AV
<br />-LE END
<br />HIP RIOF
<br />ROOF WIND DESIGN PRESSURES
<br />N 10
<br />ZONE 1 = 8.97 PSF (19.97)
<br />ZONE 2 = 17.98 PSF (27.98)
<br />ZONES = 33.53 PSF (43.53)
<br />'A'- W-O' END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: "S"
<br />RISK CATAGORY: R
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT+- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16'
<br />O.S.B. OR 1/2' CDX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 5/8 CDX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4' O.C. AT SUPPORTED
<br />PANEL EDGES AND ed RING SHANK GUN NAILS
<br />AT 6' O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS 0 4' O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS W/ IN W OF GABLE
<br />FND
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN, LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />8d
<br />RING SHANK,
<br />2 V2'
<br />0.120,
<br />170,000
<br />RING RINGS
<br />SCREW SHANK
<br />PER INCH)
<br />8d
<br />SCREW SHANK
<br />2 1/2'
<br />0.120'
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664 TOP CORD BLOCKING AT W
<br />2, INTERNATIONAL STAPE, NAIL & TOOL O.C. MAX. IN FIRST 2 FRAMING
<br />ASSOCIATION (]SANTA) ESR-1539 SPACES AT EACH END.
<br />RAFTER OR TRUSS
<br />ROOF SHEATHING -.
<br />EXTERIOR SHEATHING
<br />USE 1/2' COX OR 7/16' O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4. O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4' O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT W O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />e
<br />Z W
<br />Z�
<br />LU
<br />Y
<br />Z U
<br />U)
<br />Z
<br />2
<br />8d RING SHANK GUN NAILS 0 4" O.C.
<br />TOP & BOTTOM EDGES B
<br />Z
<br />Z �
<br />Z) W
<br />(0 LL
<br />Z
<br />O o
<br />1
<br />/
<br />(7
<br />Noe
<br />Q
<br />Z
<br />ZN
<br />w
<br />(� W
<br />z
<br />a
<br />= S
<br />NO
<br />za
<br />z
<br />9a¢
<br />Lu
<br />Q
<br />y Z
<br />N W ¢ LU
<br />3L� w
<br />LULU L)
<br />nQ O
<br />_
<br />L
<br />W
<br />a
<br />z=
<br />_ F-
<br />a
<br />m 3
<br />BUILDING LENGTH L
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />8d RING SHANK GUN NAILS
<br />B W O.C. IN FIELD
<br />TYP. OCT. SHEOPING ATTACHMENT FOROOF SH H G O.S. .
<br />TO BE STRUCTURAL GRADE
<br />�--• ed RING SHANK GUN NAILS 0 12' O.C. IN
<br />FIELD or 8d x 2 1/2' SCREW SHANK
<br />PNEUMATIC SCREW -NAILS 0 12' O.7
<br />FIELD
<br />TYP. 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE. SIZE SHALL BE 3W.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD.
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 6%ABt ENTRAINED CONCRETE EXPOSED TO EARTH ORWFAT$R
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC 2017, SU EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BECWIMFERED 3l4'.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />BUILDING CODE REQUIREMENTS
<br />GRIPPE RS SILLS ETC. SHALL BE SOUTHERN PINE NO, 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF
<br />E
<br />FACI OR STRUCTURAL ANSI SPECIFICATION FOR THE DESIGN OF
<br />FOR STRUCTURAL CONCRETE, ACI
<br />PROVIDE 84AIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SlABS9N-GIiWND1MffRE INDICATED ON
<br />PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL
<br />L630-1
<br />MEMBERS 011,
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND RISC SPECIFICATIONS
<br />DRAVANGS SEAMS UPPEDSINCHES AND SEALED WITH ADHESIVE TAPE.
<br />TREATED. A
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NON-STRUCTURAL USES
<br />PRESSURE
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM -WORK:
<br />SHALL BE RATED TO RETENTION LEVELS OF 025 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBOR 2017, 681 EDITION, SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO SE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM Al BE, GRADE 85 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH Y CHAIRS SPACED 3'-0" OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND FASTENINGS' THE NFTRUSS DESIGNS SHALL SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA.O SEE NOTED FOR SHOP DRAWINGS,
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 601N MASONRY DEF
<br />FORM D E BARS E FRE
<br />ORMED FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />W/THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI- 14. 'DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND TPIAW(CA SCSI 1'
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf
<br />AND VERTICAL BARS SHALL LAP 6 X BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 pet TOP CHORD -nm-concurrent
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 04 BAR - 26' #6 BAR - 38'
<br />WOOD TRUSSES.
<br />10 pet BIM CHORD -noD IcumN
<br />#5 BAR - 30" #7 BAR - 42'
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 35' x 38" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1 On.
