br />C14 <br />j%J1111ij:11 1r C:� <br />N. L E <br />I%N ....... 0.- <br />C) EN** <br />No PE78750 <br />STATE <br />OF fu <br />n R <br />% <br />C. <br />10 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />dravAngs comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />E S c-4 <br />0, 8 R C-0 <br />C-1 <br />N <br />0 <br />4� <br />D CWo <br />_0 ce L� <br />('40 - a. uj <br />C') V <br />Z <br />0 <br />W <br />W <br />5 04 <br />0 1­ co <br />(1) cp . - Z <br />Z <br />IL <br />OD & 0 <br />. c) Z U) <br />04 <br />a <br />Z <br />< <br />d 0 <br />W <br />< <br />V) <br />.8 <br />a) <br />(D 5 <br />4-j <br />C�; LLI <br />I U <br />DV) <br />0 <br />V) <br />Le <br />E <br />C) <br />< <br />0 <br />C, <br />C"I <br />E <br />0 <br />W3 <br />8 E <br />Co <br />C <br />M <br />t <br />ZZ <br />0 <br />M <br />0 <br />L <br />CN <br />0 <br />C_� <br />C0 00 <br />CN <br />ct') <br />00 <br />60 <br />oo <br />:3= <br />0 <br />C'14 <br />F— <br />cv) <br />C14 <br />L0 <br />C) <br />CN <br />CD <br />Q <br />LO <br />=? <br />CD <br />Lo <br />74" <br />0 <br />0 <br />E <br />T_ <br />0 <br />Z <br />LD <br />a. <br />0 _j <br />CU <br />a <br />3 <br />JOB <br />NO: 23-13121-13124 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />