GABLE -ENO
<br />HIP RODF LPL
<br />ROOF WIND DESIGN PRESSURES
<br />NET(GROSS) ASCE 7-10
<br />ZONE 1 = 8.97 PSF (19.97)
<br />ZONE 2 = 17.98 PSF (27.98)
<br />ZONE 3 = 33.53 PSF (43.53)
<br />"A"= W-O" END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: "B"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT 10.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16"
<br />O.S.B. OR 12" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 5/8 CDX EXT. PLYWOOD, WITH Sd RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND Sd RING SHANK GUN NAILS
<br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS W 4" O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS WI IN 4' OF GABLE
<br />END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />8d
<br />RING SHANK
<br />212
<br />0.120"
<br />iT00W
<br />RING"
<br />SCREW SHANK
<br />i6-2I RINGS
<br />ER NCH)
<br />8d
<br />SCREW SHANK
<br />2 112"
<br />0,120"
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION ([SANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 112" CDX OR 7/16" O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />J
<br />ZUJ
<br />Z
<br />W
<br />f)
<br />QZQd
<br />Sd
<br />CD
<br />E
<br />Go
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />TOP & BOTTOM EDGES
<br />z9.
<br />Z
<br />� W ,
<br />Z z
<br />SSQ U
<br />.
<br />y O .
<br />z
<br />z
<br />Y
<br />C7 .
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER TRUSS
<br />ROOF CHIZFAT""
<br />11
<br />Emmov1BUILDING LENGTH
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />8d RING SHANK GUN NAILS
<br />6" O.C. IN FIELD
<br />8d RING SHANK GUN NAILS @ 12" O.G. IN
<br />FIELD or 8d x 2 12" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS Q 12" 0.6w(N
<br />FIELD J\
<br />FYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 630-13/ASCE 5.13 ANSI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD, DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />ALL AGGREGATE USED IN CONCRETE SHALL
<br />;4'.
<br />WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W.
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />8d RING SHANK GUN NAILS
<br />6" O.C. IN FIELD
<br />8d RING SHANK GUN NAILS @ 12" O.G. IN
<br />FIELD or 8d x 2 12" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS Q 12" 0.6w(N
<br />FIELD J\
<br />FYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 630-13/ASCE 5.13 ANSI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD, DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />ALL AGGREGATE USED IN CONCRETE SHALL
<br />;4'.
<br />WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC ., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Flo = 1100 PSI ANDA MODULUS OF
<br />PROVIDE 64AL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SUB,SON-GROUND VAIERE INDICATED ON
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />DRAWINGS. SEAMS UPPED B INCHES AND SEALED WITH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE TREATMENT: UM
<br />ET).
<br />FORMWORK:
<br />WOO FOR STRUCTURAL USEPRESERVATIVE
<br />CORROBORATED ETRAHEEORALNNTIION(00 THAT SHALL BE TREATED FORSA
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, SM EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND W000 COLUMNS WITH 2z STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP 12.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS,
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' THE NFLO TRUSS DESIGNS SHALL SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />E O
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS,
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0,036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A815 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />W/ THE TYPICAL SENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND TPIAVTCA SCSI 1"
<br />IRA
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 f
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 psi TOP CHORD - oonc01fen1
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: A4 BAR - 25" AIB BAR - 36"
<br />WOOD TRUSSES.
<br />10 psf BTM CHORD -non-corm-t
<br />MI5 BAR - 30' p7 BAR - 42"
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36" x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982.
<br />pai 70P CHORD psf TOP CHORD
<br />(7 psf ASPHALT SHINGLES) psf w/ No GYPCRETE)
<br />Q (1
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 psf BTM CHORD 5 5 p psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1 OpV
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED =150 MPH 3. SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS, DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE 7.10 (FBC R2017) EXPOSURE B, RISK CATEGORY ILA
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />WITH BALCONIES (EXTERIOR)
<br />STORAGE: HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS:
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />: 40p
<br />AND DECKS: IOpsL GUARDS AND HANDRAILS: 200pef, GUARD IN -FILL COMPONENTS: SOpaf, PASSENGER
<br />NTS:
<br />WITHOUT THE APPROVAL Of THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHAH
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30paf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40psf
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE,
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM G90, GRADE = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS, GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB,
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SWILL NOT EXCEED S d- PRDRTO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MIXING, TRANSPORTING, ETC.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MNQMUM TIME ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE WITH THE ABOVE.
