HVAC NOTES <br />I. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH PROPER CLEARANCE, FOR SERVICING, PER <br />MFG. REQUIREMENTS. <br />2, ALL DUCT SYSTEMS INSTALLED IN NON -CONDITIONED AREAS SHALL BE CONSTRUCTED OF A VALUE <br />OF NO LE56 THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FAB ! MASTIC. AND <br />INSTALLED AS PER FBCR 5TH EDITION (2014) MECHANICAL BLDG. CODE SECTION 603. <br />3. ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER NFPA 90A 2-3.1 <br />4. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />5. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SHALL_ BE CONSTRUCTED OF SMOOTH GALv. METAL. <br />OR OTHER MATERIALS AS PER FBCR 5TH EDITION (2014) MECHANICAL CODE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORh15 SHALL BE CONSTRUCTED IN ACCORDANCE TO FBCR 5TH EDITION <br />(2014) MECHANICAL CODE 603.1 <br />'l. BATHROOMS CONTAINING BATHTUBS, SHOWERS, 5PA6 AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH FBCR 5TH EDITION (2014) MECHANICAL CODE <br />SECTION 403. <br />8. ALL EXHAUSTED BATH ROOMS, SHALL HAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EQUAL AIR EXHAUSTED. <br />9. ALL FIRE RATED CEILINGS AND WALLS SHALL HAVE AN APPROVED FIRE OR FIRE/SMOKE <br />DAMPER'S LOCATED AT CEILING OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOORS TO <br />RESET DAMPER ALL DAMPERS SHALL BE INSTALLED TO MPG. RECOMMENDATIONS AND FBCR 5TH <br />EDITION (2014) MECHANICAL CODE SECTION 601. <br />10. GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH BALANCING DAMPERS. <br />IL DRYER BOOSTER TO BE A FANTECH DBF BOOSTER FAN OR EQUAL. <br />FANTECH DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX. SIX ELBOWS. <br />NOTE <br />ALL HVAC TO HAVE PROPER <br />PANS W/ DRAINS <br />ATTIC <br />CEILING F--i— -- <br />EXTERIOR WALL <br />PLENUM T_1-- <br />AIR RETURN <br />SUCTION AND LIQUID <br />AIR SUPPLY y <br />REFRIGERANT LINES <br />�y <br />AIR HANDLER <br />-- <br />EXTERIOR WALL <br />'! <br />3/4' PVC CONDENSATE DRAIN LINE <br />EVAP. TRAY V <br />PVC SLEEVE TO LINES BELOW SLAB <br />-- <br />REFRIGERANT LINES TO <br />PLATFORM RETURN <br />CONDENSING UNIT <br />-------- <br />TRAP DRAIN LINE AND TERMINATE <br />IN AN APROVED DRAIN, AS PER <br />FBGR 5TH EDITION (2014) <br />MECHANICAL BLDG. CODE <br />SECTION 3012.1.1 <br />HVAC <br />DRAINS <br />SCORIATED NICKEL <br />BRONZE FL. PL. <br />BRASS PLUG <br />/ I I <br />INSIDE I I <br />CAULK J <br />y 11 <br />—4-- /— — — <br />FIN. FLOOR <br />OR WALL <br />I <br />FITTING OR EXTENSION TO <br />SOIL OR WASTE AS <br />REQUIRED <br />WADE 8240-K JOSAM 56000 <br />SERIES NICKEL BRASS TOP <br />P.v.0 OPTI/SPEC <br />IV. SEE__ <br />.,TE PLAN <br />nFL00R SLAB CLEAN -OUT (TYP. ) <br />�1J NTS <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR I WAY DIFFUSER <br />— <br />SOLID LINE- SUPPLY TRUNK <br />--- <br />BROKEN LINE- RETURN TRUNK <br />l <br />BALANCING DAMPER OR OBD <br />O <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />THERMOSTAT <br />m <br />PASS-THRU AIR GRILL <br />SECURE STRAP TO CONC. CONDENSER <br />W/ (2)-3/I6'X2' TAPCONS UNIT SIMP50N WB ROLL STRAP <br />OR EQUAL <br />4' CONCRETE SLAB SECURE STRAP TO UNIT W/ (2) <br />"&XI 1/4' 5-IT. MTL. SCREWS <br />CONDENSER UNIT <br />CONNECTION TO PAD <br />NOTE: MAIN COND. DRAIN 3/4' DIA. <br />OVER HEAD 0 12' FROM STRUCTURE <br />COUNTERSUNK <br />G.O. PLUG <br />SEE SPEC. <br />_ — l- — — — — — — — — — <br />m <br />\\\\ I'-8'XS' CONC. <br />FIN. GRADE' <br />OR PAVING" - <br />- -Y� FITTING OR <br />I EXTENSION TO SOIL <br />1 _ = OR WASTE AS <br />— REQUIRED <br />I I <br />y i I <br />III y ,INV. SEE <br />`'�------— —SITE PLAN <br />(EXT. GROUND CLEAN -OUT (TYP.) <br />N 5 <br />FIRST FLOOR MECHANICAL PLAN <br />PROGRESSIVE AIR SYSTEMS 05/20/14 <br />A R C R I T E C T S <br />6 <br />Design <br />Grou ... <br />41 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-774-4078 <br />www.abdwigngroup.com <br />AA #: 0003325 A <br />y <br />0 <br />C <br />y <br />O <br />F <br />4 <br />C <br />4 <br />__ <br />8UDDIV. as IJ07 <br />SILVERADO <br />LOT 4 <br />BLK 2 <br />O04128 000 04002 <br />MODIM <br />4EBB <br />"1828- CALI" <br />GARAGE B'WMG: <br />RIGHT <br />PAGE: <br />MECHANICAL <br />PLAN <br />150 MPH EXP. B <br />ARCHR'ECT <br />STATE OF FLOPMA <br />DPRINT 'I <br />10/21/16 <br />DIEM 1' <br />