ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be Installed in all dwelling units In <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed Within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The Width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I� <br />SPECIAL PURPOSE OUTLET <br />IET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />'4 � <br />FOUR-WAY SWITCH <br />�R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />[jaD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />�L <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />., <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />01 #14 to fights & outlets <br />NEMA 1 0 012 to applisnCes and GFI <br />150 AMP/ <br />200 AMP 10 #10 to WH <br />#8 to Range <br />10 #6 t0 HVAC <br />150=2/0 <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND DIa nnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING =F1 �*4ROUNDING WIRE <br />TERMINATION PER WITH CODE APPROVI <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />1.5" VTR <br />`I q <br />I <br />I <br />,111 3" VTR <br />I � I <br />I.i I <br />wit' I I <br /><�\ I I <br />.111 \!TR <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />OR <br />SWITCH FOR <br />DISPOSAL <br />/ IF)W_J <br />KITCHEN <br />C <br />DEDICATED <br />RECEPTACLE FOR <br />CROWAVE RANGE <br />HOOD PER SPECS <br />SPEC 3 & 4 KITCHEN <br />SCALE: %'=11-0" <br />WP A/C PAD <br />GFI DISC. <br />LANAI WP <br />GFI <br />G � <br />' ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />I SWITCH F OR <br />FAMILY DISPOSAL <br />I PENDANT <br />I ROUGH -IN FOR AS PER <br />OPT. CLG. FAN/ SPECS <br />I LIGHT PRE -WIRE ih <br />/� to <br />I <br />FOYER <br />/ <br />I <br />• B <br />/ I <br />/ I <br />'IE NTRY�p <br />DB &GFI TO GFI <br />BE ALIGNED — — — — — — — <br />VERTICALL <br />I <br />1 <br />Lem <br />I _ J <br />GFI <br />j /KITCHE <br />I <br />REF <br />I <br />7£ CH <br />DINING <br />' PENDANT AS <br />PER SPECS <br />I <br />C.M. <br />TO LIGHTS <br />AND <br />SWITCH <br />ABOVE <br />MEN <br />%AU <br />PWDR I W. <br />GFI 11 D. � <br />42"jk I <br />Ur -I ICU 44 uV `g,— " Uri (CU 4,4 ' f WJJ <br />A.F.F. Tr' A.F.F. 1T LWH. <br />\ J <br />/ Z 1 Z O <br />I Qa <br />I U4 <br />oIX <br />1 GARAGE > w <br />GARAGE` <br />� \\ GHT AS <br />PIER SPECS �--�—�—'--J <br />v <br />GARAGE <br />r--------------- DOOR --------------- <br />1 GFI <br />IRRIGATION <br />GFI @ 44" <br />A.F.F. <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />IX = <br />w w <br />I— <br />wZ0 <br />0 to <br />Ir <br />job <br />COACH LIGHTS COACH LIGHTS <br />OR PREWIRE AS OR PREWIRE AS <br />PER SPECS .� / '� PER SPECS <br />FIRST FLOOR ELECTRICAL PLAN - ELEV-A <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I I <br />I I I <br />I I I <br />I I I <br />I I I <br />L----------I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L--------------------------------------J <br />SECOND FLOOR ELECTRICAL PLAN <br />ELEV-A <br />a!V <br />u� <br />+R�ll <br />rpn. <br />`O <br />Oi <br />>r cr <br />ci a tom. o <br />C t9 f, N <br />-•tam x <br />rn a 'l• a. <br />_w <br />Q t'V <br />Y <br />•a � t c <br />,,y ceia d <br />N t9..fJ <br />c E <br />m 0 <br />Q. u <br />0 <br />M <br />O <br />(V <br />s <br />To the best of the Engineer's knowledge, Information and ballet, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code <br />- <br />Residential 7th Edition. Engineer's signature and seal <br />Is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />40 <br />N <br />0 <br />� <br />Be <br />/M <br />C) � VM LL <br />eL a <br />Z <br />�LLll <br />a Z <br />0 <br />W <br />N�u� <br />rnm <br />W <br />2 <br />J <br />M Z Q <br />N OU <br />ZCL <br />W <br />00 <br />CD <br />z <br />l_ <br />v0 <br />in <br />� <br />O <br />JOL <br />Ln <br />�V) <br />601 <br />=1 <br />s <br />0 <br />n <br />Z <br />Ca <br />M <br />�� <br />z <br />Q <br />r.._ <br />E <br />a <br />ZO <br />' M <br />z® <br />E p <br />U <br />9 to <br />�° <br />�e <br />'Q <br />oa <br />u� <br />ZoZ <br />8 Ewz <br />52 <br />�a <br />tin r`o <br />y c <br />Q <br />sY <br />o <br />z <br />Z <br />r��yff <br />c3 J2{$y <br />aw <br />� <br />3 y <br />]Z <br />U <br />W <br />i <br />M <br />m� <br />O <br />�w <br />c1 <br />a ° <br />0� <br />° <br />0 <br />cC:) <br />>M <br />N <br />cc <br />cv <br />;n✓1 <br />� <br />� <br />CO <br />Lis <br />T <br />Oa <br />Ln <br />CoO <br />L>n <br />o <br />LL <br />co 04 <br />0) <br />N <br />Q <br />� N <br />00 04 <br />T <br />cc <br />M <br />CD <br />o <br />z <br />E 0 <br />a <br />0 � <br />Q o <br />JOB <br />NO: <br />23-00507 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />