GABLE -END
<br />HIP ROOF
<br />ROOF WIND DESIGN PRESSURES
<br />NET(GROSS) ASCE 7-10
<br />ZONE 1 = 8.97 PSF (19.97)
<br />ZONE 2 = 1798 PSF (27.98)
<br />ZONE 3 = 3153 PSF (43.53)
<br />"A"= 4'-O' END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE:'B'
<br />RISK CATAGORY: It
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT+- GAS
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116"
<br />O.S.B. OR 12"CDX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 5/8 COX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS G 4" O.C. EDGEWISE 2X4
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />ENO
<br />k A�
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STIR.
<br />SHANK
<br />8d
<br />RING SHANK,
<br />2 12"
<br />0.120"
<br />170,000
<br />RI
<br />6-
<br />16-20 RINGS
<br />SCREW SHANK
<br />INCH)
<br />8d
<br />SCREW SHANK
<br />2 1/2"
<br />0.120"
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 1/2" CDX OR 7116" O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />z W
<br />Z O
<br />LU
<br />Y@
<br />Q L)
<br />2 �
<br />L7
<br />w
<br />w
<br />ft
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />TOP & BOTTOM EDGES
<br />J
<br />Q
<br />Z5
<br />� w
<br />Z
<br />�0
<br />N y
<br />J Z
<br />K D
<br />? S
<br />3
<br />1
<br />Q w
<br />on �
<br />Z�
<br />J
<br />W
<br />0w
<br />Z
<br />CCU
<br />U) O
<br />a
<br />_Z
<br />IL
<br />M
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END. -
<br />RAFTER OR TRUSS
<br />RDLIF RHPATHING
<br />e a
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />8d RING SHANK GUN NAILS
<br />R 6" O.C. IN FIELD
<br />C8d RING SHANK GUN NAILS @ 12" O.C. IN
<br />FIELD or 8d x 2 12" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS Q 12" 0.6wIN
<br />FIELD J\
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />8d RING SHANK GUN NAILS
<br />R 6" O.C. IN FIELD
<br />C8d RING SHANK GUN NAILS @ 12" O.C. IN
<br />FIELD or 8d x 2 12" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS Q 12" 0.6wIN
<br />FIELD J\
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXIMUM AGCREGATESUE SK41 BE YV.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />EXPOSED EARTH ORNlEATHER
<br />WOOD.
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 6%AIR ENTRAINED CONCRETE TO
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES DEPRESSIONS AND OTHER DETAILS NOT SHOWN
<br />TO CHAMFERED 314'.
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBGR 2017, 6th EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE BE
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-0ON-GROUND WHERE INDICATED ON
<br />B RRI
<br />NE VAPORLED
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />PROVIDES. SEAMS UPPED BINCHETHYLSAND ESMETAPE.
<br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM -WORK:
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN `/V OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBOR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS,
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALAEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH T CHAIRS SPACED T-0- OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRAPE LUMBER AND ITS FASTENINGS" THE NFTRUSS DESIGNS SHALL SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA.O SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0436' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 60 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND TPI1WTCA BCSI V
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 paf
<br />REVIEW,
<br />WOOD TRUSSES.
<br />20 paf TOP CHORD -non-concurrent
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 38"
<br />10 pat BTM CHORD -non-concurrent
<br />#5 BAR - 30" #7 BAR - 42"
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36" x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982.
