GBLE-END
<br />HIPRCOF
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 71
<br />PS ZONE 1 = 8.97 F (19.97)
<br />ZONE 2 =17.98 PSF (27-98)
<br />ZONE 3 = 33.53 PSF (43.53)
<br />"A'= 4%0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: "B'
<br />RISK CATAGORY: 11
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT w 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16"
<br />O.S.B. OR IQ" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 518 COX EXT. PLYWOOD, WITH Sd RING
<br />.SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT W O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS 4" O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN, DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />8d
<br />RING SHANK,
<br />2 1/2"
<br />0.120"
<br />170,000
<br />i RING
<br />RINGS
<br />SCREW SHANK
<br />PER INCH)
<br />8d
<br />SCREW SHANK
<br />2 1/2"
<br />0.120"
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIOR SHEA741,110
<br />USE 1/2" COX OR 7/16" O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" O,C. AT PANEL SIDES
<br />AND Bd RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND Sd RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />8d RING SHANK GUN NAILS Qa 4" O.C.
<br />.. TOP & BOTTOM EDGES ..
<br />Z
<br />O
<br />Zw.
<br />2 Z .
<br />U
<br />to Oa to
<br />N .
<br />J
<br />.
<br />C D
<br />z .
<br />Z
<br />Q
<br />N
<br />CD .
<br />Z
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER TRUSS
<br />R!1(1F CHPAFATHINr
<br />Emm
<br />-_-_�'
<br />_�,I
<br />.--mm
<br />mmm
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />Sd RING SHANK GUN NAILS
<br />(� 6" O.C. IN FIELD `
<br />8d RING SHANK GUN NAILS @ 12' O.C. IN
<br />FIELD or 8d x 2 1/2" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS @ IZ' 0.En jN
<br />FIELD J\
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION
<br />ACI 918-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 6-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33 MAX" AGGREGATE SIZE SWILL BE 3/d'.
<br />PROVIDE 6%AIR ENTRNNED CONCRETE EXPOSED TO EARTH OR WEATHER WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF.
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED SIC,
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />Sd RING SHANK GUN NAILS
<br />(� 6" O.C. IN FIELD `
<br />8d RING SHANK GUN NAILS @ 12' O.C. IN
<br />FIELD or 8d x 2 1/2" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS @ IZ' 0.En jN
<br />FIELD J\
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION
<br />ACI 918-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 6-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33 MAX" AGGREGATE SIZE SWILL BE 3/d'.
<br />PROVIDE 6%AIR ENTRNNED CONCRETE EXPOSED TO EARTH OR WEATHER WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF.
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED SIC,
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb - 1100 PSI AND A MODULUS OF
<br />PROVIDE 6.MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-ONGROUND VAIERE INDICATED ON
<br />ELASTICITY :ILLS,
<br />AOO,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />DRAWINGS. SEAMS LAPPED 6INCHES AND SEALED WITH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORMWORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS,
<br />MINIMUM NAILING PER PSCR 2017, 601 EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYp 02.
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WELDED WIRE MESH, SWILL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WOOD TRUSSES:
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2" CHAIRS SPACED T-O' OC EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS"BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL: CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM ASI S GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 MEETING THE REQUIREMENTS OF ASTM A446, GRADE A. AND SHALL BE HOT4NPPED GALVANIZED.
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS: W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI.14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL STANDARDS FOR METAL-PLATECONNECTED-WOOD TRUSS CONSTRUCTION:, AND TPWVTCA BCSI 1-
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 Pt R VI VERTICAL SARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL-PLATECONNECTED
<br />20 pef TOP CHORD narrerd TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' #6 BAR - 36" EW
<br />WOOD TRUSSES.
<br />-OOR-co
<br />10 paf BTM CHORD -rronoDncu"Brd
<br />DEADLOAD
<br />15 paf TOP CHORD
<br />(7 paf W/ ASPHALT SHINGLES)
<br />10 paf BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10paf
<br />DEAD LOAD
<br />20 pat TOP CHORD
<br />(10 paf W/ ND GYPCRETE)
<br />5 paf BTM CHORD
<br />BALCONY LIVE LOAD 60 Pf
<br />STAIRS LIVE LOAD 40 Pf
<br />#6 BAR - 30' #7 BAR - 42'
<br />PROVIDE 36" x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A68.1-1982.
