Laserfiche WebLink
I� <br />R <br />E <br />T <br />O <br />P <br />Y <br />S <br />T <br />E <br />M <br />01 <br />THROUGH -PENETRATION DETAIL <br />5'I'STEM No. F-A-101 5 <br />F RATINGS - 2 HR <br />1. FLOOR ASSEMBLY - THE FIRE -RATED UNPROTECTED CONCRETE AND STEEL FLOOR <br />ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER <br />SPECIFIED THE INDIVIDUAL D900 SERIES DESIGNS IN THE U.L. FIRE RESISTANCE <br />DIRECTORY AND AS SUMMARIZED BELOW: <br />A. CONCRETE - MIN 2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT <br />(100-150 PCF) CONCRETE. <br />B. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON -COMPOSITE MAX <br />3 IN. DEEP GALV FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING <br />DESIGN. MAX DIAM OF OPENING IS 6 IN. <br />2. THROUGH PENETRATIONS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED <br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. <br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH <br />OPENINGS SHALL B MIN 0 IN. (POINT CONTACTS) TO MAX 1-7/8 IN. PIPE, CONDUIT OR <br />TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. <br />THE FOLLOWING TYPES AND SIZES OF MTALI_IC PIPES, CONDUITS OR TUBING MAY <br />BE USED: <br />A. STEEL PIPE <br />B. IRON PIPE <br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC <br />TUBING OR STEEL CONDUIT. <br />D. COPPER TUBING <br />E. COPPER PIPE <br />3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: <br />PACKING MATERIAL - MIN 1-1/2 IN. THICKNESS OF MIN 4 PCF DENSITY MINERAL <br />WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. <br />PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS <br />REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL (ITEM 3B). <br />FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1/2 IN. THICKNESS OF FILL <br />MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. AT <br />POINT CONTACT LOCATION BETWEEN PENETRANT AND CONCRETE, A MIN 1/2 IN. <br />DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE/PENETRANT <br />INTERFACE ON TOP SURFACE OF FLOOR. <br />FIRESTOP SYSTEM INC. - 4800 DW <br />*BEARING THE UL CLASSIFICATION MARKING <br />THROUGH -PENETRATION DETAIL <br />F <br />51'STEM No. W-J-104P5 <br />R F RATINGS - 2 HR <br />E 1 <br />S <br />T A <br />O <br />P 3 <br />S <br />Y <br />s <br />T 2 <br />E L.A <br />M <br />SECTION A -A <br />1. WALL ASSEMBLY - MIN 6-1/8 IN. THICK NORMAL WEIGHT OR LIGHTWEIGT <br />(100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY U.L. <br />CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 14-1/8 IN. <br />SEE CONCRETE BLOCKS (CAZT) CATERGORY IN THE FIRE RESISTANCE DIRECTORY <br />FOR NAME OF MANUFACTURER. <br />2. THROUGH PENETRATIONS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED <br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. <br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF <br />OPENINGS SHALL BE MIN 3/8 IN. TO MAX 1 IN. PIPE, CONDUIT OR TUBING TO BE <br />RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING <br />TYPES AND SIZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY BE USED: <br />A. STEEL PIPE <br />B. IRON PIPE <br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC <br />TUBING OR STEEL CONDUIT. <br />D. COPPER TUBING <br />E. COPPER PIPE <br />3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1-1/4 IN. THICKNESS <br />OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF <br />OF WALL. <br />FIRESTOP SYSTEM INC. - 4800 DW <br />*BEARING THE UL CLASSIFICATION MARKING <br />FIRE ALARM NOTES: <br />SEQUENCE OF OPERATION: <br />1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS: <br />A. MANUAL PULL STATION: <br />1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE ALARM AT THE FACP. <br />3) ILLUMINATE THE ALARM RED LED. <br />4) SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES) <br />IN THE BUILDING. <br />B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER - <br />FLOW SWITCH SHALL CAUSE THE FOLLOWING: <br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION, <br />2) A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER -FLOW ALARM <br />SHALL NO BE ABLE TO BE SILENCED. <br />C. SMOKE DETECTORS FOR ELEVATOR RECALL: <br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION. <br />2) REFER TO ELEVATOR RECALL SEQUENCE OF OPERATION. <br />D. SMOKE DUCT DETECTORS : <br />1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP. <br />3 ILLUMINATE THE SUPERVISORY LED. <br />4 SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT, <br />E. FLOW BELL : <br />1) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF FLOW SWITCH ONLY. <br />2) FLOW BELL SHALL SOUND AS LONG AS THE WATER IS FLOWING. <br />3) FLOW BELL SHALL NO BE CAPLABLE OF BEING SILENCED FROM THE FACP, <br />F. ACTIVATION OF ANY SUPERVISORY CIRCUIT OR TAMPER SWITCH SHALL CAUSE THE <br />FOLLOWING ACTIONS AND INDICATIONS: <br />1) IDENTIFY THE INDIVIDUAL CIRCUIT OR DEVICE ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP. <br />3) ILLUMINATE THE SUPERVISORY LED. <br />G. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE <br />FOLLOWING ACTIONS AND INDICATIONS: <br />1)IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP. <br />3) ILLUMINATE THE TROUBLE LED. <br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE DISPLAYED ON <br />THE MAIN FIRE ALARM PANEL AS WELL AS ON ALL REMOTE ANNUNCIATOR PANELS. <br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE TRANSMITTED TO <br />A LISTED CENTRAL STATION. <br />CENTRAL STATION / TRANSMISSION OF SIGNALS / MONITORING <br />- ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE <br />CENTRAL STATION. <br />- THE MEANS OF TRANSMISSION IS WIRELESS DIALER. <br />- ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS: <br />A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION, <br />SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW: <br />DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION <br />(FLOOR + GENERAL DESCRIPTION) i INDIVIDUAL BUILDING PHYSICAL ADDRESS <br />OR BUILDING NUMBER. <br />- THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE <br />THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD. <br />CODES & PLAN NOTES <br />- ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED. <br />- COORDINATE WITH SPRINKLER CONTRACTOR EXACT LOCATION OF ALL <br />TAMPER AND FLOW SWITCHES. <br />- INSTALL STROBE BOX FOR FUTURE ADA USE IN ALL 1ST FLOOR APARTMENT'S <br />BATHROOMS. <br />- CONFIRM LOCATION OF POWER SUPPLIES IN BLDGS PRIOR TO ROUGH IN. <br />- REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR <br />RETURN SIDE), COORDINATE WITH MECHANICAL CONTRACTOR THE ACTUAL <br />LOCATIONS OF THE AHUs. <br />- ALL STROBES WILL BE SET @ 75cd UNLESS NOTED. <br />- CEILING HEIGHT IS 