<br />15 paf TOP CHORD paf TOP CHORD
<br />I7 par w/A3PHALT SHINGLES) (1 paf w/ No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 paf BTM CHORD 5 paf BTM CHORD
<br />5
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf
<br />MINIMUM 101NCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 Pat
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 PSI
<br />WIND: DEAD LOAD SPEED =150 MPN 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS:
<br />STORAGE:: WITH BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />40p NTS:
<br />AND DECKS; 40pat, GUARDS AND HANDRAILS: 200pst, GUARD IN -FILL COMPONENTS: SOpaf, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: SOpaf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30paf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40paf
<br />MASONRY'
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ ASCE S/TMS 402, BUILDING CODE REQUIREMENTS FOR
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />MASUSEONRYFORWIT
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT TO FILL MASONRY CELLS SHALL COMPLY
<br />IT
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />L
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BEE PLACED W/ A SLUMP OF 8" TO 10', USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION:
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 Pat, FOOTING
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1657. TREAT ALL
<br />CELLS TO BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEDE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT EEO -TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED S * PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MIXING, TRANSPORTING, ETC.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TINE ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE MIX
<br />UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A HATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONSIBIUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPUANCE WITH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER RESAR SHALL SEAS FOLLOWS:
<br />A 3" FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />1-1N" FOR 46 AND SMALLER
<br />2' FOR 0
<br />8 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3N. FOR SLABS, WALLS AND JOISTS
<br />1-Irr FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURALSTEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />ASS, Fy = 36 kal FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A500, GRADE 8
<br />Fy = 46 MI. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S. Fy = 35 kal. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLIUTION
<br />E.
<br />TYPE
<br />SPACMG
<br />REMARKS
<br />APPLICATpN
<br />SME
<br />TYPE
<br />I SPACWG
<br />REMAR1t9
<br />i PTFURRNGTO
<br />MASONRY100NC,
<br />CAGE IUPDENEG COIL
<br />NNL 11?LONG.
<br />a--
<br />GARAGE NOR SHELF
<br />TO MASONRYKx c
<br />1l4•DLA
<br />—HER
<br />TAPCONMASIXJRY
<br />FA —ER
<br />a,
<br />111 Ell 0., 4• END DEn..
<br />II EDGE GIST.
<br />SGOpAL.EXi. POOPS
<br />CASE HARDENED COIL
<br />e'OIC
<br />WINOOIVNOOPo I—PENED
<br />GARAGE DOOR BJCK
<br />1TDN. W,
<br />EXPANSION BOLT
<br />24"Q'C
<br />4-EMBED,.4—DTOIST..
<br />I, T,EEENOTE6
<br />NAIL IIII-ONG.
<br />STAGGERED
<br />INTO M480NRYICONC.
<br />TO MASONRY,WNC.
<br />WASHER
<br />3•EDGE OISi.
<br />WINDOW BUCK
<br />cA6E w1RDENED Con
<br />`_
<br />w— PAarENEo
<br />METAL —TO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />I.R. SEE NOTE 6
<br />NAIL „rs'LONG.
<br />STAGGERED
<br />INTO MASQVRY/ 0.
<br />MASONRY/GONG.
<br />REQUIREMENTS
<br />EXT. SWING DOOR
<br />(2)3I—A.
<br />"TAPCOM
<br />1R"EMBED, a"END.
<br />NON BEARING WON
<br />I- EXPANEON 4"EMBEO.4•E-
<br />2<OC
<br />&ICK2xM,SEENOTE6
<br />NO WASHER
<br />FASTEROIST.,1,
<br />OGE DIET.
<br />WALL TO CONC.GUB
<br />W/WASHER BOLT DIST., 3'ENEGIST.
<br />nNwaua •PAF ,re v 4 ro, Dlsr.,,rr
<br />PaoW6.,3e
<br />6TEEL NL-SEE WfW=EzR STAGGERED EEDGE GIST.
<br />raTEe
<br />1.SST�APLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NON OR THE SPACING DETAILEDABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE,
<br />W�
<br />I VA
<br />1441 N. RONALD REAGAN BLVD
<br />LONGWOOD, FL 32750
<br />PH: 407-77448078
<br />FAX: 407-7744078
<br />www.abdosigngroup.com
<br />N: 0003326
<br />eJ a O
<br />7N
<br />R
<br />w!
<br />//Gy
<br />V
<br />9VHDIV. de LOT:
<br />SILVERADO
<br />LOT #46
<br />BLK #18
<br />PROJECT
<br />04128.001-46181
<br />MODEL:
<br />4EHB
<br />rr2605-HAYDEN"
<br />GARAGE SWING:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />150 MPH EXP. B
<br />DRWT
<br />IN 07 20
<br />SCALE: 1/4"=1'-0"
<br />8tS N 1
<br />10