<br />REWIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A TFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS):
<br />e. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />1-12' FOR 05AND SMALLER
<br />Y FOR A3 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SLABS, WALLS AND JOISTS
<br />1-12' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED,
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O
<br />STRUCTURAL STEEL:
<br />THE MATERIAL FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy = 36 ksl FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B,
<br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B. TYPE E OR S. Fy = 35 K.I. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD,
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLIGTKKJ
<br />911E
<br />TYPE
<br />9PACWG
<br />REMARN9
<br />APPLIGTKKN
<br />9QE
<br />TYPE
<br />SPACING
<br />REIMPo(9
<br />1-FURRNGTO
<br />CASEHARDENED ODx
<br />GARAGE DOORBUOC
<br />M"DLA.
<br />TAPCON MASONRY
<br />11?EMBED.,PENO DGr,
<br />MA90NRYl CONC.
<br />NML 11?LONG.
<br />8`OIC
<br />TO MA9pNRYlCONC.
<br />NO WASHER
<br />FASTENER
<br />9'WC
<br />11?EDOE018T.
<br />SGD.�AL. EXT, DOORS
<br />CASEHARDENEDCOIL
<br />S"WC
<br />WINDOWIDOORIFASTENED
<br />GARAGEWORB-
<br />117 DlA. WI
<br />E%PANSAN BOLT
<br /><" EMBED., 4-DIST.,
<br />,SEEWTC.
<br />NAIL 11?LONG.
<br />STAGGERED
<br />INTO MA90NRYIWNC
<br />TOIM90NRYIfiVC.
<br />WASHER
<br />0"EDGE DIST,
<br />wuro wcK
<br />CAGE HARDENED 0-
<br />wwoaWiDaawFAsrENEo
<br />M-STRV TO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />PT, SEE NOTE a
<br />NNLI1?MONO.
<br />ST-IrED
<br />INTD MA90M G..
<br />MASONRvr CANc.
<br />REQUIREMENTS
<br />ExT. BWWG DOOR
<br />R)M1-
<br />TAPC01'
<br />1P WC
<br />11?EMBED, a•END.
<br />NONBEMING WOOD
<br />trz- EXPA-AN 1'EMBED.1'END
<br />2Y OIC
<br />BUCK 9I PT, SEE NOlE9
<br />NO WAILER
<br />FA9TNER
<br />D19T„11?EDGE D6T.
<br />WALL TO CONC, IMPS
<br />W/WASHER BOLT DIST.,YEOGEDIST.
<br />91PT WINL BUCK 0.138'PAFn11/d' PdC 1•ETA. DI _it?
<br />PT TO9TEECOL.. SEE .-ER STAGGERED EDGE PST.
<br />NO ES
<br />NOTES
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />T 8
<br />1441 N. RONALD REAGAN'
<br />LONGWOOD, FL 32751
<br />PH: 407-7744078
<br />FAX: 407-774-4078
<br />W W W.8bd"gngmup.COD1
<br />L AA 8: 0003325 /
<br />LDRAFTING BY:
<br />A.B. DESIGN GROUP
<br />DRAFTING INC.
<br />EAUMONT CENTER BLVD.SUITE 1004
<br />MPA, FLORIDA 33834PH: 813886.2628AX: 813886.2802
<br />Iltmmv. !e TAT:
<br />SILVERADO
<br />LOT #12
<br />BLK. #13
<br />P1tOJSCTp
<br />03719.000-12131
<br />MODEIt
<br />2795-F
<br />GARAGE 99WING:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />150 MPH Pp.
<br />B
<br />JUL
<br />Dw 7/07/20
<br />aCALE: 1/4"=1'-0"
<br />II, S N 1
<br />
|