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />WIND: DEAD LOAD SPEED =150 MPH 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE 7.10 (FBC R2017) EXPOSURE B, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 1OPef, UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: 20Pf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pef, BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />AND DECKS: 40Pf, GUARDS AND HANDRAILS: 2DOPf, GUARD IN -FILL COMPONENTS: SOpt, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF ?BUSSES. THE TRUSS FABRICATOR SHALL
<br />GARAGES: 50pef, ROOMS OTHER THAN SLEEPING ROOM: 40Pf, SLEEPING ROOMS: 30p f, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />IS
<br />40EHHItCLE
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ASCE 5RMS 402, BUILDING CODE REQUIREMENTS FOR
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fht = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS, GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. N4 ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE MAXIMUM 318'
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATIOW SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 Pf, FOOTING
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />CELLS TO BE FILLED,
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING,
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE•COMPACTEO AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTURAL STEEL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />CONCRETE:
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A38, Fy = 36 kel FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM... GRADE B,
<br />Fy = 46 X.I. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B. TYPE E OR S, Fy = 35 ft. TUBE AND PIPE
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-ON-GRADE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />CONNECTOR 9HAI.L eIRIMIT PROP09ED MIX DE91CfJ3, WITN M970RICAL STRENGTH DATA FOR EACH SEPARATE NIX PRIOR TO
<br />OTHER BOLTS BE ERS THE TURNED ELEMENT. BOLTS SHALL
<br />CONCRETE PLACEMENT, CONCRETE SLUMP SHALL NOT EXCEED SH- PRIORTO THE ADDITION OF PLASTICIZER,
<br />METHNDER
<br />INACCORDLL
<br />NCE WITH THE
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF AC1301 AND ASTM CA4OR MEASURING, NIXING, TRANSPORTING, ETC.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE LR BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE NIX UNTIL IT IS DEPOSITED INITS FNAL POSITION SM U. NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH 15 HELD FOR LONGER THAN 90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONSIRUT' OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE NTH THE ABOVE
<br />REOURED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A TFDR CONCRETE CAST AGAINST AND PEFMAFENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />1-1/2'FOR 06 AND SMALLER
<br />2-FOR 06 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SUBS, WALLS AND JOISTS
<br />1.12" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEOE THOSE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPUCATpN
<br />Sm
<br />TYPE
<br />SPACa1G
<br />REIMPo49
<br />APPUCATpN
<br />SITE
<br />TYPE
<br />9PACaVG REMARK$
<br />14 PT FUI NJG TO
<br />CASE HAPDENEDCOIL
<br />.-GE--
<br />-DW.
<br />1-I-EMBEO.,
<br />A'END OUST.,
<br />MASONRY/GONG
<br />NAIL112^LONG.
<br />B O,C
<br />TO MASONRY`WNc.
<br />NOWASHER
<br />FASTENER
<br />S OF 11?EGGEGST.
<br />SOD, AL. EXT. DOORS
<br />CASE HARDENED COIL
<br />9'CdC
<br />WINDOWNOCRIFASTENED
<br />GAAADE DOOR BJCK
<br />-DK WI
<br />E.-IONBOLT
<br />1A"OTC A"EMBED.,'"ENOGST.,
<br />ITPT,SEENDIES
<br />NMLit(YLONG.
<br />9TAGGERED
<br />MTO MASONRY/GONG.
<br />TO MASWIRYICOrIC.
<br />WASHER
<br />YEDGE DST.
<br />wuroaN Bucx
<br />-HAROENEG-
<br />raD
<br />WWDowl000w FASTENED
<br />METAL STRAP To
<br />CONTACT THIS ENGINEER FOR SPACING
<br />t I1 PT, SEE NOTEB
<br />HAIL 1114'LONG.
<br />STAGGERED
<br />INro MAsav6rnxWc.
<br />MAsormrl cmx.
<br />REQUIREMENTS
<br />EXT. SYIMG D00R
<br />(1)3'16'OW.
<br />^TAPCOrf
<br />11R'EMBED.B•END.
<br />NIXIBEARING WOW
<br />1Yl EXPANSION-EMBEG.f E10
<br />�" QC
<br />BUCK 2� PT, 9EE NOTEB
<br />NO WASHER
<br />FASTNER
<br />DIST.,11fC EDGE DUST.
<br />WALL TO COWC. SIAB
<br />WI WASHER BOLT DST., 3• EDGEGST.
<br />L�wN/�« at]B•Pu a]LS' YO•G PEND.OIST,11?
<br />PT IO STEELLQ., 9EF
<br />NOTE S yy/yyggRER 9TAGGERED EDGE DST.
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DDORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAP DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32780
<br />PH:407-774.6078
<br />FAX: 407-774.4078
<br />www.abdoslgngroup.com
<br />AA M: 0003325 A
<br />4
<br />�_
<br />P
<br />�le
<br />y4
<br />•
<br />6
<br />�
<br />I]P
<br />3tmDm AL: TATSILVERADO
<br />LOT #12
<br />BLK #19
<br />ROJECT/
<br />04128.002-12191
<br />MODZIU
<br />4EAB
<br />"1672- ARIA"
<br />GARAGE 8W MG:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />150 MPH EXP. B
<br />12
<br />1 SCALE: 1/4"=1'-0- 1
<br />SN1