10ft UNLESS NOTED. <br />- UNDERGROUND WIRE USED AS SLC FOR COMMUNICATION BETWEEN BUILDINGS <br />IS SUITABLE FOR WET LOCATIONS / DIRECT BURIAL. <br />- ANY PROPOSED INTERCONNECTION OF PANELS WILL BE A "NON -LATCHING" <br />CONFIGURATION PANEL RESET FROM 1 LOCATION. <br />- FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE. <br />- SMOKE DETECTORS FOR SMOKE COMPARTMENTS WILL BE PROVIDED <br />AS PER NFPA-72 17.7.5.6.5.1 (A) <br />- COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF SMOKE DAMPERS <br />- SINGLE STATION 120 AC SMOKE DETECTOR AND C/O DETECTORS PROVIDED BY <br />ELECTRICAL CONTRACTOR ON SEPARATE PERMIT. <br />- ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT <br />PERMIT #########. FBC 107.2 <br />- INSTALLATION SHALL BE IN ACCORDANCE WITH 2O20 FFPC 7TH ED., NFPA 72 2016 ED. <br />NFPA 1 2018 ED., NFPA 101 2018 ED. AND NFPA 13 2016 ED. <br />24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE. IF BUILDING IS OCCUPIED <br />DURING THIS TEST, FIREWATCH WILL BE REQUIRED. <br />- ALL AUDIBLE DEVICES LOCATED INSIDE SLEEPING AREAS MEET NFPA-72 (2016) <br />18.4.5.3 FOR LOW FREQUENCY REQUIREMENTS <br />- ALL NEW SYSTEMS SHALL INCLUDE A DOCUMENT CABINET. <br />** 24/5 STANDBY TEST REQUIRED IF ANY PART OF THE BLDG IS OCCUPIED <br />BY TENANTS DURING THIS TEST, A FIRE WATCH IS REQUIRED FROM <br />7AM-7PM. <br />"CADDY" T-GRID BOX HANGER\ <br />SUPPORT, OR EQUAL. "CADDY'—' <br />REFERENCE NO. CEC 30-302(3). <br />ELECTRICAL MOUNTING BOX <br />FOR THE CEILING MOUNTED <br />NOTIFICATION DEVICES. <br />ACOUSTICAL TILE CEILING <br />GRID SUPPORT FRAMING. <br />CEILING GRID ELECTRICAL BACK —BOX ATTACHMENT <br />FIRE ALARM DEVICE LEGEND <br />SYMBOL <br />DEVICE DESCRIPTION <br />FACP 0 <br />FIRE ALARM CONTROL PANEL <br />co <br />Fp <br />REMOTE ANNUNCIATOR PANEL <br />Z <br />co <br />U <br />FCPs <br />[:;aPOWER <br />SUPPLY EXPANDER <br />co <br />W <br />Fp <br />FIRE ALARM TERMINAL CABINET <br />z <br />�a <br />MIC <br />0 <br />REMOTE MICROPHONE PANEL <br />AUD;-d <br />AUDIO PANEL <br />DIALER <br />FIRE ALARM DIALER <br />SYMBOL <br />DEVICE DESCRIPTION <br />HORN/STROBE WALL MOUNT <br />wp <br />HORN/STROBE OUTDOOR <br />�4 CM <br />HORN/STROBE CEILING MOUNT <br />N❑4 LF <br />LOW FREQUENCY FREQUENCY <br />O <br />SPEAKER/STROBE WALL MOUNT <br />UWp <br />SPEAKER/STROBE OUTDOOR <br />LL- <br />❑s 4 CM <br />SPEAKER/STROBE CEILING MOUNT <br />O <br />Z <br />❑s <br />SPEAKER <br />F❑�' <br />STROBE <br />F Wp <br />STROBE OUTDOOR <br />zo CM <br />STROBE CEILING MOUNT <br />194 <br />LOW FREQUENCY HORNS <br />SMOKE SOUNDER BASE <br />SPRINKLER BELL <br />SYMBOL <br />DEVICE DESCRIPTION <br />F❑ <br />PULL STATION <br />�wp <br />PULL STATION OUTDOOR <br />e <br />SMOKE PHOTO DETECTOR <br />eION <br />SMOKE ION DETECTOR <br />O <br />BCO <br />SMOKE C/O DETECTOR <br />Q <br />(D <br />HEAT DETECTOR <br />~ <br />Z <br />DUCT DETECTOR SUPPLY SIDE <br />DUCT DETECTOR RETURN SIDE <br />©s g <br />FLOW SWITCH <br />® <br />BEAM DETECTOR <br />-1 <br />MONITOR MODULE <br />M❑4 <br />MINI -HORN <br />®wP <br />HEAT DETECTOR WEATHER PROOF <br />v) <br />SYMBOL <br />DEVICE DESCRIPTION <br />OTAMPER <br />SWITCH <br />- <br />® <br />RELAY <br />z <br />EOL <br />END OF LINE RESISTOR <br />v <br />SURG <br />SURGE SUPRESSOR <br />DOOR HOLDER <br />RTS <br />REMOTE TEST SWITCH <br />❑ <br />CONTROL MODULE <br />LU <br />0.