<br />paf TOP CHORD 20 paf TOP CHORD
<br />17 pef w/ ASPHALT SHINGLES) pef W/ No GYPCRETE)
<br />(7
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />et BTM CHORD 5 el RTM CHORD
<br />t0 p5 p
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: I Opef
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 pef
<br />WALL
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 pef
<br />WIND: DEAD LOAD SPEED -150 MPH 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS; UNINHABITABLE ATTIC WRHOItT STORAGE: 10pef, UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION Of EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING A3 CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />NTS: PASSENGER
<br />AND DECKS: 40p GUARDS AND HANDRAILS: GUARD COMPONENTS:
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />OFILL
<br />ROOMS:
<br />VEHICLE GARAGES: 50pe1, ROOMS OTHER THAN SLEEPING ROOM: 40pa1, SLEEPING ROOMS: 30pef, STAIRS:
<br />LEGA AGE N SEE,
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />g0pef
<br />MASONRY'
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />'SPECIFICATION MASONRY STRUCTURES' (ACI 630/ ASCE SITMS 402, BUILDING CODE REQUIREMENTS FOR
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE IWO-CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fYn = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />.
<br />RUNNING BOND UNLESS OTHERWISE NOTEDLAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS 70 TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER, IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALLPROVIDE A MINIMUM COMPRESSIVE STRENGTH OF WOO PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT,
<br />FOUNDATION/ SITE PREPARATION:
<br />'S"
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 pef, FOOTING
<br />TYPE'M' OR MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SU&GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 96 % OF THE
<br />SHALL BE 3/9' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />CELLS TO BE FILLED,
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />L
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING 70 MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />STRUCTURAL STEEL:
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 2S DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,SDO PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5' STRUCTURAL TERRACE SLAB
<br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' * PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MXING, TRANSPORTING, ETC.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE MX UNTIL R IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONNBHUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE WITH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS);
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER
<br />1.1/Z' FOR 96AND SMALLER
<br />2' FOR MI AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />314' FOR SLABS, WALLS AND JOISTS
<br />14/e' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />ASS, Fy - 36 W FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B,
<br />Fy = 46 kei. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy : 35 kai. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A326-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLICATKFI
<br />E.
<br />TYPE
<br />BPACIM3
<br />-I.-
<br />SIZE
<br />TYPE
<br />9PACwG
<br />REMARKB
<br />, IIPTFURPINGTO
<br />MASONRY/GONG.
<br />CABS HAFOENED.1
<br />NAI _L_
<br />B.
<br />GAMGEDWRBUCK
<br />TO MABONRYXXMIC.
<br />1/l'DIA.
<br />NOWABNER
<br />AFCON MASONRY
<br />T fgBTEI-Efl
<br />BOA:
<br />11lYEMEED., I•END OE:T.,
<br />I,2'EDGEDIET.
<br />E.D. AL. EXT.000R3
<br />CASE HAWENED C00.
<br />9. 6C
<br />WWDOWIDOOW FASTENED
<br />GARAGE ODOR-K
<br />12 DUN. WI
<br />I' EMBED.. I' ENO`
<br />1. PI', SEE NOTES
<br />NAIL112-G.
<br />E-EERED
<br />INTO MA30NRY�CCNC.
<br />TO MASONRYxxXJC.
<br />WASHEfl
<br />EXPANSION BOLT
<br />2I•gC
<br />3•EOOE DIET.
<br />wINDaW &!CK
<br />cABE HARDENED 001E
<br />P•oc
<br />W wr000w FASTENED
<br />MET-PAPTO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1x PT, BEE NOTE
<br />112'L014G.
<br />ETAGGERED
<br />I--flYF ,
<br />MABONRY/CONC.
<br />REQUIREMENTS
<br />E%T.9WwG DCOP
<br />(2)YtYOIA.
<br />TAPCOM
<br />1.
<br />11R'EMBED,YEM.
<br />NON.BEARING WOOD
<br />,R'° EXPANSION I'EMBED.I'END
<br />� QL
<br />BUCK 2A PT, BEE NOTE B
<br />NO WASHER
<br />FABTNER
<br />OIBT.,112' EDGE DIET,
<br />WAIL TOCOW, STAB
<br />W/ WASHER BOLT DST., e' EDGE DUST.
<br />2x Pt WwOOW &ICI BC PAf 121Q I. 4' END.D6T.,11IC
<br />P o-TEELCIX., BEE DIWI WAEHER aTAGGERED EDGE DIRT.
<br />NOTEI
<br />1LES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4, PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6,WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD
<br />LONGWOOD, FL 32750
<br />PH: 407-77443078
<br />FAX: 407-77
<br />WWW.abdesi -
<br />AA #: 00
<br />M
<br />i
<br />,
<br />F
<br />_�J
<br />XHLJHDIV. all LoT
<br />SILVERADO
<br />LOT #14
<br />BLK #18
<br />PROJECT#
<br />04128.002-14181
<br />MODELo
<br />4EAB
<br />"1672-ARIA"
<br />GARAGE 871ING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />150 MPH EXP. B