CJ <br />GABLE. END r— <br />HIP ROOF T w <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 52.70 PSF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e = 60.50 PSF (70.50) <br />ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2n = 69.80 PSF (79.80) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2r = 69.80 PSF (79.80) <br />"A"= 4' -0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT. -/_ 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/37' STRUCTURAL SHEATHING <br />EXP 1 4020) FOR CEMENTITIOUS TILE AND METAL ROOFING USE MIN. <br />( <br />19/32" STRUCTURAL SHEATHING EXP 1 (40/20).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />IuoFBBFUTc <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STIR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />21/Z' <br />0,131 <br />F1667 <br />SC E SHANK <br />170,000 <br />RING <br />(i-20 RINGS <br />6 <br />RSRS-03 <br />8d <br />RING SHANK, <br />23/8" <br />0.113 <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />2316' <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />KHYI tKU IK —� <br />F SHEATHING --� � ROOF � <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Sd RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL U BUILDING LENGTH U <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADO'L DROPPED <br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />16'O.C. IF NO DROPPED GABLE END, ATTACH 2X4 #2 SYP <br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />ZONE 1: 10d NAILS C 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />ZONE 2e, 2n, 2r: I OdNAILS ®4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 10d NAILS C 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />WRINGS— GUN NAILS 04" O.C. <br />,. TOP 4 BOTTOM EOGEB ,. <br />l/ ' <br />VP FXT RHFATHING ATTACHMF <br />�w <br />o <br />8 <br />Ho <br />$M <br />■���s00 <br />ult 11 111 <br />101 <br />11 <br />mmmmmL <br />iilull <br />- 1. RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING \ , <br />.".'DECK SCREWS 0 6"-8" O.C. MAX <br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING ` <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C330314 MAXIMUM AGGREGATE SIZE SHALL BE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE fi%AIR ENTRAINED CNCRETE EXPOSEDTOEARTH ORWEATHER <br />IENO <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7M EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE 70 BE CH4MFERED 314°. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb = 1100 PSI AND MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR SORRIER MEMBRANE UNDER All SLABS -ON -GROUND WHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVETAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION, RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN'A° OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7tn EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP 02. <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIETDOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF'. LIVE LOAD FLOOR: LIVE LOAD 40 Psf <br />20 psf TOP CHORD no—curfent <br />10 psf BTM CHORD-n—onc—m <br />DEAD LOAD DEAD LOAD <br />15 pH TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ASPHALT SHINGLES) (10 psfw/ No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />BALCONY LIVE LOAD 60 psf <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED =160 MPH 3-SECOND GUST <br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY 10 <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED <br />STORAGE: 20P'f, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />AND DECKS: 40Psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />40Psf <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A816 <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO, UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36' <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 36' % 38' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />RUN REINFORCING BARS CONTINUOUSLY. LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS, STAGGER SPLICES WHEREVER POSSIBLE. <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />MASONRY: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAVANGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BV <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />LEVATIONS DIMENSIONS ETC. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY LENGTH ELEVATIONS, <br />' <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />OF THE DELEGATED TRUSS ENGINEER. WINO UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI, BLOCK SHALL BE PLACED USING <br />ALL CLADDING WAND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. ALL INSTANCES, THE CONTRACT <br />ASTM C476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BEE PLACED W/A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 FOOTING <br />PM' <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXES AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTARJOINTS <br />EXCAVATIONS AND SLAB DE SHALL BE COMPACTED A DRY DENSITY OF AT LEAST THE <br />SHALL BE BE THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />795%T E <br />DR <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0.1557. TREAT ALL <br />MAXIMUM A <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SWILL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />STRUCTURAL STEEL: <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB, <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5" N- PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIME STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A TFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATION$); <br />B. FOR CONCRETE EXPOSED TOEARTH ANDIOR WEATHER: <br />1.1/2' FOR ASAND SMALLER <br />2" FOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4° FOR SLABS, WALLS AND JOISTS <br />1-iQ" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M FY = 36 W FOR ANGLES PLATES AND WSRAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M GRADE B F = 48 Iwi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE BTYPE E OR S F = <br />Y Y <br />35 kei. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP, <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, J-BOLTS ARE TO BE STEEL <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />A—CATON <br />st¢ <br />_clNG <br />APPucAnON <br />svE <br />TYPE <br />REMA,:Ks <br />#PTFURPoNOTO <br />INA6CNRY/GONG <br />6E HARDENED COIL <br />GNAILI t?LONG. <br />0. <br />GARAGE DOOR BULL( <br />ASONRY.CVNC. <br />OVi <br />ASHER <br />APWN MgSONRY <br />FASTENER <br />9 On; <br />?EMBED' END <br />EDST. <br />SO., AL E%i DOORS <br />I T, SEE WTE6 <br />G16E HARDENED CCIL <br />NNLI I?LONO. <br />9 <br />YANDOW/OpIX!/FASTENED <br />INTOMA60NRYICONC. <br />PRAGE DOOR BLCI( <br />AGNRY�NC. <br />b6?q <br />wr wA3NER <br />E%PAN&ON BOLT <br />FgC(3Id"DIN <br />24 OIC (1?DA) <br />d•EMBEO.. d•ENDDST., <br />YECGE q9i. <br />veNoow BUCK <br />cA9E HARDENED WIL <br />9•Gc� <br />`MNDOKYOpON FASTENED <br />Eru sTRM TO <br />CONTACT THIS ENGINEER FOR SPACING <br />PT.9EE NOTE6 <br />WBLI I?LONG. <br />AG GERED <br />INTOMASONRY,CUNC. <br />nMiASDNRYrcoNc. <br />REQUIREMENTS <br />IXT. SKINS DOOR <br />BUCK h PT, BEE NOTE 6 <br />(1)yf 8•W1 <br />NO WggHER <br />'TAPCIkY <br />10 aC <br />I IR"EMBED, B END. <br />DST., I t? EMiE DST. <br />NON9EWIN0 WOOD <br />qLl TO GONC.9lFB <br />EXXGN Di OC ISEMBED. <br />SHER BOLT DST., 3• EDGE DST <br />"TOwN00W BUIX G.13B° PAF e d D9T.,1 I? <br />SNEELCOL., SEE W/WASHER STAGGERED ENOEGGE DST. <br />OTEfi <br />1. S � PLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />8. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED Wl TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32780 <br />PH: 407-774.6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />_. AA #: 0003325 <br />p <br />M <br />i6 <br />rr <br />IND <br />S <br />D <br />6 <br />SUSDM Ae LOT <br />ABBOTT PARK <br />LOT #24 <br />BLK. #9 <br />PROJECT* <br />04181.000-24091 <br />MODEU <br />4EBB <br />311828—CALIf1 <br />GARAGE SWING: <br />LEFT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />7 <br />�"0XAWkrroA"CRA) <br />WW <br />PDAINT R21 <br />TE: 8 /14 / <br />ff <br />1/4"=1'-0"N1 <br />