❑ <br />LOCK BOX (PROVIDED BY OTHERS) <br />co <br />CEILING MOUNTED <br />SMOKE/HEAT PERMNFPA 72 <br />DETECTOR <br />24" MIN HANDICAP A/C SUPPLY DIFFUSER <br />BEDROOM STROBE <br />AUDIO/VISUAL CEILING MOUNTED NOTIFICATION <br />VICESVISUAL-ONLY <br />DEVICE (TO BE WHITE). <br />SEE PLAN FOR LOCATION. <br />MORE THAN TWO APPLIANCES <br />IN THE SAME ROOM OR ADJACENT <br />SPACE WITHIN THE FIELD OF VIEW <br />SHALL FLASH IN SYNCHRONIZATION, <br />80" MIN <br />96" MAX <br />NFPA 72 2016 <br />(ADAAG) <br />80" ABOVE HIGHEST FLOOR <br />LEVEL OR 6" BELOW CEILING <br />TO THE BOTTOM OF THE <br />STROBE. WHICHEVER IS LOWER. <br />FINISHED <br />FLOOR <br />5'-0 <br />MAX FROM EXIT DOOR <br />ACCEPTABLE HERE,/ <br />DO NOT INSTALL, <br />IN THIS AREA <br />WALL MOUNTED <br />HEAT DETECTOR — <br />TO THE BOTTOM. <br />WALL MOUNTED <br />SMOKE DETECTOR — <br />TO THE TOP. <br />4" <br />MANUAL -� <br />PULL <br />STATION <br />O 6„ <br />MAGNETIC/ <br />DOOR <br />HOLDER <br />48" (ADA) <br />TO THE WORKING MECHANISM <br />48" ALSO MEETS THE <br />REQUIREMENTS OF NFPA 72 2016 <br />IMPORTANT NOTE <br />NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE <br />THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH <br />DEVICES APPLY, AND WHICH DO NOT. <br />SI TE PLAN <br />FIRE ALARM DEVICE MOUNTING <br />NOTE <br />CHECK WITH MANUFACTURE'S INSTALLATION SHEET <br />FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF <br />BACK BOXES, AND WIRING REQUIREMENTS. <br />4" <br />12" (MAX) <br />REMOTE <br />ANNUNCIATOR <br />w a <br />57< <br />� o <br />0 <br />o <br />CC Ln <br />GUIDE <br />THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND <br />SEALED BY SAMUEL P. DEAN, P.E. ON [11.28.2022] USING <br />A SHA 1 AUTHENTICATION CODE. PRINTED COPIES OF <br />THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND <br />SEALED AND THE SHA-1 AUTHENTICATION CODE MUST <br />BE VERIFIED ON ANY ELECTRONIC COPIES. <br />uperier <br />Fire Alarm & C mmunicati ns <br />Cust mer Service is ur Greatest TeOn I gy. <br />BE <br />SUPERIOR HIRE ALARM 8c <br />COMMUNICATIONS <br />6201 JOHNS ROAD <br />SUITE 9 <br />TAMPA, FL 33634 <br />81 3— 818— 4444 <br />CERTIFIED ALARM SYSTEM <br />CONTRACTOR 1 <br />LICENSE EF 20001 162 <br />U_ <br />V7 <br />�-. <br />E <br />s <br />Ey <br />iL <br />W <br />N <br />O <br />? <br />N <br />U <br />Q <br />U <br />14- <br />O <br />i <br />U <br />_ja <br />az <br />O f- <br />U� <br />c= w <br />ir OQ <br />3 LL<L <br />J LL <br />J Z <br />Q <br />CAD DATE: 9/9/2022 <br />NO. ISSUE/REVISION DATE <br />p���-VEL P D <br />No 88915 <br />9 : STATE OF <br />dAL <br />fills <br />Digitally signed <br />by Samuel P. <br />Dean <br />Date: 2022.11.28 <br />09:17:31-05'00' <br />SAMUEL P. DEAN P.E. <br />CONSULTING ENGINEER <br />REGO MTION NUMBER 8891E <br />CA AF 20M <br />1503-A WEST BUSCH BLVD. <br />TAMPA FLORIDA 33612 <br />PHONE: (813) 961-3075 <br />FAX: (813) 961-1031 <br />email: sdeon@beltengineering.com <br />I CERTIFY THAT TO THE BEET OF MY RUOWLEBBE AND BELIEF <br />ALL OF THE STRUCTURAL ELEMENTS AND SYSTEMS FOR THIN <br />STRUCTURE HAVE BEEN OEIWNED TO BE IN COMPLIANCE <br />WTTN THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL <br />OTHER ELEMENTS, SYSTEMI AND ASSEMBUES ARE THE <br />TOTAL RESPONSIBNdTY OF OTHERS. <br />FIRE ALARM <br />FA- I of 2 <br />